TIB • Technical Information • Operating Instructions
VEGATROL 20 Ex
Fail safe overfill
protection for
pressurized vessels
storing liquid gas
VEGA Grieshaber KG
Electronic level measurement
Am Hohenstein 113
Postfach 11 42
D-77757 Schiltach/Schwarzwald
Phone 0 78 36 / 50 - 0
Fax 0 78 36 / 50 201
VEGATOR 526W Ex
on
Approved acc. to the
VdTÜV-information
"Overfill protection" 100
no. TÜV.ÜS.94-35
liquid gas PN 25
Corresponds to the
requirements to
component tested overfill
protections of TRB 801,
no. 25
Corresponds to the
requirements of
DIN V 19250 AK 5
Conformity certificates
PTB-no. Ex-94.C.4035 X
BVS-no. 93.C.2015 X
Vue de la page 0
1 2 3 4 5 6 ... 19 20

Résumé du contenu

Page 1 - VEGATROL 20 Ex

TIB • Technical Information • Operating InstructionsVEGATROL 20 ExFail safe overfillprotection forpressurized vesselsstoring liquid gasVEGA Grieshaber

Page 2 - Contents

VEGATROL 20 Ex102 Technical InformationL1: length of the concentric tube andthe rod electrodeL2: length of the tuning fork sensor(concentric tube and

Page 3 - 1 Introduction

VEGATROL 20 Ex112 Technical Information45°ø kø Db90°d2D = outer flange diameterb = flange thicknessk = hole circled2= diameter of holes2.5.2 FlangesTh

Page 4 - 2 Technical Information

VEGATROL 20 Ex12Sensor 112 324681220282422101416183032zz24681220282422101416183032dd24681220282422101416183032d b zE Ex i262N (-)488101820d

Page 5 - VEGATOR 526 W Ex

VEGATROL 20 Ex131232 Technical Information2.6.2 VEGATROL 20 system sensorInner view after removing the coverPlastic cover (visible afterremoving the o

Page 6 - 2.3.2 Additional switch point

VEGATROL 20 Ex142 Technical Information2.7 Mounting instructions andregulationsGeneral instruction for electrical connectionThe electrical connection

Page 7 - 2.4 Technical data

VEGATROL 20 Ex151E2E2E1E1A2A2A1A1A1A2A2A1E2E2E1E1212Typ B62-27Typ B62-27Typ B62-27GTyp B62-27G2 Technical Information2.8 Connection examples for o

Page 8 - P3 P4 P5

VEGATROL 20 Ex16Pre-requirements for set-up- the sensor VEGATROL is installed in its final positionand the tuning fork is not covered- the failure LED

Page 9

VEGATROL 20 Ex174 Supplement3.3 OperationIf in case of overfilling, the tuning fork is covered up to theswitch point with the liquid gas, the level re

Page 10 - 2.5 Dimensional drawings

VEGATROL 20 Ex184 Supplement4.2 Calculation information for sensor lengthThe determination of the sensor length must be generally made with the respec

Page 11 - 2.5.2 Flanges

VEGATROL 20 Ex194 Supplement4.3 General instructions for the use ofoverfill protectionsApplication of a liquid gas overfill protection (ÜFS) is tomoni

Page 12 - 2.6 Electrical connection

VEGATROL 20 Ex2ContentsContents1 Introduction1.1 Contents of the instruction manual ...

Page 13

Technical data subject to alterations 2.17 749 / Sept. '94VEGA Grieshaber KGElectronic level measurementAm Hohenstein 113Postfach 11 42D-77757 Sc

Page 14 - 2.7 Mounting instructions and

VEGATROL 20 Ex31 Introduction1 Introduction1.1 Contents of the instruction manualThis Technical Information / Operating Instructions(T.I.B.) contains

Page 15

VEGATROL 20 Ex42 Technical Information2.1 Product descriptionGeneralVEGATROL 20 for liquid gas consists of:- VEGATROL 20 system sensor- signal conditi

Page 16 - 3 Mounting and set-up

VEGATROL 20 Ex52.2 Configuration of an overfill protectionStorage vessels in liquid gas plants of group A, B, C and DThe overfill protection VEGATROL

Page 17 - 4 Supplement

VEGATROL 20 Ex622 Technical Information2.3 Configuration of a measuring system2.3.1 Continuous level measurementSensor VEGATROL 20 VEGATROL 20 VEGATRO

Page 18 - Example: cylindrical tank

VEGATROL 20 Ex72.4 Technical data2.4.1 Signal conditioning instrument VEGATOR 526 W ExPower supplyOperating voltage Unenn= 24 V AC (20 … 28 V), 50 / 6

Page 19

VEGATROL 20 Ex8Electrical protective measuresProtection unassembled IP 00installed in Carrier Type 596 Ex with Ex-modulefront completely equipped ...

Page 20

VEGATROL 20 Ex92 Technical InformationMechanical dataMaterial Mounting parts Stainless steel1.4571 (V4A)Extension tube Stainless steel 1.4571 (V4A)Tun