Operating InstructionsSuspension pressure transmitter with CERTEC® measuring cellVEGABAR 66Probus PADocument ID: 36739
103 Product descriptionVEGABAR 66 • Probus PA36739-EN-130321Instruments with hygienic tting are equipped with a gap-free form seal.Power supply via
113 Product descriptionVEGABAR 66 • Probus PA36739-EN-130321The delivery must be checked for completeness and possible transit damage immediately at
123 Product descriptionVEGABAR 66 • Probus PA36739-EN-130321The protective cover protects the sensor housing against soiling and intense heat from so
134 MountingVEGABAR 66 • Probus PA36739-EN-1303214 Mounting4.1 General instructionsMake sure that all parts of the instrument coming in direct conta
144 MountingVEGABAR 66 • Probus PA36739-EN-13032121212112Fig. 4: Position of the lter element1 Filter element2 Blind plugCaution:Due to the lter
154 MountingVEGABAR 66 • Probus PA36739-EN-130321Fig. 5: Mounting example: Version with connection tube in an open vesselFig. 6: Mounting example: Ve
164 MountingVEGABAR 66 • Probus PA36739-EN-1303214.3 Mounting steps with straining clamp231Fig. 7: Straining clamp1 Suspension cable2 Suspension o
174 MountingVEGABAR 66 • Probus PA36739-EN-130321Mount VEGABAR 66 with screwed connection as follows:1. Weld the welded socket into the vessel top2.
184 MountingVEGABAR 66 • Probus PA36739-EN-1303213. Turn the lock tting on the lower hexagon into the welded socket. Use a resistant seal. Spanner
194 MountingVEGABAR 66 • Probus PA36739-EN-1303212. Insert the transmitter with connection tube or suspension cable into the opening of the mounting
2ContentsVEGABAR 66 • Probus PA36739-EN-130321Contents1 About this document1.1 Function ...
205 Connecting to power supplyVEGABAR 66 • Probus PA36739-EN-1303215 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the
215 Connecting to power supplyVEGABAR 66 • Probus PA36739-EN-130321next distributor must be connected to each other and also connected to ground pote
225 Connecting to power supplyVEGABAR 66 • Probus PA36739-EN-130321Fig. 12: Connection steps 6 and 7Proceed as follows:1. Loosen the four screws on
235 Connecting to power supplyVEGABAR 66 • Probus PA36739-EN-130321Information:The cable gland can be mounted in three positions each displaced by 90
245 Connecting to power supplyVEGABAR 66 • Probus PA36739-EN-130321I2CDisplay112 5 678Fig. 15: Wiring plan, single chamber housing1 Voltage supply,
255 Connecting to power supplyVEGABAR 66 • Probus PA36739-EN-130321123Display12I2CFig. 17: Connection compartment, double chamber housing1 Spring-lo
265 Connecting to power supplyVEGABAR 66 • Probus PA36739-EN-1303215.5 Wiring plan, double chamber housing Ex d132Display12 5678I2CFig. 19: Electron
275 Connecting to power supplyVEGABAR 66 • Probus PA36739-EN-130321112Fig. 21: Wiring plan, Ex-d double chamber housing1 Voltage supply, signal outp
285 Connecting to power supplyVEGABAR 66 • Probus PA36739-EN-1303215.7 Wiring plan, external housing with version IP 68Fig. 23: VEGABAR 66 in IP 68
295 Connecting to power supplyVEGABAR 66 • Probus PA36739-EN-130321567812DisplayI²C21543Fig. 24: Electronics and connection compartment1 Spring-load
3ContentsVEGABAR 66 • Probus PA36739-EN-1303217.1 Connect the PC via VEGACONNECT ...
