Vega VEGAWELL 52 4 … 20 mA_HART Pt 100 Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Équipement Vega VEGAWELL 52 4 … 20 mA_HART Pt 100. VEGA VEGAWELL 52 4 … 20 mA_HART Pt 100 User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer

Résumé du contenu

Page 1 - VEGAWELL 52

Operating InstructionsVEGAWELL 524 … 20 mA/HART Pt 100Document ID:35402Process pressure/Hydrostatic

Page 2

Upto the time of installation, the packages must be left closed andstored according to the orientation and storage markings on theoutside.Unless other

Page 3

4 Mounting4.1 General instructionsMake sure that all parts of the instrument exposed to the process, inparticular the sensor element, process seal and

Page 4 - 1.3 Symbolism used

4.2 Mounting steps with straining clamp231Fig. 4: Strainingclamp1 Suspension cable2 Suspension opening3 Clamping jawsMount VEGAWELL 52 with straining

Page 5 - 2.3 Warning about misuse

4.3 Mounting steps with screwed connection123456Fig. 5: Threaded fitting1 Suspensioncable2 Seal screw3 Cone bushing4 Seal cone5 Threaded fitting6 SealMo

Page 6

4.4 Mounting steps with threaded connection orhousing231Fig. 6: Plastichousing1 Housing2 Seal3 ThreadMount VEGAWELL 52 as follows:1 Weld the welded so

Page 7 - 3 Produc

5 Connecting to power supply5.1 Preparing the connectionGenerally connect the instrument only in the complete absence of linevoltage.The instrument is

Page 8 - 3.2 Principle of operation

1231 2 3 4 5 61 2 3 4 5 6Fig. 7: Connect VEGAWELL 52 topower supply1 Direct connection2 Connection via VEGABOX 023 Connection via housingIf screened c

Page 9 - 3.3 Operation

Warning:Within galvanic plants as well as vessels with cathodic corrosionprotection there are considerable potential differences. Considerablyequalisat

Page 10 - 35402-EN-111021

10 Screwthe housing cover onThe electrical connection is finished.Proceed as follows:1 Unscrew the housing cover2 Insert the connection cable through t

Page 11 - 4.1 General instructions

1213–+1 2 3 4 5 61 2 3 4 5 6Fig. 9: Wiringplan VEGABOX 021 To power supply or the processing system (signal pressure transmitter)2 To power supply or

Page 12 - 4.2 Mount

Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .

Page 13 - 4.3 Mount

Wirenumber Wire colour/Polarity Terminal VEGABOX 021 brown (+) 12 blue (-) 23 Shielding GroundWire number Wire colour/Polarity Terminal temperaturetra

Page 14 - 4.4 Mount

Terminal, housing Wirecolour transmit-ter/polarityFunction5 Red Measurement Pt 1006 Black Power supply Pt 10012+( )(-)3 4+( )(-)123Fig. 12: Wiringpl

Page 15 - 5.1 Preparing the connection

6 Setup with VEGADIS 626.1 ConnectionThe VEGADIS 62 is an indicating and adjustment unit without externalenergy for looping into 4 … 20 mA/HART circui

Page 16

Ifyou want to change this value, edit the value via "OK" and adjust therequested value via [↑] and [↓]. Save the value via "OK",

Page 17 - 5.2 Connection procedure

7 Setupwith PACTware7.1 Connecting the PC15234Fig. 14: Connectionof the PC to VEGABOX 02 or communication resistor1 PC with PACTware2 RS232 interface

Page 18 - 5.3 Wiring plan

Note:Withpower supply units with integrated HART resistance (internalresistance approx. 250 Ω), an additional external resistance is notnecessary (e.

