Operating InstructionsVEGAPULS 674 … 20 mA/HART two-wireDocument ID:32938Radar
Two-wire electronics 4 … 20 mA/HART for power supply andmeasured value transmission over the same cable.The supply voltage range can differ depending o
Unless otherwise indicated, the packages must be stored only underthe following conditions:l Not in the openl Dry and dust freel Not exposed to corros
4 Mounting4.1 General instructionsSelect an installation position you can easily reach for mounting andconnecting as well as later retrofitting of an i
1 32100%0%4Fig. 3: Measuringrange (operating range) and max. measuring distance1 full2 empty (max. measuring distance)3 Measuring range4 Reference pla
1Fig. 4: Positionof the polarisation plane of VEGAPULS 671 Marking barsMake sure that all parts of the instrument exposed to the process, inparticular
Fig. 5: Radarsensor with mounting strapThe strap is supplied unassembled and must be screwed to the sensorbefore setup with three hexagon nuts M5x10 a
Fig. 6: Adjustmentof the angle of inclinationFig. 7: Turningby fastening in the centreThe compression flange allows mounting on a flange DN 80/ANSI 3&qu
Fig. 8: Flangemounting of the radar sensor4.3 Mounting instructionsMount VEGAPULS 67 at least 200 mm (7.874 in) away from the vesselwall.If you cannot
Fig. 9: Recommendedsocket mountingIf the medium has good reflective properties, VEGAPULS 67 can alsobe mounted on a longer socket piece. Recommended va
Socketdiameter d Socket length h80 mm 300 mm100 mm 400 mm150 mm 500 mmSocket diameter d Socket length h3" 11.8 in4" 15.8 in6" 19.7 inTi
Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .
The optimum mounting position is on the outer wall of the silo with thesensor oriented towards the outlet in the silo center.Fig. 12: Installationand
be a place where no installations cross the microwave signals. Makesure when planning your measurement loop that the radar signalshave a "clear v
the max. measuring rate must be observed (see chapter "Technicaldata").Fig. 16: Radarsensors on traverse crane22 VEGAPULS 67 • 4 … 20 mA/HAR
5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o
Caution:Nogrease should be used when screwing the NPT cable gland orsteel tube into the threaded insert. Standard grease can containadditives that cor
7 Insertthe wire ends into the open terminals according to the wiringplanFig. 17: Connectionsteps 6 and 78 Press down the opening levers of the termin
55551 243Fig. 18: Materialversions, single chamber housing1 Plastic2 Aluminium3 Stainless steel, investment casting4 Stainless steel, electro-polished
I²CDisplay1 2 5 6 7 83412Fig. 19: Electronicsand connection department with single chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Sp
1 2 345Fig. 21: Doublechamber housing1 Housing cover, connection compartment2 Blind stopper or plug M12 x 1 for VEGADIS 61 (optional)3 Housing cover,
312Display1 2I²CFig. 23: Connectioncompartment, double chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Ground terminal for connection
7.3 Parameter adjustment with AMS™ and PDM . . . . . . .457.4 Saving the parameter adjustment data . . . . . . . . . . . .458 Maintenance and fault re
5.5 Wiring plan - version IP 66/IP 68, 1 bar+-12Fig. 25: Wireassignment connection cable1 brown (+) and blue (-) to power supply or to the processing
6 Setup with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,
Fig. 26: Insertindicating and adjustment moduleNote:Ifyou intend to retrofit the instrument with an indicating and adjustmentmodule for continuous meas
6.3 Adjustment system1.1231Fig. 27: Indicatingand adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov
6.4 SetupstepsIn HART-Multidrop mode (several sensors on one input) the addressmust be set before continuing with the parameter adjustment. You willfin
Min. adjustment0.00 %=5.000 m (d)4.000 m (d)3 Prepare the % value for editing with [OK] and set the cursor to therequested position with [->]. Set
Inliquids, fluctuating surfaces and foam generation are furtherinterfering factors. To adapt the sensor to the different conditions, ageneral selection
Information:However, the measuring signals are not damped by the product incompletely empty, closed metal vessels. Due to this, considerablemultiple r
