Operating InstructionsVEGAPULS 65Foundation FieldbusRadar

Page 2

3.2 Principle of operationVEGAPULS 65 is a radar sensor in C-band technology (emittingfrequency approx. 6 GHz) for continuous level measurement. It is

Page 3

The entered parameters are generally saved in VEGAPULS 65,optionally also in the indicating and adjustment module or inPACTware.3.4 Packaging, transpo

Page 4 - 1.3 Symbolism used

4 Mounting4.1 General instructionsSelect an installation position you can easily reach for mounting andconnecting as well as later retrofitting of an i

Page 5 - 2.3 Warning about misuse

1 32100%0%4Fig. 3: Measuringrange (operating range) and max. measuring distance1 full2 empty (max. measuring distance)3 Measuring rangeInformation:If

Page 6 - 2.7 Fulfillmen

1Fig. 4: Positionof the polarisation plane with VEGAPULS 651 Marking holeMake sure that all parts of the instrument in contact with the measuredproduc

Page 7

Whenmounting VEGAPULS 65, keep a distance of at least 500 mm(19.69 in) to the vessel wall. If the sensor is installed in the center ofdished or round

Page 8 - 3 Produc

Fig. 6: Vesselwith conical bottomDo not mount the instruments in or above the filling stream. Make surethat you detect the product surface, not the infl

Page 9

Fig. 8: Recommendedsocket mountingIn case of very big socket diameters, the active antenna part can beslightly recessed in the socket. The following r

Page 10 - 3.3 Operation

Fig. 10: Coversmooth profiles with deflectorsIf there are agitators in the vessel, a false echo storage should becarried out with the agitators in motio

Page 11 - 28452-EN-090305

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Page 12 - 4.1 General instructions

Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .

Page 13

Insystems without potential equalisation, connect the cable screendirectly to ground potential at the power supply unit and at the sensor.In the conne

Page 14 - 4.2 Mounting instructions

7 Insertthe wire ends into the open terminals according to the wiringplanFig. 12: Connectionsteps 6 and 78 Press down the opening levers of the termin

Page 15 - > 500 mm

55551 243Fig. 13: Materialversions, single chamber housing1 Plastic2 Aluminium3 Stainless steel, investment casting4 Stainless steel, electro-polished

Page 16

I2CDisplay11 2 56 7 8Fig. 15: Wiringplan, single chamber housing1 Voltage supply/Signal output5.4 Wiring plan, double chamber housingThe following ill

Page 17

4I2C1 23I²C124DisplayTyp:1 2 5 6 7 8BusSim.Fig. 17: Electronicscompartment, double chamber housing1 Simulation switch ("on" = mode for simul

Page 18

312Display1 2I²CFig. 18: Connectioncompartment, double chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Ground terminal for connection

Page 19 - 5.1 Preparing the connection

1 2 345Fig. 20: Doublechamber housing1 Housing cover, connection compartment2 Blind stopper or plug M12 x 1 for VEGADIS 61 (optional)3 Housing cover,

Page 20 - 5.2 Connection procedure

121 2Fig. 22: Connectioncompartment double chamber housing Ex d1 Spring-loaded terminals for power supply and cable screen2 Ground terminal for connec

Page 21

5.6 Wiring plan - version IP 66/IP 68, 1 bar+-12Fig. 24: Wireassignment, connection cable1 brown (+) and blue (-) to power supply or to the processing

Page 22

6 Setup with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,

Page 23

7.3 Parameter adjustment with AMS™ . . . . . . . . . . . . . .417.4 Saving the parameter adjustment data . . . . . . . . . . . .418 Maintenance and fa

Page 24

Fig. 25: Insertindicating and adjustment moduleNote:Ifyou intend to retrofit the instrument with an indicating and adjustmentmodule for continuous meas

Page 25

6.3 Adjustment system1.1231Fig. 26: Indicatingand adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov

Page 26

6.4 SetupprocedureAs VEGAPULS 65 is a distance measuring instrument, the distancefrom the sensor to the product surface is measured. To have the realp

Page 27

3 Prepare the % value for editing with [OK] and set the cursor to therequested position with [->]. Set the requested percentage valuewith [+] and s

Page 28 - 5.7 Switch on phase

Apart from the medium, the vessel shape can also influence themeasurement. To adapt the sensor to these measuring conditions, thismenu item offers differ

Page 29 - 6.1 Short description

3 Confirm "False signal suppression - Change now" with [OK] andselect in the below menu "Create new". Enter the actual distancefrom

Page 30

Copy sensor data?Additional adjustment and diagnosis options such as e.g. scaling,simulation or trend curve presentation are shown in the following me

Page 31 - - Select editing position

6.5 MenuschematicInformation:Depending on the version and application, the light-coloured menuwindows are not always available or offer nor selection p

Page 32 - 6.4 Setup

Service4Basic adjustmentDisplayDiagnostics▶ServiceInfo4.1Gating out of false signalsChange now?4.2Extended settingNone4.4SimulationStart simulation?▼4

Page 33

6.6 Savingthe parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwar

Page 34

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Page 35 - Extended setting

7 Setupwith PACTware and other adjustmentprograms7.1 Connecting the PC312Fig. 27: Connectionof the PC via VEGACONNECT directly to the sensor1 USB cabl

Page 36 - Copy sensor data?

