Operating InstructionsRadar sensor for continuous level measurement of liquidsVEGAPULS 614 … 20 mA/HART - four-wireDocument ID: 36500
103 Product descriptionVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210113 Product description3.1 CongurationThe type label contains the most
113 Product descriptionVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011The instrument is available in two dierent electronics versions. Each v
123 Product descriptionVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Transport must be carried out under consideration of the notes on the tr
133 Product descriptionVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011The PLICSMOBILE T61 is an external GSM/GPRS radio unit for transmission
144 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210114 Mounting4.1 General instructionsWith instruments with threaded process tting, s
154 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Fig. 5: Flange mounting of the radar sensor4.3 Mounting preparations, mounting str
164 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Fig. 6: Adjustment of the angle of inclinationFig.7:Turningbyfasteninginthec
174 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011dished or round vessel tops, multiple echoes can arise. These can, however, be supp
184 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Fig.11:MountingoftheradarsensorwithinowingmediumA corresponding collar a
194 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011dhThe below charts specify the max. socket piece length h depending on the diameter
2Quick startVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Quick startThe quick start enables a quick setup with many applications. You can n
204 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011The socket piece should be dimensioned in such a way that the an-tenna end protrude
214 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Make sure when planning your measuring site that the radar sensor has a "clear
224 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011When using a surge pipe in a vessel, inuences from vessel installa-tions and turbu
234 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011• The tube diameter must be at least DN 40 or 1½" with antenna size 40 mm (1½&
244 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210110 %100 %125436Fig.21:Congurationbypass1 Radar sensor2 Marking of the polarisa
254 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011• The measurement through a ball valve with complete run is pos-sibleConstructional
264 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-12101123 ... 4 x hmax90°hmaxd1BFig.23:FlowmeasurementwithKhafagi-Venturiume:d=M
275 Connecting to power supplyVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210115 Connecting to power supply5.1 Preparing the connectionAlways
285 Connecting to power supplyVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Warning:Signicant potential dierences exist inside galvanizatio
295 Connecting to power supplyVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210115. Insert the cable into the sensor through the cable entryFig.
3Quick startVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210114. Carry out the adjustment in the menu items "Min. adjustment" and &quo
305 Connecting to power supplyVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-12101156784...20mA212+( )(-)1Fig.25:Electronicscompartment,double
315 Connecting to power supplyVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011power supply 4...20mA activepassivecommonIS GND51/L/N2+( )(-)67
326 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210116 Set up with the indicating and adjustmen
336 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210111 2Fig. 29: Insertion of the indicating and
346 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011 – Edit parameter – Save value• [->] key
356 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011You can nd in the operating instructions m
366 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011The selection "Standpipe" opens a
376 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011 – Fast lling and emptying – Vessel is ver
386 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011 – Extreme damping of output signal due to
396 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011 – Automatic false signal suppression with
4ContentsVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Contents1 About this document1.1 Function ...
406 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011With this selection, the operating range of
416 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011100%0%0,5 m(19.68")5 m(196.9")21F
426 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210114. Enter the suitable distance value in m
436 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011The "Echocurve" shows the signal
446 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011• Vessel installations such as struts• Agit
456 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011The menu item "Delete" is used to
466 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011signal suppression, user-programmed lineari
476 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Menu Menu item Default valueAdditional adju
487 Setup with PACTwareVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210117 Setup with PACTware7.1 Connect the PC312Fig. 32: Connection of the P
497 Setup with PACTwareVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011• Power supply unit or processing systemNote:With power supply units wit
5ContentsVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210119.4 Rectify faults ...
507 Setup with PACTwareVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011All device DTMs are available as a free-of-charge standard version and a
518 Set up with other systemsVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210118 Set up with other systems8.1 DD adjustment programsDevice desc
529 Diagnosis, Asset Management and serviceVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210119 Diagnosis, Asset Management and service9.1 Mainte
539 Diagnosis, Asset Management and serviceVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Further echo curves: Up to 10 echo curves can be sto
549 Diagnosis, Asset Management and serviceVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011The following table shows the error codes in the sta
559 Diagnosis, Asset Management and serviceVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011CodeText mes-sageCause RecticationF264Installation/
569 Diagnosis, Asset Management and serviceVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011CodeText mes-sageCause RecticationM501Error in the
579 Diagnosis, Asset Management and serviceVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Error Cause Rectication4 … 20 mA signal not stable
589 Diagnosis, Asset Management and serviceVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210119.4 Measurement error with constant levelFault desc
599 Diagnosis, Asset Management and serviceVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Fault description Error pattern Cause Rectication7.
61 About this documentVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210111 About this document1.1 FunctionThis operating instructions manual prov
609 Diagnosis, Asset Management and serviceVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Fault description Error pattern Cause Rectication13
619 Diagnosis, Asset Management and serviceVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011You can nd the actual sensor software as well as de
6210 DismountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-12101110 Dismounting10.1 Dismounting stepsWarning:Before dismounting, be aware of da
6311 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-12101111 Supplement11.1 Technical dataGeneral data316L corresponds to 1.4404 or 1.443
6411 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Max. torque for NPT cable glands and Conduit tubes Ʋ Plastic housing 10 Nm (7.37
6511 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Signal resolution 0.3 µAFailure signal current output (adjustable) mA-value unch
6611 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210110,5 m (1.6 ft)10 mm (0.394 in)- 10 mm (- 0.394 in)2 mm (0.079 in)- 2 mm (- 0.079
6711 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Beam angle2) Ʋ Encapsulated antenna system 22° Ʋ Plastic horn antenna 10°Emitted
6811 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Wire cross-section (spring-loaded terminals) Ʋ Massive wire, cord 0.2 … 2.5 mm²
6911 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-12101111.2 DimensionsThe following dimensional drawings represent only an extract of t
72 For your safetyVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210112 For your safety2.1 Authorised personnelAll operations described in this o
7011 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011VEGAPULS61,hygienictting1 23SW 50 mm(1.97")SW 50 mm(1.97")SW 50 mm
7111 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011VEGAPULS 61, version with mounting strap75 mm(2.95")107 mm(4.21")115 m
7211 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011VEGAPULS61,versionwithcompressionange126 mm(4.96")10,5 mm(0.41")
7311 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-12101111.3 Industrial property rightsVEGA product lines are global protected by indus
74INDEXVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011INDEXAAccessories – External indicating and adjustment unit 12 – External radio unit 1
75INDEXVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Socket 18, 20Status messages 53Storage 12Surge pipe 22TType label 10VVessel form 4
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany36500-EN-121011All statements concerning scope of delivery, application, practi
82 For your safetyVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210112.5 CE conformityThe device fullls the legal requirements of the applicable
92 For your safetyVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011tection. The environment management system is certied according to DIN EN IS