Operating InstructionsCapacitive cable electrode for continuous level measurementVEGACAL 65Probus PADocument ID: 30034
103 Product descriptionVEGACAL 65 • Probus PA30034-EN-130917• with the suitable VEGA DTM in conjunction with an adjustment software according to the
113 Product descriptionVEGACAL 65 • Probus PA30034-EN-130917You can nd further information in the operating instructions "Interface adapter VEG
124 MountingVEGACAL 65 • Probus PA30034-EN-1309174 Mounting4.1 General instructionsMake sure that all parts of the instrument coming in direct conta
134 MountingVEGACAL 65 • Probus PA30034-EN-130917The max. permissible pressure is specied in chapter "Technical data" or on the type label
144 MountingVEGACAL 65 • Probus PA30034-EN-130917132Fig. 5: Fasten the probe1 Gravity weight2 Insulated adapter3 Lug M12 (article no. 2.27423)In v
155 Connecting to power supplyVEGACAL 65 • Probus PA30034-EN-1309175 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the
165 Connecting to power supplyVEGACAL 65 • Probus PA30034-EN-130917next distributor must be connected to each other and also connected to ground pote
175 Connecting to power supplyVEGACAL 65 • Probus PA30034-EN-13091710. Connect the screen to the internal ground terminal, connect the outer ground
185 Connecting to power supplyVEGACAL 65 • Probus PA30034-EN-130917I²CDisplay12 56783412Fig. 9: Electronics and connection compartment, single chambe
195 Connecting to power supplyVEGACAL 65 • Probus PA30034-EN-1309171 2 345Fig. 11: Double chamber housing1 Housing cover, connection compartment2 B
2ContentsVEGACAL 65 • Probus PA30034-EN-130917Contents1 About this document1.1 Function ...
205 Connecting to power supplyVEGACAL 65 • Probus PA30034-EN-130917123Display12I2CFig. 13: Connection compartment, double chamber housing1 Spring-lo
215 Connecting to power supplyVEGACAL 65 • Probus PA30034-EN-130917132Display12 5678I2CFig. 16: Electronics compartment, double chamber housing1 Plu
225 Connecting to power supplyVEGACAL 65 • Probus PA30034-EN-130917112Fig. 18: Wiring plan, Ex-d double chamber housing1 Voltage supply, signal outp
236 Set up with the display and adjustment module PLICSCOMVEGACAL 65 • Probus PA30034-EN-1309176 Set up with the display and adjustment module PLICS
246 Set up with the display and adjustment module PLICSCOMVEGACAL 65 • Probus PA30034-EN-130917Fig. 20: Insert display and adjustment moduleNote:If y
256 Set up with the display and adjustment module PLICSCOMVEGACAL 65 • Probus PA30034-EN-130917 – Save value• [->] key to select: – Menu change –
266 Set up with the display and adjustment module PLICSCOMVEGACAL 65 • Probus PA30034-EN-130917In the main menu item "Basic adjustment", th
276 Set up with the display and adjustment module PLICSCOMVEGACAL 65 • Probus PA30034-EN-130917Min. adjustmentAccept current measured value?Accept?Ed
286 Set up with the display and adjustment module PLICSCOMVEGACAL 65 • Probus PA30034-EN-130917Enter the requested parameters via the appropriate key
296 Set up with the display and adjustment module PLICSCOMVEGACAL 65 • Probus PA30034-EN-130917Function ResetvalueMax. adjustment 3000 pFMin. adjust
3ContentsVEGACAL 65 • Probus PA30034-EN-1309178.3 Exchanging the electronics module ...
