Operating InstructionsVEGAPULS 674 … 20 mA/HART two-wireDocument ID:32938Radar

Page 2

Two-wire electronics 4 … 20 mA/HART for power supply andmeasured value transmission over the same cable.The supply voltage range can differ depending o

Page 3

Unless otherwise indicated, the packages must be stored only underthe following conditions:l Not in the openl Dry and dust freel Not exposed to corros

Page 4 - 1.3 Symbolism used

4 Mounting4.1 General instructionsSelect an installation position you can easily reach for mounting andconnecting as well as later retrofitting of an i

Page 5 - 2.3 Warning about misuse

1 32100%0%4Fig. 3: Measuringrange (operating range) and max. measuring distance1 full2 empty (max. measuring distance)3 Measuring range4 Reference pla

Page 6 - 2.7 Fulfillmen

1Fig. 4: Positionof the polarisation plane of VEGAPULS 671 Marking barsMake sure that all parts of the instrument exposed to the process, inparticular

Page 7

Fig. 5: Radarsensor with mounting strapThe strap is supplied unassembled and must be screwed to the sensorbefore setup with three hexagon nuts M5x10 a

Page 8 - 3 Produc

Fig. 6: Adjustmentof the angle of inclinationFig. 7: Turningby fastening in the centreThe compression flange allows mounting on a flange DN 80/ANSI 3&qu

Page 9 - 3.2 Principle of operation

Fig. 8: Flangemounting of the radar sensor4.3 Mounting instructionsMount VEGAPULS 67 at least 200 mm (7.874 in) away from the vesselwall.If you cannot

Page 10 - 3.3 Operation

Fig. 9: Recommendedsocket mountingIf the medium has good reflective properties, VEGAPULS 67 can alsobe mounted on a longer socket piece. Recommended va

Page 11 - 32938-EN-100514

Socketdiameter d Socket length h80 mm 300 mm100 mm 400 mm150 mm 500 mmSocket diameter d Socket length h3" 11.8 in4" 15.8 in6" 19.7 inTi

Page 12 - 4.1 General instructions

Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .

Page 13

The optimum mounting position is on the outer wall of the silo with thesensor oriented towards the outlet in the silo center.Fig. 12: Installationand

Page 14 - 4.2 Mounting preparation

be a place where no installations cross the microwave signals. Makesure when planning your measurement loop that the radar signalshave a "clear v

Page 15

the max. measuring rate must be observed (see chapter "Technicaldata").Fig. 16: Radarsensors on traverse crane22 VEGAPULS 67 • 4 … 20 mA/HAR

Page 16

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Page 17 - 4.3 Mounting instructions

Caution:Nogrease should be used when screwing the NPT cable gland orsteel tube into the threaded insert. Standard grease can containadditives that cor

Page 18

7 Insertthe wire ends into the open terminals according to the wiringplanFig. 17: Connectionsteps 6 and 78 Press down the opening levers of the termin

Page 19

55551 243Fig. 18: Materialversions, single chamber housing1 Plastic2 Aluminium3 Stainless steel, investment casting4 Stainless steel, electro-polished

Page 20

I²CDisplay1 2 5 6 7 83412Fig. 19: Electronicsand connection department with single chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Sp

Page 21

1 2 345Fig. 21: Doublechamber housing1 Housing cover, connection compartment2 Blind stopper or plug M12 x 1 for VEGADIS 61 (optional)3 Housing cover,

Page 22

312Display1 2I²CFig. 23: Connectioncompartment, double chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Ground terminal for connection

Page 23 - 5.1 Preparing the connection

7.3 Parameter adjustment with AMS™ and PDM . . . . . . .457.4 Saving the parameter adjustment data . . . . . . . . . . . .458 Maintenance and fault re

Page 24 - 5.2 Connection procedure

5.5 Wiring plan - version IP 66/IP 68, 1 bar+-12Fig. 25: Wireassignment connection cable1 brown (+) and blue (-) to power supply or to the processing

Page 25

6 Setup with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,

Page 26

Fig. 26: Insertindicating and adjustment moduleNote:Ifyou intend to retrofit the instrument with an indicating and adjustmentmodule for continuous meas

Page 27

6.3 Adjustment system1.1231Fig. 27: Indicatingand adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov

Page 28

6.4 SetupstepsIn HART-Multidrop mode (several sensors on one input) the addressmust be set before continuing with the parameter adjustment. You willfin

Page 29

Min. adjustment0.00 %=5.000 m (d)4.000 m (d)3 Prepare the % value for editing with [OK] and set the cursor to therequested position with [->]. Set

Page 30 - 5.6 Switch on phase

Inliquids, fluctuating surfaces and foam generation are furtherinterfering factors. To adapt the sensor to the different conditions, ageneral selection

Page 31 - 6.1 Short description

Information:However, the measuring signals are not damped by the product incompletely empty, closed metal vessels. Due to this, considerablemultiple r

Page 32

This function enables reading out parameter adjustment data as wellas writing parameter adjustment data into the sensor via the indicatingand adjustme

Page 33

Function ResetvalueCurrent output - characteristics 4 … 20 mACurrent output - max. current 20 mACurrent output - min. current 4 mACurrent output - fai

Page 34 - 6.4 Setup

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Page 35

6.5 MenuschematicInformation:Depending on the version and application, the light-coloured menuwindows are not always available or offer nor selection p

Page 36 - Linearisation curve

Diagnostics3Basic adjustmentDisplay▶DiagnosticsServiceInfo3.1PointerDistance min.: 0.234 m(d)Distance max.: 5.385 m(d)3.2Meas. reliability15 dBSensor

Page 37 - Extended setting

6.6 Savingthe parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwar

Page 38 - Copy sensor data?

