Operating InstructionsVEGAFLEX 67-200 … +400 °CFoundation FieldbusDocument ID:32314Guided Microwave
TSd1h1h2d21L2L1Fig. 2: Interface measurement1 Reference planed1 Distance to the interfaced2 Distance to the levelTS Thickness of the upper medium (d1
The data for power supply are specified in chapter "Technical data".The optional heating requires its own operating voltage. You can finddetai
4 Mounting4.1 General instructionsMake sure that all parts of the instrument exposed to the process, inparticular the sensor element, process seal and
Fig. 3: Measures against moisture penetrationThe reference plane for the measuring range of the sensors is thesealing surface of the thread or flange.K
keep in mind that measurement down to the tip of the probe is notpossible. The exact value of the min. distance (lower dead band) isstated in chapter
more than 1 m (3.281 in) length, you must secure the probe byfastening a suitable insulated brace or guy directly above the end ofthe rod.If there is
5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o
In systems without potential equalisation, connect the cable screendirectly to ground potential at the power supply unit and at the sensor.In the conn
7 Insert the wire ends into the open terminals according to the wiringplanFig. 7: Connection steps 6 and 78 Press down the opening levers of the termi
I²C34512DisplayTyp:1 2 5 6 7 8 BusSim.Fig. 8: Electronics and connection compartment, single chamber housing1 Plug connector for VEGACONNECT (I²C inte
Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .
132Display1 2 5 6 7 8I2CFig. 10: Electronics compartment, double chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Internal connection
I2C11 2Fig. 12: Wiring plan, double chamber housing1 Voltage supply, signal output5.5 Wiring plan - version IP 66/IP 68, 1 bar12Fig. 13: Wire assignme
6 Set up with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,
Fig. 14: Insert indicating and adjustment moduleNote:If you intend to retrofit the instrument with an indicating and adjustmentmodule for continuous me
6.3 Adjustment system2311.1Fig. 15: Indicating and adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mo
6.4 Setup stepsAfter VEGAFLEX 67 is connected to voltage supply or after voltagerecurrence, the instrument carries out a self-check for approx. 30seco
Dielectric valueUpper medium0003 Enter the dielectric figure (DK value) of the upper medium andconfirm with [OK].Save the settings with [OK] and move to
ApplicationLiquidStandard(DK ≥ 2)Measured products have different reflective properties that depend onthe dielectric figure (dielectric constant). For th
1 Move from the measured value display to the main menu bypushing [OK].2 Select the menu item "Service" with [->] and confirm with [OK].No
The following safety-relevant data are not read out or written:l HART model PINl Sensor length/Sensor typel False signal suppressionCopy sensor dataCo
8 Maintenance and fault rectification8.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .358.2 Remove interferences. . . . . . .
6.5 Menu schematicBasic adjustment1▶Basic adjustmentDisplayDiagnosticsServiceInfo1.1Upper mediumDielectric figure of the uppermediumenter/calculate1.2M
Service4Basic adjustmentDisplayDiagnostics▶ServiceInfo4.1Sensor5.00 m(d)Rod4.2SimulationStart simulation?4.3ResetSelect reset?4.4Unit of measurementm(
6.6 Saving the parameter adjustment dataWe recommended noting the adjusted data, e.g. in this operatinginstructions manual, and archiving them afterwa
7 Set up with PACTware and other adjustmentprograms7.1 Connect the PC312Fig. 16: Connection of the PC via VEGACONNECT directly to the sensor1 USB cabl
Necessary components:l VEGAFLEX 67l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system7.2 Parameter adjustmen
8 Maintenance and fault rectification8.1 MaintenanceIf the instrument is used properly, no special maintenance is requiredin normal operation.8.2 Remov
Error Cause RectificationIncorrect termina-tionCheck termination at the beginningand end points of the bus and termin-ate, if necessary, according to t
If there is no electronics module available on site, one can be orderedfrom the VEGA agency serving you.The new electronics module must be loaded with