306 Set up with the display and adjustment module PLICSCOMVEGACAL 65 • Probus PA30034-EN-130917DisplayBasic adjustment 2▶DisplayDiagnosticsServiceInf
316 Set up with the display and adjustment module PLICSCOMVEGACAL 65 • Probus PA30034-EN-130917InfoBasic adjustment 5DisplayDiagnosticsService▶InfoIn
327 Set up with PACTware and other adjustment programsVEGACAL 65 • Probus PA30034-EN-1309177 Set up with PACTware and other adjustment programs7.1
337 Set up with PACTware and other adjustment programsVEGACAL 65 • Probus PA30034-EN-1309177.2 Parameter adjustment with PACTwareFurther setup steps
348 Maintenance and fault recticationVEGACAL 65 • Probus PA30034-EN-1309178 Maintenanceandfaultrectication8.1 MaintenanceIf the instrument is u
358 Maintenance and fault recticationVEGACAL 65 • Probus PA30034-EN-130917Error Cause RecticationMeasured val-ue on the display and adjustment modu
368 Maintenance and fault recticationVEGACAL 65 • Probus PA30034-EN-130917Depending on the reason for the fault and the measures taken, the steps de
378 Maintenance and fault recticationVEGACAL 65 • Probus PA30034-EN-13091770 mm(2.76")200 mm (7.87")Fig. 24: Take the gravity weight into
389 DismountingVEGACAL 65 • Probus PA30034-EN-1309179 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process cond
3910 SupplementVEGACAL 65 • Probus PA30034-EN-13091710 Supplement10.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materia
41 About this documentVEGACAL 65 • Probus PA30034-EN-1309171 About this document1.1 FunctionThis operating instructions manual provides all the info
4010 SupplementVEGACAL 65 • Probus PA30034-EN-130917 Ʋ PTFE partly insulated: ø 8 mm (0.315 in)10 KN (2248 lbf)Max. torque (process tting - thread)
4110 SupplementVEGACAL 65 • Probus PA30034-EN-130917123-50°C(-58°F)50°C(122°F)40°C(104°F)-40°C(-40°F)80°C(176°F)0°C(32°F)100°C(212°F)150°C(302°F)200°
4210 SupplementVEGACAL 65 • Probus PA30034-EN-130917 Ʋ Single chamber housing 1 x IP 68 cable gland M20 x 1.5; 1 x blind plug M20 x 1.5 Ʋ Double cham
4310 SupplementVEGACAL 65 • Probus PA30034-EN-130917 Ʋ Aluminium housing, stainless steel housing - investment casting, stain-less steel housing - el
4410 SupplementVEGACAL 65 • Probus PA30034-EN-130917pF% Lin%Min-MaxadjustmentLinearizationPROFIBUS PA-outputPrimaryValueSecondaryValue 2SecondaryValu
4510 SupplementVEGACAL 65 • Probus PA30034-EN-130917Byte-No.1234 5 6789 10StatusStatusStatusStatus(FB1)IEEE-754-Floating point valuePA-OUT(FB1)IEEE-7
4610 SupplementVEGACAL 65 • Probus PA30034-EN-130917Status codeDescription according to ProbusstandardPossible cause0x44 uncertain - last unstable
4710 SupplementVEGACAL 65 • Probus PA30034-EN-13091710.3 DimensionsHousinginprotectionIP66/IP68(0.2bar)~ 69 mm(2.72")ø 77 mm(3.03")1
4810 SupplementVEGACAL 65 • Probus PA30034-EN-130917HousinginprotectionIP66/IP68(1bar)117 mm (4.61")~ 103 mm(4.06")ø 77 mm(3.03"
4910 SupplementVEGACAL 65 • Probus PA30034-EN-130917LG1 AG11/2 A56 mm(2.21")ø 30 mm(1.18")22 mm(0.87")200 mm(7.87")ø 6 mm(0.24&qu
52 For your safetyVEGACAL 65 • Probus PA30034-EN-1309172 For your safety2.1 Authorised personnelAll operations described in this operating instruct
5010 SupplementVEGACAL 65 • Probus PA30034-EN-130917LG1 AG11/2 A56 mm(2.21")ø 30 mm(1.18")22 mm(0.87")200 mm(7.87")ø 8 mm(0.32&qu
5110 SupplementVEGACAL 65 • Probus PA30034-EN-130917108 mm (4.25")ø 40 mm (1.58")Fig. 35: Temperature adapterø 16 mm (0.63")L7 mm (0.2
5210 SupplementVEGACAL 65 • Probus PA30034-EN-13091710.4 Industrial property rightsVEGA product lines are global protected by industrial property ri
53NotesVEGACAL 65 • Probus PA30034-EN-130917
54NotesVEGACAL 65 • Probus PA30034-EN-130917
55NotesVEGACAL 65 • Probus PA30034-EN-130917
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany30034-EN-130917All statements concerning scope of delivery, application, practi
62 For your safetyVEGACAL 65 • Probus PA30034-EN-1309172.5 Safety label on the instrumentThe safety approval markings and safety tips on the device
73 Product descriptionVEGACAL 65 • Probus PA30034-EN-1309173 Product description3.1 CongurationThe scope of delivery encompasses:• Level sensor VE
83 Product descriptionVEGACAL 65 • Probus PA30034-EN-130917The nameplate contains the most important data for identication and use of the instrument
93 Product descriptionVEGACAL 65 • Probus PA30034-EN-130917123Fig. 3: Functional principle - Plate capacitor1 Distance between the electrode surface