This function enables reading out parameter adjustment data as wellas writing parameter adjustment data into the sensor via the indicatingand adjustme
Function ResetvalueCurrent output - characteristics 4 … 20 mACurrent output - max. current 20 mACurrent output - min. current 4 mACurrent output - fai
1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as
6.5 MenuschematicInformation:Depending on the version and application, the light-coloured menuwindows are not always available or offer nor selection p
Diagnostics3Basic adjustmentDisplay▶DiagnosticsServiceInfo3.1PointerDistance min.: 0.234 m(d)Distance max.: 5.385 m(d)3.2Meas. reliability15 dBSensor
6.6 Savingthe parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwar
7 Setup with PACTware and other adjustmentprograms7.1 Connect the PC via VEGACONNECT312Fig. 28: Connectionof the PC via VEGACONNECT directly to the se
Necessary components:l VEGAPULS 67l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system12 43OPENTWISTUSBLOCKFi
Note:Keepin mind that for setup of VEGAPULS 67, DTM-Collection in theactual version must be used.All currently available VEGA DTMs are included as a D
8 Maintenance and fault rectification8.1 Maintenance, cleaningWhen the instrument is used properly, no special maintenance isrequired in normal operati
Error Cause Removal4 … 20 mA signalnot stableLevel fluctuations Set damping via the indicating andadjustment module4 … 20 mA signalmissingElectrical co
8.3 Exchanging the electronics moduleIf the electronics module is defective, it can be replaced by the user.In Ex applications only one instrument and
Connect the sensor to power supply and provide connection from PCto the instrument via VEGACONNECT. Start PACTware and provideconnection to the sensor
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist
9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper
10 Supplement10.1 Technical dataGeneral data316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Horn antenna PBT-GF30- Focussing lens PP- Ada
InputvariableMeasured variable distance between process fitting and product sur-faceMin. distance from antenna end 50 mm (1.969 in)3)Measuring range up
30 mm (1.180 in)15 mm (0.590 in)0-15 mm (- 0.590 in)- 30 mm (- 1.180 in)1,0 m (3.280 ft)15 m (49.21 ft)Fig. 31: Deviation VEGAPULS 67Influence of the a
l 1 xclosing cap ½ NPT, 1 x blind plug ½ NPTor:l 1 x plug (depending on the version), 1 x blindstopper M20 x 1.5- Double chamber housing l 1 x cable e
Protection rating- unassembled IP 20- mounted into the sensor without cover IP 40Materials- Housing ABS- Inspection window Polyester foilVoltage suppl
- Aluminium housing, stainless steelhousing - investment casting, stainlesssteel housing - electro-polishedIP 66/IP 68 (0.2 bar)10)- Aluminium and sta
10.2 DimensionsHousing in protection IP 66/IP 68 (0.2 bar)~ 69 mm(2.72")ø 77 mm(3.03")112 mm (4 13/32")M20x1,5/½ NPT~ 69 mm(2.72")
Housing in protection IP 66 /IP 68 (1 bar)117 mm (4.61")~ 103 mm(4.06")ø 77 mm(3.03")116 mm (4.57")~ 150 mm (5.91")ø 84 mm (3
VEGAPULS 67 - version with mounting strap125 mm(4.92")2,5 mm(0.10")75 mm(2.95")107 mm(4.21")115 mm(4.53")300 mm(11.81")1
Duringthe entire duration of use, the user is obliged to determine thecompliance of the required occupational safety measures with thecurrent valid ru
VEGAPULS 67 - version with compression flange126 mm(4.96")10,5 mm(0.41")19 mm(0.75")ø 75 mm (2.95")ø 115 mm (4.53")ø 156 mm (6
VEGAPULS 67 - version with adapter flange21DN100 PN16DN150 PN16ASME 4" 150psiASME 6" 150psiJIS DN100 10KJIS DN150 10KøD220285228,6279,4210280
10.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only
VEGAPULS 67 • 4 … 20 mA/HART two-wire 6310 Supplement32938-EN-100514
VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9
2. The instrument must operate unaffected by incoming interferenceradiation, also by such that may trigger unwanted operating conditions.The instrument
3 Product description3.1 StructureThe scope of delivery encompasses:l VEGAPULS 67 radar sensorl Mounting strap (option)l Compression or adapter flange
3 42 1 Fig. 1: VEGAPULS 67 - versionwith plastic housing1 Housing cover with integrated PLICSCOM (optional)2 Housing with electronics3 Process fitting