Page 1 - Operating Instructions

inoutLevel and PressureOperating InstructionsVEGAMET 614VSer. No.12345678CONNECT%100+-OKESCon12614

Page 2 - Contents

10 VEGAMET 614VA oB oC o1 o2 o3 o o o o7 o8 o9 o o o12 oNL10…10 VDISBUSVEGAA oB oC o1 o2 o3 o4 o5 o6 o7 o8 o9 o10 o11 o12 oNL10…10 VDISBUSVEGA-+-+Moun

Page 3 - VEGAMET 614V 3

VEGAMET 614V 11Transparent coverTo protect the instrument against unauthor-ized adjustment, the front plate of VEGAMETcan be equipped with two lockabl

Page 4 - 1 Product description

12 VEGAMET 614V3.2 Wiring planFailsaferelayLevelrelay 1Levelrelay 2Power supplyVBUSsensorCurrentoutput 1The connections „9, 10, 15, 16, 17 and 18“ can

Page 5 - 1.2 Approvals

VEGAMET 614V 13Adjustment4 Adjustment4.1 Indicating and adjustmentelementsA rotary switch is located on the upper sideof the housing. It is used to se

Page 6 - 1.4 Technical data

14 VEGAMET 614VAdjustment4.2 Adjustment systemIndicating and adjustment moduleDepending on the menu item, change valueor choose out of a listChoose me

Page 7 - VEGAMET 614V 7

VEGAMET 614V 15Adjustment4.3 Adjustment via PCSetup- directly via the keys of the adjustmentmodule- or with a PC, equipped with VVO software(VEGA Visu

Page 8 - 8 VEGAMET 614V

16 VEGAMET 614VAdjustment4.4 Configuration and parameteradjustmentNo matter whether you set up yourVEGAMET via the keys of the adjustmentmodule or via

Page 9 - Ex technical data

VEGAMET 614V 17Adjustment4.5 Comparison: "Reduced menu" – "Extended menu"In the table the most important functions of VEGAMET 614

Page 10 - Mounting

18 VEGAMET 614VSetup5 Setup• Set the VEGAMET instrument address onthe circuit board by means of the rotaryswitch (only necessary, if severalVEGAMET ar

Page 11 - Transparent cover

VEGAMET 614V 19Settings in the „Reduced menu“Name measurement loopTAG-NameTAG -No. 1TAG-NameTAG -No. 1TAG-NameVes.4Hall3Ves.4Hall3 % 27,86

Page 12 - 3 Electrical connection

2 VEGAMET 614VContentsContents1 Product description1.1 Function and configuration... 41.2 Approvals ...

Page 13 - 4 Adjustment

20 VEGAMET 614VSettings in the „Reduced menu“6.3 Adjustment with mediumYou can either carry out the adjustment withmedium or without medium. Adjustmen

Page 14 - Adjustment structure

VEGAMET 614V 21Settings in the „Reduced menu“6.4 Adjustment without mediumFor this adjustment procedure, you have toenter two values (pressure or dist

Page 15 - Changing the menu mode:

22 VEGAMET 614V6.5 ScalingSettings in the „Reduced menu“The adjustments under scaling determinewhich number values and which unit will beactually disp

Page 16 - 16 VEGAMET 614V

VEGAMET 614V 23Settings in the „Reduced menu“6.6 Integration timePercentPressureMassprop.to HeightUnit mdmcm….TAG -No. 1 m 2,341TAG-No. 1

Page 17 - VEGAMET 614V 17

24 VEGAMET 614V6.7 OutputsOverfill protectionThe relay of relay output 1 deenergises at theswitching point „Low“ (safe switching condi-tion).The relay

Page 18 - 18 VEGAMET 614V

VEGAMET 614V 256.8 SimulationTo check outputs and connected instruments,you can adjust any individual percentagevalue with the keys [+] and [–] in thi

Page 19 - VEGAMET 614V 19

26 VEGAMET 614V7 Settings in the „Extended menu“7.1 Configuration of measurement loopSettings in the „Extended menu“The measurement loop configuration

