Recurring function
test
for VEGAFLEX series 60
Document ID:
36552
Vue de la page 0
1 2 3 4 5 6 ... 19 20

Résumé du contenu

Page 1 - Recurring function

Supplementary informationRecurring functiontestfor VEGAFLEX series 60Document ID:36552

Page 2

3.3 Verification of the instrument parametersFor this test point, the sensor documentation of the setup or the lastsensor documentation (at least 6 mon

Page 3

3.4 Verification of echo dataFor this test point, you require the sensor documentation of the setupor a sensor documentation created at least 6 months

Page 4

ExampleDuring setup, the level echo had 32 dB. The distance [m] to themedium was 12.5 m.The actual level echo has 25 dB. The distance [m] to the mediu

Page 5 - 2.4 Required plant situation

Ifall function tests we re successful, the recurring function test isfinished.If you used an mA-meter for the recurring function test, switch off thesen

Page 6

4 Result of the recurring function te stIf all test points could be terminated successfully, then the recurringfunction test was successful.Fulfilled t

Page 7 - 3 Sequen

5 Testprotocol - Recurring function testIf you copy this protocol, please note the date of the function test, themeasurement loop and the sensor seria

Page 8

Test 3.3 - Verification of the instrument parameters□ Sensor documentation of thesetup availableor□ Sensor documentation (at least 6months old) is avai

Page 9 - 3.2 Verificat

● Summary 88 % (λdu)Test 3.1 / 3.2 / 3.5 □ All three test points passed □ One or several test points did notpassDate _________________________________

Page 10 - 3.3 Verificat

18 Recurringfunction test • for VEGAFLEX series 605 Test protocol - Recurring function test36552-EN-100225

Page 11 - 3.4 Verificat

Recurringfunction test • for VEGAFLEX series 60 195 Test protocol - Recurring function test36552-EN-100225

Page 12 - 36552-EN-100225

Contents1 About this document2 Prerequisites2.1 Authorised personnel . . . . . . . . . . . . . . . . . . . . . . . .52.2 Required tools . . . . . . .

Page 13

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9

Page 14

1 About this documentThe recurring function test serves to check the safety function andreveal possible undetected, dangerous failures (λdu). The func

Page 15

Please note the Ex-specific safety information for installation andoperation in Ex areas. These safety instructions are part of the scopeof delivery an

Page 16

2 Prerequisites2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist pe

Page 17

Information:Document the recurring function test, for example, in the test protocolin the supplement.The following conditions must be fulfilled when pe

Page 18

3 Sequence of the recurring function testCarry out the recurring function test in the following sequence:l 3.1 Restart the sensorl 3.2 Verification of

Page 19

Ifyou do not have this possibility, connect an mA-meter accordingto the following illustration.You require the mA-meter for the verification of the cur

Page 20 - ISO 9001

3.2 Verification of the current outputIn this test point you simulate certain level values via the currentoutput. With this you can test the reaction o