Page 1 - Operating Instruction

Operating InstructionsVEGAPULS 654 … 20 mA/HART two-wireRadar

Page 2 - Contents

With the serial number, youcan access the delivery data of theinstrument viawww.vega.com, "VEGA Tools" and "serial numbersearch".

Page 3

3.4 Packaging, transport and storageYour instrument was protected by packaging during transport. Itscapacity to handle normal loads during transport i

Page 4 - 1 About this document

4 Mounting4.1 General instructionsSelect an installation position you can easily reach for mounting andconnecting as well as later retrofitting of an i

Page 5 - 2 For your safety

1 32100%0%4Fig. 3: Measuring range (operating range) andmax. measuring distance1 full2 empty (max. measuring distance)3 Measuring rangeInformation:If

Page 6 - 2.7 Fulfillment o

1Fig. 4: Position of thepolarisation plane with VEGAPULS 651 Marking holeMake sure that all parts of the instrument in contact with the measuredproduc

Page 7

When mounting VEGAPULS 65, keepa distance of at least 500 mm(19.69 in) to the vessel wall. If the sensor is installed in the center ofdished or round

Page 8 - 3 Product description

Fig. 6: Vessel with conicalbottomDo not mount the instruments in or above the filling stream. Make surethat you detect the product surface, not the infl

Page 9

Fig. 8: Recommended socket mountingIncase of very big socket diameters, the active antenna part can beslightly recessed in the socket. The following r

Page 10 - 3.3 Operation

Fig. 10: Cover smooth profileswith deflectorsIf there are agitators in the vessel, a false echo storage should becarried out with the agitators in motio

Page 11 - 3.4 Packaging, trans

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Page 12 - 4 Mounting

Contents1 About thisdocument1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . . .

Page 13 - 28437-EN-090305

Caution:No grease should be used when screwing the NPT cable gland orsteel tube into the threaded insert. Standard grease can containadditives that co

Page 14 - 4.2 Mounting instructions

7 Insert the wire ends into the open terminals according to the wiringplanFig. 12: Connection steps 6 and 78 Pressdown the opening levers of the termi

Page 15 - > 500 mm

55551 243Fig. 13: Material versions, single chamberhousing1 Plastic2 Aluminium3 Stainless steel, investment casting4 Stainless steel, electro-polished

Page 16

I2CDisplay11 2 56 7 8Fig. 15: Wiring plan, single chamberhousing1 Voltage supply/Signal output5.4 Wiring plan, double chamber housingThe following ill

Page 17

132Display1 2 5 6 7 8I²CFig. 17: Electronics compartment, double chamberhousing1 Plug connector for VEGACONNECT (I²C interface)2 Internal connection c

Page 18

I2C11 2Fig. 19: Wiring plan, double chamberhousing1 Voltage supply/Signal output5.5 Wiring plan double chamber housing Ex d1 2 345Fig. 20: Doublechamb

Page 19 - 5 Connecting to power supply

132Display1 2 5 6 7 8I²CFig. 21: Electronics compartment, double chamberhousing1 Plug connector for VEGACONNECT (I²C interface)2 Internal connection c

Page 20 - 5.2 Connection procedure

11 2Fig. 23: Wiring plan doublechamber housing Ex d1 Voltage supply/Signal output5.6 Wiring plan - version IP 66/IP 68, 1 bar+-12Fig. 24: Wireassignme

Page 21

6 Set up with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,

Page 22

Fig. 25: Insert indicating andadjustment moduleNote:If you intend to retrofit the instrument with an indicating and adjustmentmodule for continuous mea

Page 23

7.3 Parameter adjustment with AMS™ and PDM .. . . . . .427.4 Saving the parameter adjustment data . . . . . . . . . . . .428 Maintenance and fault rec

Page 24

6.3 Adjustment system1.1231Fig. 26: Indicating and adjustmentelements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov

Page 25

6.4 Setup procedureIn HART-Multidrop mode (several sensors on one input) the addressmust be set before continuing with the parameter adjustment. You w

Page 26

▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Select the menu item "Basic adjustment" with [->] and confirm with[OK]. Now the menu item

Page 27 - 5.7 Switch on phase

LiquidAccording to the conductivity and the dielectric value of liquids, thereflection properties can differ considerably. Therefore additionaloptions s

Page 28 - 6.1 Short description

Caution:Note the following, if VEGAPULS 65 is used as part of an overfillprotection system according to WHG:If a linearisation curve is selected, the m

Page 29

Note:Check the distance to the product surface, because if an incorrect (toolarge) value is entered, the exi sting le vel will be saved as false signa

Page 30 - - Select editing position

Menu item Reset valueDamping 0 sLinearisation linearSensor-TAG SensorDisplayedvalue DistanceExtended settings NoneCurrent output - characteristics 4 …

Page 31 - Address 0

6.5 Menu schematicInformation:Depending on the version and application, the light-coloured menuwindows are not always available or offer nor sel ection

Page 32

3.1PointerDistance min.: 0.234 m(d)Distance max.: 5.385 m(d)3.2Meas. reliability15 dBSensor statusOK3.3Curve selectionEcho curve▼3.4Echo curvePresenta

Page 33 - Linearisation curve

6.6 Saving the parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwa

Page 34 - Change now?

