Operating InstructionsTDR sensor for continuous level and interface measurement of liquidsVEGAFLEX 83Probus PAPolished versionDocument ID: 44223
103 Product descriptionVEGAFLEX 83 • Probus PA44223-EN-1309103 Product description3.1 CongurationThe nameplate contains the most important data fo
113 Product descriptionVEGAFLEX 83 • Probus PA44223-EN-130910This operating instructions manual applies to the following instrument versions:• Hardwa
123 Product descriptionVEGAFLEX 83 • Probus PA44223-EN-130910dh1Fig. 5: Level measurement1 Sensorreferenceplane(sealsurfaceoftheprocessttin
133 Product descriptionVEGAFLEX 83 • Probus PA44223-EN-130910TSd1h1h2d21L2L1L3Fig. 6: Interface measurement1 Sensorreferenceplane(sealsurfaceof
143 Product descriptionVEGAFLEX 83 • Probus PA44223-EN-130910The instrument is always preset to the application "Level measure-ment".For th
153 Product descriptionVEGAFLEX 83 • Probus PA44223-EN-130910You can nd further information in the operating instructions "Interface adapter VE
164 MountingVEGAFLEX 83 • Probus PA44223-EN-1309104 Mounting4.1 General instructionsProtect your instrument further through the following measures a
174 MountingVEGAFLEX 83 • Probus PA44223-EN-130910measurement all the way down to the tip of the probe may not be pos-sible. The exact value of the m
184 MountingVEGAFLEX 83 • Probus PA44223-EN-130910If possible, avoid sockets. Mount the sensor ush with the vessel top. If this is not possible, use
194 MountingVEGAFLEX 83 • Probus PA44223-EN-130910Do not mount the instruments in or above the lling stream. Make sure that you detect the product s
2Quick startVEGAFLEX 83 • Probus PA44223-EN-130910Quick startThe quick start procedure enables a quick setup of the instrument with many applications
204 MountingVEGAFLEX 83 • Probus PA44223-EN-130910In case of dicult installation conditions, for example in a socket, the probe can be adapted respe
215 Connecting to power supplyVEGAFLEX 83 • Probus PA44223-EN-1309105 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the
225 Connecting to power supplyVEGAFLEX 83 • Probus PA44223-EN-130910Information:The terminal block is pluggable and can be removed from the electroni
235 Connecting to power supplyVEGAFLEX 83 • Probus PA44223-EN-1309106. Insert the wire ends into the terminals according to the wiring planInformati
245 Connecting to power supplyVEGAFLEX 83 • Probus PA44223-EN-130910115005162738490516273849101678Bus2312+( )(-)Fig. 16: Electronics compartment, do
255 Connecting to power supplyVEGAFLEX 83 • Probus PA44223-EN-130910You can nd detailed information on connection in the supplementary instructions
265 Connecting to power supplyVEGAFLEX 83 • Probus PA44223-EN-130910312Fig. 21: View to the electronics compartment1 DIS-ADAPT2 Internal plug connec
275 Connecting to power supplyVEGAFLEX 83 • Probus PA44223-EN-1309105.7 Supplementary electronicsThe radio module PLICSMOBILE is an external GSM/GPR
285 Connecting to power supplyVEGAFLEX 83 • Probus PA44223-EN-1309105005162738490516273849101678Bus21312+( )(-)Fig. 25: Address selection switch1 A
296 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-1309106 Set up with the display and adjustment module6.1 Insert di
3Quick startVEGAFLEX 83 • Probus PA44223-EN-1309101. In this menu item you can select the application. You can choose between level and interface me
306 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-1309101 2Fig. 27: Insertion of the display and adjustment module int
316 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910 – Conrm selected menu – Edit parameter – Save value• [->]
326 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910You can nd "Extended adjustment" in the next sub-ch
336 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910Dielectric constant - upper mediumIn this menu item, you can d
346 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910False signal suppressionHigh sockets and internal vessel insta
356 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910Additional adjustments: Sensor address, PIN, date/time, reset,
366 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910• Capital letters from A … Z• Numbers from 0 … 9• Special char
376 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910Note:The selection of the application has a considerable inue
386 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910You can enter the dielectric constant of the upper medium dire
396 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910This menu item is only available if you have selected interfac
4Quick startVEGAFLEX 83 • Probus PA44223-EN-130910For this adjustment, the distance is entered when the vessel is full and nearly empty. If these val
406 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910be done with the lowest possible level so that all potential i
416 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910Warning:If a linearization curve is selected, the measuring si
426 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910In menu item"Channel" you determine which measured v
436 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910The following adjustment functions are possible without enteri
446 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910The default setting for the displayed value 2 is the electroni
456 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910In another window you can carry out a reset of the two peak va
466 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910Select the requested simulation size and adjust the requested
476 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910available if adjustment is enabled in the menu "Lock/Rele
486 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910Menu item Default value ModiedvalueMedium, dielectric consta
496 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910Menu item Default value ModiedvalueAI FB1 Fail Safe Mode (be
5ContentsVEGAFLEX 83 • Probus PA44223-EN-130910Contents1 About this document1.1 Function ...