Connect the signal conditioning instrument to power supply andprovide the connection from the PC to the instrument via the interfaceadapter. Start PAC
9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper
1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as
10 Supplement10.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts - version -200 … +400°C (-328 … +752°
- Rod: ø 16 mm (0.63 in) approx. 1600 g/m (17 oz/ft)- Cable: ø 6 mm (0.236 in) approx. 170 g/m (1.8 oz/ft)- Gravity weight approx. 730 g (25.8 oz)Prob
24351Fig. 18: Measuring ranges of VEGAFLEX 67 - coax version1 Reference plane2 Probe length3 Measuring range (default setting refers to the measuring
2435124531Fig. 19: Measuring ranges of the VEGAFLEX 67 - rod and cable version1 Reference plane2 Probe length3 Measuring range4 Upper dead band (see d
10 m (32.82 ft)11 m (36.09 ft)12 m (39.37 ft)13 m (42.65 ft)14 m (45.93 ft)15 m (49.21 ft)16 m (52.49 ft)17 m (55.77 ft)18 m (59.06 ft)23 m (75.46 ft)
TSd1h1h2d21L2L1Fig. 21: Interface measurement (interface is between L1 and L2)1 Reference planed1 Distance to the interface (Secondary Value 2)d2 Dist
interface.Depending on the installation conditions, there canbe deviations which can be rectified with anadaptation of the adjustment or a change of th
L0-10 mm (-0.394")10 mm (0.394")0,1 m (3.937")0,15 m(1.968")1 1Fig. 24: Deviation VEGAFLEX 67 in coax version1 Dead zone - no meas
21-100°C(-148°F)-200°C(-328°F)100 bar(1450 psig)200 bar(2900 psig)300 bar(4350 psig)400 bar(5800 psig)380 bar(5510 psig)350 bar(5070 psig)0°C(32°F)200
Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 barCable entry/plug4)- Single chamber housing l 1 x cable gland M20 x 1.5 (cable: ø
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist
- Min. bending radius 25 mm (0.984 in) with 25 °C (77 °F)- Diameter approx. 8 mm (0.315 in)- Colour - standard PE Black- Colour - standard PUR Blue- C
ApprovalsInstruments with approvals can have different technical data depending on the version.That's why the associated approval documents have t
10.2 Foundation FieldbusBlock diagram, measured value processingThe following illustration shows the Transducer Block (TB) and Function block (FB) in
Diagram, adjustmentThe following illustration shows the function of the adjustment.Secondary_value_1CalibrationLowest PointCalibrationHighest PointSen
l secondary_value_2- This is the distance value (sensor_value) with the status of the transducer block- It is the input for the AIFB when CHANNEL = 3
- Min./Max. adjustment: this is the value of level at "Calibration Lowest Point". The unit isdefined in "level_unit"- When writing
10.3 DimensionsThe following dimensional drawings represent only an extract of thepossible versions. Detailed dimensional drawings can be downloadedon
Aluminium housing in protection rating IP 66/IP 68, 1 bar120 mm (4.72")~ 105 mm (4.13")116 mm (4.57")~ 150 mm (5.91")ø 84 mm (3.31
VEGAFLEX 67, rod, cable version (-200 … +400 °C/-328 … +752 °F)SW60G1½ /1½ NPTø 16mm(5/8")ø 30mm(1 3/16")ø 6mm(15/64")L292mm (11 1/2&qu
VEGAFLEX 67, coax version (-200 … +400 °C/-328 … +752 °F)G1½ / 1½ NPT ø 42,4 mm(1.67")L 292 mm (11.45")57 mm(2.24")35 mm(1.38")SW
2.5 CE conformityThis device fulfills the legal requirements of the applicable ECguidelines. By attaching the CE mark, VEGA provides a confirmationof su
10.4 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only
VEGAFLEX 67 • Foundation Fieldbus 6110 Supplement32314-EN-120329
62 VEGAFLEX 67 • Foundation Fieldbus10 Supplement32314-EN-120329
VEGAFLEX 67 • Foundation Fieldbus 6310 Supplement32314-EN-120329
VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9
3 Product description3.1 StructureThe scope of delivery encompasses:l Level sensor VEGAFLEX 67l Documentation- this operating instructions manual- Ope
123Fig. 1: VEGAFLEX 67 - cable version with plastic housing1 Housing cover with integrated indicating and adjustment module (optional)2 Housing with e
It is designed for industrial use in all areas of process technology andcan be used in liquids.High frequency microwave impulses are guided along a st