Page 20 - 20 VEGAMET 614V

VEGAMET 614V 27Pos. A Pos. ASettings in the „Extended menu“Level measurementLevel measurementApplication: LevelSensor: Hydrostatic pressure transmitte

Page 21 - VEGAMET 614V 21

28 VEGAMET 614VIf another VEGAMET has been selected, themenu item „Input undefined" appears inwhich you can set the input number of theother VEGA

Page 22 - 22 VEGAMET 614V

VEGAMET 614V 29Settings in the „Extended menu“7.4 Configuration of outputsPC/DCS output and DIS output:The PC/DCS signal as well as the DIS signalare

Page 23 - VEGAMET 614V 23

VEGAMET 614V 3Contents7 Settings in the „Extended menu“7.1 Configuration of measurement loop ... 267.2 Configuration of te

Page 24 - 24 VEGAMET 614V

30 VEGAMET 614VSettings in the „Extended menu“7.5 AdjustmentThe adjustment with medium correspondsto the procedure in the reduced menu (seeappropriat

Page 25 - Menu mode

VEGAMET 614V 31Settings in the „Extended menu“7.6 ConditioningThe menu items „Scaling“ and „Integrationtime“ correspond to the menu items in the„reduc

Page 26 - 26 VEGAMET 614V

32 VEGAMET 614VSettings in the „Extended menu“7.7 Parameter adjustment of outputsCurrent outputs/Volt outputsIn the menu item „prop. to“, you can choo

Page 27 - Pos. A Pos. A Pos. A

VEGAMET 614V 33Settings in the „Extended menu“Relay outputsIn the menu item „prop. to“, you choose aparameter that the relay will react to. You cancho

Page 28 - 28 VEGAMET 614V

34 VEGAMET 614VRelay mode: overfill protectionThe relay deenergises at switching point„High“ (safe condition).Relay mode: dry run protectionThe relay

Page 29 - VEGAMET 614V 29

VEGAMET 614V 35Settings in the „Extended menu“Tendency determinationThe level change within the cycle time (ta) is determined and after completion of

Page 30 - 30 VEGAMET 614V

36 VEGAMET 614VMET indication/PC/DCS outputs/DIS outputsSettings in the „Extended menu“MET indication/Unit:In the menu item „prop. to“, you choose the

Page 31 - VEGAMET 614V 31

VEGAMET 614V 37Settings in the „Extended menu“7.8 Simulation 7.9 Special function: ResetTo check the outputs and connected instru-ments, you can adjus

Page 32 - Current outputs/Volt outputs

38 VEGAMET 614VSettings in the „Extended menu“7.10 Password, language, menu modeSee chapter „6 Settings in the reduced menu“.7.11 Special function: Ma

Page 33 - Relay outputs

VEGAMET 614V 39Settings in the „Extended menu“7.12 Linearisation curvesLinearisation curve 1 … 3A linearisation curve is generated by a cer-tain numbe

Page 34 - 34 VEGAMET 614V

4 VEGAMET 614VProduct description1 Product description1.1 Function and configurationVEGAMET 614 V is a signal conditioninginstrument for a number of d

Page 35 - VEGAMET 614V 35

40 VEGAMET 614VX (in %)V (in %)20040 60 80 10080100604020X1 %12,0Y1 V %5,0X32 %100,0Y32V %100,0To delete the index markers,select the value pairs

Page 36 - 36 VEGAMET 614V

VEGAMET 614V 41Settings in the „Extended menu“Linearisation curve 1Index Value pairmarker no. X % Y V %12345678910111213141516171819202122232425262728

Page 37 - VEGAMET 614V 37

42 VEGAMET 614V7.13 InfoSettings in the „Extended menu“All menu items under „Info“ only have displayfunction.Param.TAG-No. 1Confi-gura-tionAdd’lfunc-

Page 38 - 38 VEGAMET 614V

VEGAMET 614V 43Settings in the „Extended menu“7.14 Reset VEGAMETWith the function „TAG 1 to default“, youreset the whole configuration and all param-e