7 Setup with PACTware and other adjustmentprograms7.1 Connect the PC via VEGACONNECT312Fig. 28: Connectionof the PC via VEGACONNECT directly to the se

Page 39

Necessary components:l VEGAPULS 67l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system12 43OPENTWISTUSBLOCKFi

Page 40 - 6.5 Menu

Note:Keepin mind that for setup of VEGAPULS 67, DTM-Collection in theactual version must be used.All currently available VEGA DTMs are included as a D

Page 41

8 Maintenance and fault rectification8.1 Maintenance, cleaningWhen the instrument is used properly, no special maintenance isrequired in normal operati

Page 42 - 6.6 Saving

Error Cause Removal4 … 20 mA signalnot stableLevel fluctuations Set damping via the indicating andadjustment module4 … 20 mA signalmissingElectrical co

Page 43

8.3 Exchanging the electronics moduleIf the electronics module is defective, it can be replaced by the user.In Ex applications only one instrument and

Page 44

Connect the sensor to power supply and provide connection from PCto the instrument via VEGACONNECT. Start PACTware and provideconnection to the sensor

Page 45

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist

Page 46 - 8.2 Rectify malfunctions

9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper

Page 47 - ? E041, E042, E043

10 Supplement10.1 Technical dataGeneral data316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Horn antenna PBT-GF30- Focussing lens PP- Ada

Page 48 - 8.4 Software update

InputvariableMeasured variable distance between process fitting and product sur-faceMin. distance from antenna end 50 mm (1.969 in)3)Measuring range up

Page 49 - 8.5 Instrument repair

30 mm (1.180 in)15 mm (0.590 in)0-15 mm (- 0.590 in)- 30 mm (- 1.180 in)1,0 m (3.280 ft)15 m (49.21 ft)Fig. 31: Deviation VEGAPULS 67Influence of the a

Page 50 - 9 Dismou

l 1 xclosing cap ½ NPT, 1 x blind plug ½ NPTor:l 1 x plug (depending on the version), 1 x blindstopper M20 x 1.5- Double chamber housing l 1 x cable e

Page 51 - 10 Supplem

Protection rating- unassembled IP 20- mounted into the sensor without cover IP 40Materials- Housing ABS- Inspection window Polyester foilVoltage suppl

Page 52

- Aluminium housing, stainless steelhousing - investment casting, stainlesssteel housing - electro-polishedIP 66/IP 68 (0.2 bar)10)- Aluminium and sta

Page 53

10.2 DimensionsHousing in protection IP 66/IP 68 (0.2 bar)~ 69 mm(2.72")ø 77 mm(3.03")112 mm (4 13/32")M20x1,5/½ NPT~ 69 mm(2.72")

Page 54

Housing in protection IP 66 /IP 68 (1 bar)117 mm (4.61")~ 103 mm(4.06")ø 77 mm(3.03")116 mm (4.57")~ 150 mm (5.91")ø 84 mm (3

Page 55

VEGAPULS 67 - version with mounting strap125 mm(4.92")2,5 mm(0.10")75 mm(2.95")107 mm(4.21")115 mm(4.53")300 mm(11.81")1

Page 56

Duringthe entire duration of use, the user is obliged to determine thecompliance of the required occupational safety measures with thecurrent valid ru

Page 57 - 10.2 Dim

VEGAPULS 67 - version with compression flange126 mm(4.96")10,5 mm(0.41")19 mm(0.75")ø 75 mm (2.95")ø 115 mm (4.53")ø 156 mm (6

Page 58 - M20x1,5M20x1,5

VEGAPULS 67 - version with adapter flange21DN100 PN16DN150 PN16ASME 4" 150psiASME 6" 150psiJIS DN100 10KJIS DN150 10KøD220285228,6279,4210280

Page 59

10.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only

Page 60

VEGAPULS 67 • 4 … 20 mA/HART two-wire 6310 Supplement32938-EN-100514

Page 61

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9

Page 62 - 10.4 Trademark

2. The instrument must operate unaffected by incoming interferenceradiation, also by such that may trigger unwanted operating conditions.The instrument

Page 63

3 Product description3.1 StructureThe scope of delivery encompasses:l VEGAPULS 67 radar sensorl Mounting strap (option)l Compression or adapter flange

Page 64 - ISO 9001

3 42 1 Fig. 1: VEGAPULS 67 - versionwith plastic housing1 Housing cover with integrated PLICSCOM (optional)2 Housing with electronics3 Process fitting