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Page 35 - Copy sensor data?

7 Setup with PACTware andother adjustmentprograms7.1 Connecting the PC312Fig. 27: Connection of the PC via VEGACONNECT directlyto the sensor1 USB cabl

Page 36

Necessary components:l VEGAPULS 65l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system12 43OPENTWISTUSBLOCKFi

Page 37 - 6.5 Menu schem

Note:Keep in mindthat for setup of VEGAPULS 65, DTM-Collection in theactual version must be used.All currently available VEGA DTMs are provided in the

Page 38

8 Maintenance and fault rectification8.1 MaintenanceWhen used in the correct way, no special maintenance is required innormal operation.8.2 Remove inte

Page 39 - 6.6 Saving the pa

? Current signal greater than 22 mA or less than 3.6 mAl Electronics module defectiveà Exchange instrument or return instrument for repairIn Ex applic

Page 40 - 7 Setup with PACTware and

Information:When loading on site, first of all the order data must be downloadedfrom the Internet (see operating instructions manual "Oscillator&q

Page 41

l Please ask the agency serving you for the address of your returnshipment. Youcan find the respective agency on our websitewww.vega.com under: "C

Page 42

9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper

Page 43 - ? 4 … 20 mA signal missing

10 Supplement10.1 TechnicaldataGeneral data316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - thread PVDF, 316L- Seal - thr

Page 44 - ? E041, E042, E043

Input variableMeasuredvalue distance between process fitting and product sur-faceMin. distance from antenna end 50 mm (1.969 in)Measuring range up to 3

Page 45 - 8.5 Instrument repair

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist

Page 46

1,0 m (3.28 ft)30 m (98.43 ft)20 mm (0.788 in)10 mm (0.394 in)- 10 mm (- 0.394 in)- 20 mm (- 0.788 in)0Fig. 30: Deviation VEGAPULS 65Influence ofthe

Page 47 - 9 Dismounting

Vessel pressure- Screwed part PVDF -100 … 300 kPa/-1 … 3 bar (-14.5 … 43.5 psig)- Screwed part and flange 316L -100 … 1600 kPa/-1 … 16 bar (-14.5 … 232

Page 48 - 10 Supplement

Electromechanical data - version IP 66/IP 68 (1 bar)Cable entry- Single chamber housing 1 x IP 68 cable gland M20 x 1.5; 1 x blind stopperM20 x 1.5- D

Page 49

Permissible residual ripple- < 100 Hz Uss< 1 V- 100 Hz … 10 kHz Uss< 10 mVLoad see diagram1000750500250141816 20 22 24 26 28 30 32 34 36ΩV412

Page 50

Functional safety according to IEC 61508-4- Singlechannel architecture (1oo1D) up to SIL2- double channel diversitary redundantarchitecture (1oo2D)up

Page 51

10.2 DimensionsHousingin protection IP 66 /IP 68 (0.2 bar)~ 69 mm(2.72")ø 77 mm(3.03")112 mm (4 13/32")M20x1,5/½ NPT~ 69 mm(2.72")

Page 52

Housing in protection IP 66/IP 68 (1 bar)117 mm (4.61")~ 103 mm(4.06")ø 77 mm(3.03")116 mm (4.57")~ 150 mm (5.91")ø 84 mm (3.

Page 53

VEGAPULS 65 - threaded version41 mm(1.61")ø 40 mm(1.58")ø 33 mm(1.30")ø 33 mm(1.30")82 mm (3.23")415 mm (16.34")120 mm (

Page 54

VEGAPULS 65 - flange versiondø 33 mm(1.30")395 mm (15.55")120 mm (4.72")270 mm (10.63")545 mm (21.46")94 mm (3.70")2 mm (

Page 55 - 10.2 Dimensions

10.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only

Page 56 - M20x1,5M20x1,5

During t he entire duration of use, the useris obliged to determine thecompliance of the required occupational safety measures with thecurrent valid r

Page 57

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9

Page 58

l The instrument must not cause any interfering emissionsl Thedevice must be insensitive to interfering immissions, includingthose that may cause unde

Page 59 - 10.4 Trademark

3 Product description3.1 ConfigurationThe scope of delivery encompasses:l VEGAPULS 65 radar sensorl Documentation- this operating instructions manual-

Page 60 - ISO 9001

321Fig. 1: VEGAPULS 65 - threaded version withplastic housing1 Housing cover with integrated PLICSCOM (optional)2 Housing with electronics3 Process fit