Page 39 - Linearisation curve 1 … 3

44 VEGAMET 614VScalingprop. to UnitPercent %Volume m3hllgalV %ft3in3Distance m (d)Height mdmcmmmydftinPressure barmbarpsihPaMass kgtlbDensity kg/dm3g/

Page 40 - 40 VEGAMET 614V

VEGAMET 614V 45Diagnosis9 Diagnosis9.1 MaintenanceThe instrument is maintenance-free.9.2 SimulationNoteWhen the simulation is activated, the entiredis

Page 41 - Linearity protocol

46 VEGAMET 614VDiagnosis9.5 Error codesError code MeaningE004 This operation is not supported by the instrument (different software versions).You hav

Page 42 - 42 VEGAMET 614V

VEGAMET 614V 47Error code MeaningDiagnosisE022 Scaling span too big.E027 Actual measured value is less than -10 %.E28 Actual measured value is more th

Page 43 - VEGAMET 614V 43

48 VEGAMET 614VError code MeaningDiagnosisE051 Failure during transmission of measured values via DISBUS. It is not possibleto receive a valid measure

Page 44 - 8 Measured quantity and units

VEGAMET 614V 49Menu schematic "Reduced menu"With these keys youmove in the menu field10.1 Menu schematic "Reduced menu"10 Menu sch

Page 45 - 9 Diagnosis

VEGAMET 614V 5Product description1.3 Features- microcomputer-controlled signal condition-ing instrument for continuous measurement- adjustment module

Page 46 - 9.5 Error codes

50 VEGAMET 614V10.2 Menu schematic "Extended menu"Menu schematic "Extended menu"Param.TAG -No. 1TAG -No. 1 % xx,xAdjust-men

Page 47 - VEGAMET 614V 47

VEGAMET 614V 51Menu schematic "Extended menu"METdisplayPC/DCSoutputsRelayoutputsprop.toPer-centUnit0,0%DIS-outputsSimu-lationSpe-cialfunc-ti

Page 48 - 48 VEGAMET 614V

52 VEGAMET 614V1)The parameters in these menu itemscan only be modified, when a „Resetto single measurement“ has beencarried out first.1) 1) 1)1)Confi

Page 49 - 10 Menu schematics

VEGAMET 614V 53Menu schematic "Extended menu"Bold print/italic is the sensor ormeasured value informationwhich cannot be modified inthis pos

Page 50 - With these keys you move

54 VEGAMET 614Vlike input 1Pass-word offEditlin.curveInfo Lang-uageEng-lishInputinfoVEGA-METinfoPro-graminfoMeas.loopinfoPro-graminfoxxxxxxTAG 1TAG

Page 51

VEGAMET 614V 55ResetVEGA-METTAG 1tode-faultReset OK?ResetNow! OK?tosinglemeas.ResetTAG 1DeleteTA G 1 ?Reset OK?ResetNow! OK?Ser-viceMenumodeEx-ten

Page 52 - 5 … 10

ISO 9001All statements concerning scope of delivery, application, practicaluse and operating conditions of the sensors and processing sys-tems corresp

Page 53

6 VEGAMET 614VProduct description1.4 Technical dataPower supplyOperating voltage / power consumption Unom= 90 … 250 V AC, 50/60 Hz / approx. 14VA= 90

Page 54 - 54 VEGAMET 614V

VEGAMET 614V 7Product descriptionRelay outputsNumber 2 operating relays, 1 fail safe relayContact floating spdtContact material AGSNO2, hard gold plat

Page 55

8 VEGAMET 614VProduct descriptionElectrical protective measuresInstrument IP 30Plug-in socket IP 20Protection class IIOvervoltage category IIElectrica

Page 56 - ISO 9001

VEGAMET 614V 912 34910 111217 18 20 21 2213454,57256 7813 14 15 1623 24 25 26 27 28118,5Ser. No.12345678CONNECT614%100+-OKESCon12Transparent coverCarr