Necessary components:l VEGAPULS 65l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system7.2 Parameter adjustmen

Page 37 - 6.5 Menu

8 Maintenance and fault rectification8.1 MaintenanceWhen used in the correct way, no special maintenance is required innormal operation.8.2 Remove inte

Page 38

In Exapplications, the regulations for the wiring of intrinsically safecircuits must be observed.? E013l no measured value availableà sensor in boot p

Page 39 - 6.6 Saving

Information:When loading on site, first of all the order data must be downloadedfrom the Internet (see operating instructions manual "Oscillator&q

Page 40 - 7.1 Connecting the PC

l Please ask the agency serving you for the address of your returnshipment. You can find the respective agency on our websitewww.vega.com under: "

Page 41

9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pr essure in the vessel, high tempe

Page 42 - 8.2 Remove interferences

10 Supplement10.1 Technical dataGeneral data316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - thread PVDF, 316L- Seal - th

Page 43 - ? E041, E042, E043

InputvariableMeasured value distance between process fitting and product sur-faceMin. distance from antenna end 50 mm (1.969 in)Measuring range up to 3

Page 44 - 8.5 Instrument repair

1,0 m (3.28 ft)30 m (98.43 ft)20 mm (0.788 in)10 mm (0.394 in)- 10 mm (- 0.394 in)- 20 mm (- 0.788 in)0Fig. 29: Deviation VEGAPULS 65Influence of the

Page 45

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist

Page 46 - 9 Dismou

Vessel pressure- Screwed part PVDF -100 … 300 kPa/-1 … 3 bar (-14.5 … 43.5 psig)- Screwed part and flange 316L -100 … 1600 kPa/-1 … 16 bar (-14.5 … 232

Page 47 - 10 Supplem

Electromechanical data - version IP 66/IP 68 (1 bar)Cable entry- Single chamber housing 1 x IP 68 cable gland M20 x 1.5; 1 x blind stopperM20 x 1.5- D

Page 48

Power supply by/max. number of sensors- H1 power supply max. 32 (max. 10 with Ex)Electrical protective measuresProtection, depending on housing versio

Page 49

10.2 Foundation FieldbusBlock diagram, measured value processingThe following illustration shows the Transducer Block and Function block in simplified

Page 50

Secondary_value_1CalibrationLowest PointCalibrationHighest PointSensor_valuecal_level_local_level_hiCalibrationLowest PointCalibrationHighest PointSen

Page 51

l sensor_value- Raw sensor value, i.e. theuncalibrated measurement value from the sensor. Unit derives from'Sensor_range.unit'l sensor_range

Page 52

- Min./max.-adjustment: Level at 'Cal_point_lo'. When writing 'Cal_level_lo' and 'Cal_type' = 1(Online), the 'Cal_p

Page 53

- Distance from the sensor to the product surface. Unitderives from 'Sensor_range.unit'l empty_vessel_curve_corr_op_code- Update, createnew

Page 54

10.3 DimensionsHousing in protection IP 66/IP 68 (0.2 bar)~ 69 mm(2.72")ø 77 mm(3.03")112 mm (4 13/32")M20x1,5/½ NPT~ 69 mm(2.72")

Page 55

Housing in protection IP 66/IP 68 (1 bar)117 mm (4.61")~ 103 mm(4.06")ø 77 mm(3.03")116 mm (4.57")~ 150 mm (5.91")ø 84 mm (3.

Page 56

Duringthe entire duration of use, the user is obliged to determine thecompliance of the required occupational safety measures with thecurrent valid ru

Page 57 - - Update, create

VEGAPULS 65 - threaded version41 mm(1.61")ø 40 mm(1.58")ø 33 mm(1.30")ø 33 mm(1.30")82 mm (3.23")415 mm (16.34")120 mm (

Page 58 - 10.3 Dim

VEGAPULS 65 - flange versiondø 33 mm(1.30")395 mm (15.55")120 mm (4.72")270 mm (10.63")545 mm (21.46")94 mm (3.70")2 mm (

Page 59 - M20x1,5M20x1,5

10.4 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only

Page 60

VEGAPULS 65 • Foundation Fieldbus 6310 Supplement28452-EN-090305

Page 61

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9

Page 62 - 10.5 Trademark

l The instrument must not cause any interfering emissionsl The device must be insensitive to interfering immissions, includingthose that may cause und

Page 63

3 Product description3.1 ConfigurationThe scope of delivery encompasses:l VEGAPULS 65 radar sensorl Documentation- this operating instructions manual-

Page 64 - ISO 9001

321Fig. 1: VEGAPULS 65 - threadedversion with plastic housing1 Housing cover with integrated PLICSCOM (optional)2 Housing with electronics3 Process fit