305 Connecting to power supplyVEGABAR 66 • Probus PA36739-EN-1303211234634125Fig. 25: Connection of the sensor in the housing socket1 Brown2 Blue3
316 Set up with the display and adjustment module PLICSCOMVEGABAR 66 • Probus PA36739-EN-1303216 Set up with the display and adjustment module PLICS
326 Set up with the display and adjustment module PLICSCOMVEGABAR 66 • Probus PA36739-EN-130321Fig. 27: Insert display and adjustment moduleNote:If y
336 Set up with the display and adjustment module PLICSCOMVEGABAR 66 • Probus PA36739-EN-130321 – Save value• [->] key to select: – Menu change –
346 Set up with the display and adjustment module PLICSCOMVEGABAR 66 • Probus PA36739-EN-130321The display and adjustment module enables the adjustme
356 Set up with the display and adjustment module PLICSCOMVEGABAR 66 • Probus PA36739-EN-1303215. Select the requested unit, e.g. kg/dm³ with [->
366 Set up with the display and adjustment module PLICSCOMVEGABAR 66 • Probus PA36739-EN-130321Information:For an adjustment with lling, simply ente
376 Set up with the display and adjustment module PLICSCOMVEGABAR 66 • Probus PA36739-EN-130321You can nd the data on the type label on the instrume
386 Set up with the display and adjustment module PLICSCOMVEGABAR 66 • Probus PA36739-EN-1303214. Activate the selection with [OK] and select the re
396 Set up with the display and adjustment module PLICSCOMVEGABAR 66 • Probus PA36739-EN-130321If the adjustment ranges are exceeded, the message &qu
41 About this documentVEGABAR 66 • Probus PA36739-EN-1303211 About this document1.1 FunctionThis operating instructions manual provides all the info
406 Set up with the display and adjustment module PLICSCOMVEGABAR 66 • Probus PA36739-EN-130321This function enables reading out parameter adjustment
416 Set up with the display and adjustment module PLICSCOMVEGABAR 66 • Probus PA36739-EN-130321Menu section Function ResetvalueDamping 0 sLinearizat
426 Set up with the display and adjustment module PLICSCOMVEGABAR 66 • Probus PA36739-EN-130321Basic adjustment▶Basic adjustment 1DisplayDiagnosticsS
436 Set up with the display and adjustment module PLICSCOMVEGABAR 66 • Probus PA36739-EN-130321ServiceBasic adjustment 4DisplayDiagnostics▶ServiceInf
447 Set up with PACTware and other adjustment programsVEGABAR 66 • Probus PA36739-EN-1303217 Set up with PACTware and other adjustment programs7.1
457 Set up with PACTware and other adjustment programsVEGABAR 66 • Probus PA36739-EN-1303217.2 Parameter adjustment with PACTwareFurther setup steps
468 Maintenance and fault recticationVEGABAR 66 • Probus PA36739-EN-1303218 Maintenanceandfaultrectication8.1 MaintainIf the instrument is used
478 Maintenance and fault recticationVEGABAR 66 • Probus PA36739-EN-130321Error Cause RecticationWrong pres-entation of the measured value in Simat
488 Maintenance and fault recticationVEGABAR 66 • Probus PA36739-EN-1303218.3 Calculation of total deviation (according to DIN16086)The total devi
498 Maintenance and fault recticationVEGABAR 66 • Probus PA36739-EN-130321FKl = 0.1 %Fa = 0.15 %Fperf = √((0.05 %/10 K x 20 K x 1.4)2 + (0.1 %)2 + (
52 For your safetyVEGABAR 66 • Probus PA36739-EN-1303212 For your safety2.1 Authorised personnelAll operations described in this operating instruct
508 Maintenance and fault recticationVEGABAR 66 • Probus PA36739-EN-130321Connect the signal conditioning instrument to power supply and provide the
519 DismountingVEGABAR 66 • Probus PA36739-EN-1303219 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process cond
5210 SupplementVEGABAR 66 • Probus PA36739-EN-13032110 Supplement10.1 Technical dataGeneral dataMeasured variable LevelMeasuring principle Ceramic-c
5310 SupplementVEGABAR 66 • Probus PA36739-EN-130321 Ʋ Ohmic contact Between ground terminal, process tting and transmitter Ʋ Connection cable betwe
5410 SupplementVEGABAR 66 • Probus PA36739-EN-130321Resolution 1 °C (1.8 °F)Accuracy Ʋ in the range of 0 … +100 °C (+32 … +212 °F)±3 K Ʋ in the range
5510 SupplementVEGABAR 66 • Probus PA36739-EN-130321The specications are only an overview and refer to the measuring cell. Limitations due to the ma
5610 SupplementVEGABAR 66 • Probus PA36739-EN-130321Applies to the digital signal output (HART, Probus PA, Foundation Fieldbus) as well as to ana-lo
5710 SupplementVEGABAR 66 • Probus PA36739-EN-130321 Ʋ with measuring ranges 0.1 bar (1.45 psig) or 0.2 bar (2.9 psig)max. 15 bar (217.6 psig) or max
5810 SupplementVEGABAR 66 • Probus PA36739-EN-130321 Ʋ Single chamber housing – 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm), 1 x blind plug M20 x
5910 SupplementVEGABAR 66 • Probus PA36739-EN-130321Electromechanical data - version IP 68Cable entry/plug18) Ʋ External housing – 1 x cable gland M
62 For your safetyVEGABAR 66 • Probus PA36739-EN-1303212.6 CE conformityThis device fullls the legal requirements of the applicable EC guide-lines.
