Operating InstructionsVEGAPULS 65Foundation FieldbusRadar
3.2 Principle of operationVEGAPULS 65 is a radar sensor in C-band technology (emittingfrequency approx. 6 GHz) for continuous level measurement. It is
The entered parameters are generally saved in VEGAPULS 65,optionally also in the indicating and adjustment module or inPACTware.3.4 Packaging, transpo
4 Mounting4.1 General instructionsSelect an installation position you can easily reach for mounting andconnecting as well as later retrofitting of an i
1 32100%0%4Fig. 3: Measuringrange (operating range) and max. measuring distance1 full2 empty (max. measuring distance)3 Measuring rangeInformation:If
1Fig. 4: Positionof the polarisation plane with VEGAPULS 651 Marking holeMake sure that all parts of the instrument in contact with the measuredproduc
Whenmounting VEGAPULS 65, keep a distance of at least 500 mm(19.69 in) to the vessel wall. If the sensor is installed in the center ofdished or round
Fig. 6: Vesselwith conical bottomDo not mount the instruments in or above the filling stream. Make surethat you detect the product surface, not the infl
Fig. 8: Recommendedsocket mountingIn case of very big socket diameters, the active antenna part can beslightly recessed in the socket. The following r
Fig. 10: Coversmooth profiles with deflectorsIf there are agitators in the vessel, a false echo storage should becarried out with the agitators in motio
5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o
Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .
Insystems without potential equalisation, connect the cable screendirectly to ground potential at the power supply unit and at the sensor.In the conne
7 Insertthe wire ends into the open terminals according to the wiringplanFig. 12: Connectionsteps 6 and 78 Press down the opening levers of the termin
55551 243Fig. 13: Materialversions, single chamber housing1 Plastic2 Aluminium3 Stainless steel, investment casting4 Stainless steel, electro-polished
I2CDisplay11 2 56 7 8Fig. 15: Wiringplan, single chamber housing1 Voltage supply/Signal output5.4 Wiring plan, double chamber housingThe following ill
4I2C1 23I²C124DisplayTyp:1 2 5 6 7 8BusSim.Fig. 17: Electronicscompartment, double chamber housing1 Simulation switch ("on" = mode for simul
312Display1 2I²CFig. 18: Connectioncompartment, double chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Ground terminal for connection
1 2 345Fig. 20: Doublechamber housing1 Housing cover, connection compartment2 Blind stopper or plug M12 x 1 for VEGADIS 61 (optional)3 Housing cover,
121 2Fig. 22: Connectioncompartment double chamber housing Ex d1 Spring-loaded terminals for power supply and cable screen2 Ground terminal for connec
5.6 Wiring plan - version IP 66/IP 68, 1 bar+-12Fig. 24: Wireassignment, connection cable1 brown (+) and blue (-) to power supply or to the processing
6 Setup with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,
7.3 Parameter adjustment with AMS™ . . . . . . . . . . . . . .417.4 Saving the parameter adjustment data . . . . . . . . . . . .418 Maintenance and fa
Fig. 25: Insertindicating and adjustment moduleNote:Ifyou intend to retrofit the instrument with an indicating and adjustmentmodule for continuous meas
6.3 Adjustment system1.1231Fig. 26: Indicatingand adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov
6.4 SetupprocedureAs VEGAPULS 65 is a distance measuring instrument, the distancefrom the sensor to the product surface is measured. To have the realp
3 Prepare the % value for editing with [OK] and set the cursor to therequested position with [->]. Set the requested percentage valuewith [+] and s
Apart from the medium, the vessel shape can also influence themeasurement. To adapt the sensor to these measuring conditions, thismenu item offers differ
3 Confirm "False signal suppression - Change now" with [OK] andselect in the below menu "Create new". Enter the actual distancefrom
Copy sensor data?Additional adjustment and diagnosis options such as e.g. scaling,simulation or trend curve presentation are shown in the following me
6.5 MenuschematicInformation:Depending on the version and application, the light-coloured menuwindows are not always available or offer nor selection p