Page 19

8 Maintenance and fault rectification8.1 MaintenanceIf the instrument is used properly, no special maintenance is requiredin normal operation.In some a

Page 20

? 4 … 20 mA signal not stablel Level fluctuationsà Adjust integration time via PACTwarel no atmospheric pressure compensationà Check the capillaries an

Page 21 - 5.4 Switch-on phase

8.4 Shorten suspension cableThe suspension cable can be shortened individually. For the versionwith plastic or stainless steel housing proceed as foll

Page 22 - 6.2 Adjust the sensor

4325671Fig. 16: Configurationof the cable seal1 Connection cable (up to 6 pieces depending on the version)2 Cable screening3 Breather capillaries with

Page 23 - 6.3 Scale the indication

8.3 Shorten suspension cable . . . . . . . . . . . . . . . . . . . . .278.4 Shorten suspension cable . . . . . . . . . . . . . . . . . . . . .288.5 In

Page 24 - 7.1 Connecting the PC

9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper

Page 25

10 Supplement10.1 Technical dataGeneral dataMeasured variable LevelMeasuring principle Ceramic-capacitive, dry measuring cellCommunication interface H

Page 26 - 8.2 Remove interferences

InputvariablePercentage value -10 … +110 % of the nominal measuring rangePressure value -20 … +120 % of the nominal measuring rangeRecommended max. tu

Page 27 - 8.3 Shorten suspension cable

Nominalrange Overload capacity, max.pressureOverload capacity, min.pressure0 … 70 psi 900 psi0 psi0 … 150 psi 1300 psi0 psi0 … 350 psi 1900 psi0 psiOu

Page 28 - 8.4 Shor

- Turn down up to 10 : 1 < 0.04 % x TDDeviation with version < 0.1 %- Turn down 1 : 1 up to 5 : 1 < 0.1 %- Turn down up to 10 : 1 < 0.02 %

Page 29 - 8.5 Instrument repair

Ambient conditionsAmbient temperature- Connection cable PE -40 … +60 °C (-40 … +140 °F)- Connection cable PUR, FEP -40 … +80 °C (-40 … +176 °F)Storage

Page 30 - 9 Dismou

Cable entry housing 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm), 1 xblind stopper M20 x 1.5Screw terminals for cable cross-section up to 1.5 mm² (AW

Page 31 - 10 Supplem

That's why the associated approval documents have to be noted with these instruments. They arepart of the delivery or can be downloaded underwww.

Page 32

10.2 DimensionsVEGAWELL 52 - 316L/Titanium 22 mm1 2L175 mm (6.89")220 mm (8.66")ø 22 mm(0.87")220 mm (8.66")ø 22 mm(0.87")52

Page 33

VEGAWELL 52 - Titanium 33 mmL22 mm(0.87")G1 ½A/NPT1 ½316 L~ 69 mm(2.72")ø 77 mm(3.03")112 mm (4.41")M20x1,5/½ NPT321SW 30 mm(1.18&

Page 34

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Page 35

VEGAWELL 52 - Duplex/PVDFSW46(1.81")L22 mm(0.87")G1 ½A/NPT1 ½316 L~ 69 mm(2.72")ø 77 mm(3.03")112 mm (4.41")M20x1,5/½ NPT52 3

Page 36

VEGAWELL 52 - Duplexthreaded fittingL234 mm (9.21")20 mm(0.79")74 mm(2.91")ø 32 mm(1.26")ø 40 mm(1.58")SW 27 mm(1.06")ø 3

Page 37

10.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only

Page 38 - 10.2 Dim

INDEXAAccessory- External indicating and adjustment unitVEGADIS 62 10- Interface adapter 10- Measuring instrument holder 10- Mounting bracket 10Applic

Page 39

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9

Page 40 - - Duplex/PVDF

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist

Page 41 - - Duplex

2.5 Safetylabel on the instrumentThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device fulfills the l

Page 42 - 10.4 Trademark

3 Product description3.1 StructureThe scope of delivery encompasses:l VEGAWELL 52 pressure transmitter with suspension cablel optionally available wit

Page 43

The type label contains the most important data for identification anduse of the instrument:1234578910 111213146Fig. 2: Structuretype label VEGAWELL 52

Page 44 - ISO 9001

The CERTEC®measuring cell is also equipped with a temperaturesensor P t 100 in four-wire technology. The resistance value isaccessed via the wires of

Commentaires sur ces manuels

Pas de commentaire