Vega VEGAVIB 66 - NAMUR Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Équipement Vega VEGAVIB 66 - NAMUR. VEGA VEGAVIB 66 - NAMUR User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer

Résumé du contenu

Page 1 - Operating Instructions

Operating InstructionsVEGAVIB 66with NAMUR output

Page 2 - Contents

l signal lamp for indication of the switching condition (yellow)l potentiometer for adaptation to the product densityl Mode switch to select the switc

Page 3

4 Mounting4.1 GeneralIn general, VEGAVIB 66 can be mounted in any position. Theinstrument must be mounted in such a way that the vibratingelement is a

Page 4 - 1 Sequence

Warning:The housing must not be used to screw in the instrument!Applying tightening force on the housing can damage itsinternal mechanical parts.To sc

Page 5 - 2 For your safety

dd6123Fig. 4: Filling in the center, emptying laterally1 VEGAVIB 662 Emptying opening3 Filling openingThe vibrating element should protrude into the v

Page 6 - 2.8 Manufacturer declaration

Fig. 5: Inflowing materialTo minimise flow resistance caused by the tuning fork,VEGAVIB 66 should be mounted in such a way that thesurfaces of the fork

Page 7

This baffle must be manufactured by you.>125Fig. 7: Baffle protection against damagesVEGAVIB 66 - with NAMUR output 15Mounting31219-EN-060508

Page 8 - 3 Product description

5 Connecting to power supply5.1 Preparing the connectionAlways observe the following safety instructions:l Connect only in the complete absence of lin

Page 9 - 3.3 Adjustment

3 Remove approx. 10 cm (4 in) of the cable mantle, stripapprox. 1 cm (0.4 in) insulation from the ends of theindividual wires4 Insert the cable into t

Page 10 - 3.4 Storage and transport

14442 3Fig. 9: Material versions, single chamber housing1 Plastic (not with EExd)2 Aluminium3 Stainless steel (not with EExd)4 Filter element for pres

Page 11 - 4 Mounting

1 2++--Fig. 11: Wiring plan, single chamber housingExternal simulation keyIn addition to the test key on the electronics module, you canconnect an ext

Page 12 - 4.2 Mounting information

Contents1 About this document1.1 Function ...41.2 Target group ...41.3 Symbolism used ...

Page 13 - 31219-EN-060508

6 Set up6.1 GeneralThe numbers in brackets refer to the following illustrations.On the electronics module you will find the following indicatingand adj

Page 14

case of very light-weight solids, you have to turn thepotentiometer to the complete left position (>0.008 g/cm³ or>0.0003 lbs/in³). Hence the VE

Page 15

Note:The mode adjustment on the NAMUR amplifier must beselected in such a way that the switching output goes to safeposition in case of a failure messa

Page 16 - 5 Connecting to power supply

sequence of the switching conditions must be monitored viathe switching amplifier as well as the connected systems. Thesensor must neither be removed n

Page 17

Sensor cur-rentLevel relayamplifier -overfill pro-tectionLevel relayamplifier -dry runprotectionSignal lampamplifier -overfill pro-tectionSignal lampamplifi

Page 18

7 Maintenance and fault rectification7.1 MaintenanceWhen used as directed in normal operation, VEGAVIB 66 iscompletely maintenance-free.7.2 Fault recti

Page 19

à Check if there is buildup on the vibrating element, and ifso, remove it.l Unfavourable installation locationà Mount the instrument at a location in

Page 20 - 6 Set up

21Fig. 16: Loosen the screws1 Electronics module2 Screws (2 pcs.)6 Remove the old oscillator7 Compare the new oscillator with the old one. The type la

Page 21 - 6.3 Function chart

7.4 Instrument repairIf a repair is necessary, please proceed as follows:You can download a return form (23 KB) from our homepagewww.vega.com under: &

Page 22 - 6.4 Recurring function test

8 Dismounting8.1 Dismounting procedureWarning:Before dismounting, be aware of dangerous process con-ditions such as e.g. pressure in the vessel, high

Page 23 - 3 4,5 t/s

8 Dismounting8.1 Dismounting procedure ...298.2 Disposal ...299 Supplement9.1 Technical data...

Page 24

9 Supplement9.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - Thread 316L- Process

Page 25 - 7.2 Fault rectification

Modes (NAMUR output adjustable to falling or rising characteristics)- min. rising characteristics (High current when im-mersed)- max. falling characte

Page 26

Connection cable- Configuration four cores, one suspension cable, one breathercapillary, screen braiding, foil, mantle- wire cross section 0.5 mm²- wir

Page 27

Overvoltage category IIIProtection class IIApprovals3)ATEX II 1G, 1/2G, 2GEExiaIIC T6 + ATEX II 1/2 DIP66 TATEX II 1/2G, 2GEExd d IIC T6ATEX II 1/2 DI

Page 28 - 7.4 Instrument repair

9.2 DimensionsHousing in protection IP 66/IP67 and IP 66/IP 68; 0.2 barø77mm (3 1/32")112mm (4 13/32")69mm (2 23/32")ø77mm (3 1/32"

Page 29 - 8 Dismounting

150mm (5 29/32")L22mm(55/64")40mm(1 37/64")33mm(1 19/64")G1½Aø 43mm (1 11/16")ø 11mm (7/16")ø 43mm (1 11/16")160mm

Page 30 - 9 Supplement

9.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only i

Page 31

SupplementVEGAVIB 66 - with NAMUR output 3731219-EN-060508

Page 32

Supplement38 VEGAVIB 66 - with NAMUR output31219-EN-060508

Page 33

SupplementVEGAVIB 66 - with NAMUR output 3931219-EN-060508

Page 34 - 9.2 Dimensions

1 About this document1.1 FunctionThis operating instructions manual has all the information youneed for quick setup and safe operation. Please read th

Page 35

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] 9001All stateme

Page 36

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manualmust be carried out only by trained specialist

Page 37

2.6 SIL conformityVEGAVIB 66 fulfills the requirements of functional safetyaccording to IEC 61508/IEC 61511. You can find furtherinformation in the supp

Page 38

l Make sure there is no explosive atmosphere present if youwant to operate the instrument with opened coverl Make sure that the cable gland is tight a

Page 39

3 Product description3.1 ConfigurationThe scope of delivery encompasses:l VEGAVIB 66 level sensorl documentation- this operating instructions manual- S

Page 40 - ISO 9001

Typical applications are overfill and dry run protection. Thanksto its simple and robust measuring system, VEGAVIB 66 isvirtually unaffected by the chem