506 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910Menu item Default value ModiedvalueAI FB2 Tag DescriptorAI F
516 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910Menu item Default value ModiedvalueAI FB3 Target Mode AutoTh
526 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910In this menu, you read out the instrument name and the instrum
536 Set up with the display and adjustment moduleVEGAFLEX 83 • Probus PA44223-EN-130910into the replacement instrument and the data are likewise writ
547 Setup with PACTwareVEGAFLEX 83 • Probus PA44223-EN-1309107 Setup with PACTware7.1 Connect the PC312Fig. 30: Connection of the PC directly to th
557 Setup with PACTwareVEGAFLEX 83 • Probus PA44223-EN-130910Fig. 31: Example of a DTM viewAll device DTMs are available as a free-of-charge standard
567 Setup with PACTwareVEGAFLEX 83 • Probus PA44223-EN-130910Fig. 32: Select quick setup1 Quick setup2 Extended adjustment3 MaintenanceQuick setupW
577 Setup with PACTwareVEGAFLEX 83 • Probus PA44223-EN-130910Serial numberHere, you can nd the serial number of your instrument. You cannot change t
587 Setup with PACTwareVEGAFLEX 83 • Probus PA44223-EN-130910Type of mediumHere you can see which type of medium your instrument is suitable for. If
597 Setup with PACTwareVEGAFLEX 83 • Probus PA44223-EN-130910Adjustment for the level measurementIf you have selected level measurement in the previo
6ContentsVEGAFLEX 83 • Probus PA44223-EN-1309109.2 Diagnosis memory ...
607 Setup with PACTwareVEGAFLEX 83 • Probus PA44223-EN-130910Displayeddistancecorrect?Is the displayed distance value correct? If you have the poss
618 Set up with other systemsVEGAFLEX 83 • Probus PA44223-EN-1309108 Set up with other systems8.1 DD adjustment programsDevice descriptions as Enha
629 Diagnostics and serviceVEGAFLEX 83 • Probus PA44223-EN-1309109 Diagnostics and service9.1 MaintenanceIf the device is used correctly, no mainten
639 Diagnostics and serviceVEGAFLEX 83 • Probus PA44223-EN-130910• Display and adjustment moduleFurther echo curves: Up to 10 echo curves can be stor
649 Diagnostics and serviceVEGAFLEX 83 • Probus PA44223-EN-130910still valid. Plan in maintenance for the instrument because a failure is expected i
659 Diagnostics and serviceVEGAFLEX 83 • Probus PA44223-EN-130910CodeText mes-sageCause Rectication PA DevS-pecDiagnosisF125Unper-missible electroni
669 Diagnostics and serviceVEGAFLEX 83 • Probus PA44223-EN-130910CodeText mes-sageCause RecticationS600Unpermissi-ble electronics temperature – Temp
679 Diagnostics and serviceVEGAFLEX 83 • Probus PA44223-EN-130910CodeText mes-sageCause RecticationM505No echo avail-able – Level echo can no longer
689 Diagnostics and serviceVEGAFLEX 83 • Probus PA44223-EN-130910Note:• Wherever the sensor displays a constant value, the reason could also be the f
699 Diagnostics and serviceVEGAFLEX 83 • Probus PA44223-EN-130910Measurement error during emptyingFault description Error pattern Cause Rectication7
71 About this documentVEGAFLEX 83 • Probus PA44223-EN-1309101 About this document1.1 FunctionThis operating instructions manual provides all the inf
709 Diagnostics and serviceVEGAFLEX 83 • Probus PA44223-EN-130910Measurement error with constant levelFault description Error pattern Cause Recticat
719 Diagnostics and serviceVEGAFLEX 83 • Probus PA44223-EN-130910Measurement error during emptyingFault description Error pattern Cause Rectication6
729 Diagnostics and serviceVEGAFLEX 83 • Probus PA44223-EN-130910• Or on site by the userIn both cases, the serial number of the sensor is needed. Th