6010 SupplementVEGABAR 66 • Probus PA36739-EN-130321 Ʋ Exd instrument 14 … 32 V DCOperating voltage with illuminated display and adjustment module Ʋ
6110 SupplementVEGABAR 66 • Probus PA36739-EN-130321When using the prole-specic GSD le, the PA-OUT value as well as the temperature value are tran
6210 SupplementVEGABAR 66 • Probus PA36739-EN-130321Tip:The modules are available in two versions:• Short for Probus master supporting only one &quo
6310 SupplementVEGABAR 66 • Probus PA36739-EN-130321The status byte corresponds to prole 3.0 "Probus PA Prole for Process Control Devices&quo
6410 SupplementVEGABAR 66 • Probus PA36739-EN-130321Status codeDescription according to ProbusstandardPossible cause0 x 8e good (non-cascade) - act
6510 SupplementVEGABAR 66 • Probus PA36739-EN-130321Aluminium housing in protection rating IP 66/IP 68, 1 bar120 mm (4.72")~ 105 mm (4.13")
6610 SupplementVEGABAR 66 • Probus PA36739-EN-130321External housing with version IP 681265 mm(2.68")68 mm(2.68")92 mm(3.62")42mm(1.65
6710 SupplementVEGABAR 66 • Probus PA36739-EN-130321VEGABAR66,standardversion1 2 3 4 5 175 mm (6 57/64")52 mm (2 3/64")132 mm(5 13/64&
6810 SupplementVEGABAR 66 • Probus PA36739-EN-130321VEGABAR66,transmitter32mm1 2 3 4 5 175 mm (6 57/64")52 mm (2 3/64")178 mm(7 1/64&
6910 SupplementVEGABAR 66 • Probus PA36739-EN-130321VEGABAR66,PVDFversion1 2LL20 mm(25/32")22 mm(55/64")40 mm(1 37/64")SW 46 mm(1 1
73 Product descriptionVEGABAR 66 • Probus PA36739-EN-1303213 Product description3.1 CongurationThe scope of delivery encompasses:• VEGABAR 66 pres
7010 SupplementVEGABAR 66 • Probus PA36739-EN-130321VEGABAR66,angeconnection2 43/64"3 15/32"4 1/64"5 7/16"6 3/8"3 5/64&q
7110 SupplementVEGABAR 66 • Probus PA36739-EN-130321VEGABAR66,hygienicttingsø 78 mm (3 5/64")ø 92 mm (3 5/8")51 mm(2 1/64")L51 mm(
7210 SupplementVEGABAR 66 • Probus PA36739-EN-13032110.4 Industrial property rightsVEGA product lines are global protected by industrial property ri
73INDEXVEGABAR 66 • Probus PA36739-EN-130321INDEXAAccessories – Display and adjustment module 11 – External display and adjustment unit 11 – Flange
74NotesVEGABAR 66 • Probus PA36739-EN-130321
75NotesVEGABAR 66 • Probus PA36739-EN-130321
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany36739-EN-130321All statements concerning scope of delivery, application, practi
83 Product descriptionVEGABAR 66 • Probus PA36739-EN-1303211 2 3 4 4 5 6 Fig. 1: Example of a VEGABAR 66 with suspension cable (left) and connection
93 Product descriptionVEGABAR 66 • Probus PA36739-EN-1303212113105436789111214Fig. 2: Layout of the type label (example)1 Instrument type2 Product