Service4Basic adjustmentDisplayDiagnostics▶ServiceInfo4.1Gating out of false signalsChange now?4.2Extended settingNone4.4SimulationStart simulation?▼4
6.6 Savingthe parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwar
1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as
7 Setupwith PACTware and other adjustmentprograms7.1 Connecting the PC312Fig. 27: Connectionof the PC via VEGACONNECT directly to the sensor1 USB cabl
Necessary components:l VEGAPULS 65l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system7.2 Parameter adjustmen
8 Maintenance and fault rectification8.1 MaintenanceWhen used in the correct way, no special maintenance is required innormal operation.8.2 Remove inte
In Exapplications, the regulations for the wiring of intrinsically safecircuits must be observed.? E013l no measured value availableà sensor in boot p
Information:When loading on site, first of all the order data must be downloadedfrom the Internet (see operating instructions manual "Oscillator&q
l Please ask the agency serving you for the address of your returnshipment. You can find the respective agency on our websitewww.vega.com under: "
9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pr essure in the vessel, high tempe
10 Supplement10.1 Technical dataGeneral data316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - thread PVDF, 316L- Seal - th
InputvariableMeasured value distance between process fitting and product sur-faceMin. distance from antenna end 50 mm (1.969 in)Measuring range up to 3
1,0 m (3.28 ft)30 m (98.43 ft)20 mm (0.788 in)10 mm (0.394 in)- 10 mm (- 0.394 in)- 20 mm (- 0.788 in)0Fig. 29: Deviation VEGAPULS 65Influence of the
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist
Vessel pressure- Screwed part PVDF -100 … 300 kPa/-1 … 3 bar (-14.5 … 43.5 psig)- Screwed part and flange 316L -100 … 1600 kPa/-1 … 16 bar (-14.5 … 232
Electromechanical data - version IP 66/IP 68 (1 bar)Cable entry- Single chamber housing 1 x IP 68 cable gland M20 x 1.5; 1 x blind stopperM20 x 1.5- D
Power supply by/max. number of sensors- H1 power supply max. 32 (max. 10 with Ex)Electrical protective measuresProtection, depending on housing versio
10.2 Foundation FieldbusBlock diagram, measured value processingThe following illustration shows the Transducer Block and Function block in simplified
Secondary_value_1CalibrationLowest PointCalibrationHighest PointSensor_valuecal_level_local_level_hiCalibrationLowest PointCalibrationHighest PointSen
l sensor_value- Raw sensor value, i.e. theuncalibrated measurement value from the sensor. Unit derives from'Sensor_range.unit'l sensor_range
- Min./max.-adjustment: Level at 'Cal_point_lo'. When writing 'Cal_level_lo' and 'Cal_type' = 1(Online), the 'Cal_p
- Distance from the sensor to the product surface. Unitderives from 'Sensor_range.unit'l empty_vessel_curve_corr_op_code- Update, createnew
10.3 DimensionsHousing in protection IP 66/IP 68 (0.2 bar)~ 69 mm(2.72")ø 77 mm(3.03")112 mm (4 13/32")M20x1,5/½ NPT~ 69 mm(2.72")
Housing in protection IP 66/IP 68 (1 bar)117 mm (4.61")~ 103 mm(4.06")ø 77 mm(3.03")116 mm (4.57")~ 150 mm (5.91")ø 84 mm (3.
Duringthe entire duration of use, the user is obliged to determine thecompliance of the required occupational safety measures with thecurrent valid ru
VEGAPULS 65 - threaded version41 mm(1.61")ø 40 mm(1.58")ø 33 mm(1.30")ø 33 mm(1.30")82 mm (3.23")415 mm (16.34")120 mm (
VEGAPULS 65 - flange versiondø 33 mm(1.30")395 mm (15.55")120 mm (4.72")270 mm (10.63")545 mm (21.46")94 mm (3.70")2 mm (
10.4 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only
VEGAPULS 65 • Foundation Fieldbus 6310 Supplement28452-EN-090305
VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9
l The instrument must not cause any interfering emissionsl The device must be insensitive to interfering immissions, includingthose that may cause und
3 Product description3.1 ConfigurationThe scope of delivery encompasses:l VEGAPULS 65 radar sensorl Documentation- this operating instructions manual-
321Fig. 1: VEGAPULS 65 - threadedversion with plastic housing1 Housing cover with integrated PLICSCOM (optional)2 Housing with electronics3 Process fit