739 Diagnostics and serviceVEGAFLEX 83 • Probus PA44223-EN-130910Fig. 52: Exchanging the measuring rodInformation:Please keep the stated torque so th
749 Diagnostics and serviceVEGAFLEX 83 • Probus PA44223-EN-130910Caution:Instruments with approvals can be bound to certain software ver-sions. There
7510 DismountingVEGAFLEX 83 • Probus PA44223-EN-13091010 Dismounting10.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process
7611 SupplementVEGAFLEX 83 • Probus PA44223-EN-13091011 Supplement11.1 Technical dataGeneral data316L corresponds to 1.4404 or 1.4435Materials, wett
7711 SupplementVEGAFLEX 83 • Probus PA44223-EN-130910Torque for exchangeable rod probe (in the process tting)4.5 Nm ±0.5 (3.32 lbf ft)Torque for NPT
7811 SupplementVEGAFLEX 83 • Probus PA44223-EN-130910Output variableOutput signal digital output signal, format according to IEEE-754Sensor address 1
7911 SupplementVEGAFLEX 83 • Probus PA44223-EN-130910L0-2mm (-0.079")2mm (0.079")15mm(0.591")-15mm (-0.591")0,2 m(7.874"
82 For your safetyVEGAFLEX 83 • Probus PA44223-EN-1309102 For your safety2.1 Authorised personnelAll operations described in this operating instruc
8011 SupplementVEGAFLEX 83 • Probus PA44223-EN-130910InuenceofthesuperimposedgasandpressuretotheaccuracyThe propagation speed of the radar
8111 SupplementVEGAFLEX 83 • Probus PA44223-EN-130910120°C(32°F)-40°C(-104°F)80°C(176°F)150°C(302°F)-20°C(-68°F)Fig. 56: Ambient temperature - proces
8211 SupplementVEGAFLEX 83 • Probus PA44223-EN-130910 Ʋ Cable gland with integrated connec-tion cableM20 x 1.5 (cable: ø 5 … 9 mm) Ʋ Cable entry ½ NP
8311 SupplementVEGAFLEX 83 • Probus PA44223-EN-130910 Ʋ EEx-ia instrument - Power supply ENTITY model9 … 24 V DC Ʋ EEx-d instrument 14 … 32 V DCNumbe
8411 SupplementVEGAFLEX 83 • Probus PA44223-EN-130910Device name Instrument ID GSDlenameVEGA Instrument class in prole3.02VEGA Prole-specicVEG
8511 SupplementVEGAFLEX 83 • Probus PA44223-EN-130910 – This module must be used if a value in the data telegram of the cyclical data trac should no
8611 SupplementVEGAFLEX 83 • Probus PA44223-EN-130910Byte nByte n+1Bit7VZExponentBit62Bit52Bit42Bit32Bit22Bit12Bit02Bit72Bit62Bit52Bit42Bit32Bit22Bit
8711 SupplementVEGAFLEX 83 • Probus PA44223-EN-130910Status code Description according to ProbusstandardPossible cause0 x 89 good (non-cascade) - a
8811 SupplementVEGAFLEX 83 • Probus PA44223-EN-130910Aluminium housing21ø 86 mm(3.39")~ 116 mm(4.57")116 mm(4.57")M20x1,5M20x1,5/½ NPT
8911 SupplementVEGAFLEX 83 • Probus PA44223-EN-130910Stainless steel housing~ 69 mm(2.72")ø 79 mm(3.11")117 mm(4.61")M20x1,5/½ NPT~ 59
92 For your safetyVEGAFLEX 83 • Probus PA44223-EN-130910Electromagnetic compatibilityInstruments with plastic housing as well as in four-wire or Ex-d
9011 SupplementVEGAFLEX 83 • Probus PA44223-EN-130910VEGAFLEX 83, rod version ø 8 mm (0.315 in), polishedL56 mm(2.20")ø 8 mm(0.32")Fig. 65:
9111 SupplementVEGAFLEX 83 • Probus PA44223-EN-130910VEGAFLEX 83, rod version ø 8 mm (0.315 in), polished - autoclaved version112 mm(4.84")DIN D
9211 SupplementVEGAFLEX 83 • Probus PA44223-EN-13091011.4 Industrial property rightsVEGA product lines are global protected by industrial property r
93INDEXVEGAFLEX 83 • Probus PA44223-EN-130910INDEXAAdjustment – Max. adjustment 38, 39 – Min. adjustment 38, 39Adjustment system 31AI FB1 Function
94INDEXVEGAFLEX 83 • Probus PA44223-EN-130910Scaling unit 42Sensor characteristics 52Sensor status 44Service – Hotline 71Setup – Quick start 2Si
95NotesVEGAFLEX 83 • Probus PA44223-EN-130910
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany44223-EN-130910All statements concerning scope of delivery, application, practi