Operating InstructionsVEGAVIB 63- Relay (DPDT)Document ID:29277Vibration
4 Mounting4.1 General instructionsMake sure that all parts of the instrument exposed to the process, inparticular the sensor element, process seal and
The max. permissible pressure is specified in chapter "Technical data"or on the type label of the sensor.The vibrating level switch is a meas
Fig. 3: Inflowing mediumVEGAVIB 63 can be mounted with a lock fitting for height adjustment.Take note of the pressure information of the lock fitting.The
d dd6d6Fig. 4: Filling and emptying centreddd6123Fig. 5: Filling in the centre, emptying laterally1 VEGAVIB 632 Discharge opening3 Filling openingVEGA
In applications su ch as grit chambers or settling basins for coarsesediments, the vibrating element must be protected against damagewith a suitable b
5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o
5 Lift the opening levers of the terminals with a screwdriver (seefollowing illustration)Fig. 7: Connection steps 5 and 66 Insert the wire ends into t
14442 3Fig. 8: Material versions, single chamber housing1 Plastic (not with EEx d)2 Aluminium3 Stainless steel (not with EEx d)4 Filter element for pr
6 Set up6.1 General informationThe figures in brackets refer to the following illustrations.On the electronics module you will find the following indica
As a default setting, the potentiometer of VEGAVIB 63 is set to thecomplete right position (> 0.3 g/cm³/0.011 lbs/in³). In very light solidsyou hav
Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .
Level Switching status Control lampMode min.Dry run protection53 4(8)(6) (7)Relay deenergized RedFailure of the sup-ply voltage(min./max. mode)any53 4
7 Maintenance and fault rectification7.1 MaintenanceIf the instrument is used properly, no special maintenance is requiredin normal operation.7.2 Remov
Error Cause RectificationWrong mode selected Set the correct mode on the mode switch (overflowprotection, dry run protection). Wiring should be carriedo
6 Pull out the old electronics module7 Compare the new electronics module with the old one. The typelabel of the electronics module must correspond to
8 Dismounting8.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper
9 Supplement9.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - thread 316L- Process
253 V AC, 253 V DCWith circuits > 150 V AC/DC, the relay contactsmust be in the same circuit.Switching current- Min. 10 µA- Max. 3 A AC, 1 A DCBrea
Process temperature (thread or flange tem-perature) with temperature adapter (option)-50 … +250 °C (-58 … +482 °F)123-50°C(-58°F)50°C(122°F)40°C(104°F)
Voltage supplyOperating voltage 20 … 253 V AC, 50/60 Hz, 20 … 72 V DC (atU >60 V DC, the ambient temperature can be max.50 °C/122 °F)Power consumpt
9.2 DimensionsVEGAVIB 63 - housing3214~ 69 mm(2.72")ø 79 mm(3.11")117 mm (4.61")M20x1,5/½ NPT~ 59 mm(2.32")ø 80 mm(3.15")112
9.2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29Supplementary documentationInformation:Supplementary documents appropria
20mm(25/32")25mm(63/64")L125mm (4 59/64")ø16mm (5/8")G1Aø 29mm (1 9/64")Fig. 28: VEGAVIB 63, threaded version G1 A (DIN ISO 2
22mm(55/64")33mm(1 19/64")L125mm (4 59/64")ø16mm (5/8")G1½Aø 29mm (1 9/64")Fig. 29: VEGAVIB 63, threaded version G1½ A (DIN I
ø 34 mm(1 11/32")178 mm (7 1/64")Fig. 30: Temperature adapter32 VEGAVIB 63 • - Relay (DPDT)9 Supplement29277-EN-120418
9.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only i
34 VEGAVIB 63 • - Relay (DPDT)9 Supplement29277-EN-120418
VEGAVIB 63 • - Relay (DPDT) 359 Supplement29277-EN-120418
VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9
1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist
2.5 Safety label on the instrumentThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device fulfills the
3 Product description3.1 StructureThe scope of delivery encompasses:l VEGAVIB 63 point level switchl Documentation- this operating instructions manual
With the serial number, you can access the delivery data of theinstrument viawww.vega.com, "VEGA Tools" and "serial numbersearch".
3.3 OperationWith the factory setting, products with a density of > 0.05 g/cm³(0.002 lbs/in³) can be measured. It is possible to adapt the instrume