Operating InstructionsTDR sensor for continuous level and interface measurement of liquidsVEGAFLEX 86Foundation FieldbusCoax probeDocument ID: 44230

Page 2 - Quick start

103 Product descriptionVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910This operating instructions manual applies to the following instrument versions

Page 3

113 Product descriptionVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910dh1Fig. 4: Level measurement1 Sensorreferenceplane(sealsurfaceoftheproc

Page 4 - Contents

123 Product descriptionVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910TSd1h1h2d21L2L1L3Fig. 5: Interface measurement1 Sensorreferenceplane(seals

Page 5

133 Product descriptionVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910The instrument is always preset to the application "Level measure-ment&quo

Page 6 - 1 About this document

143 Product descriptionVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910You can nd further information in the operating instructions "Interface a

Page 7 - 2 For your safety

154 MountingVEGAFLEX 86 • Foundation Fieldbus44230-EN-1309104 Mounting4.1 General instructionsOn instruments with process tting thread, the hexagon

Page 8 - 2.6 NAMUR recommendations

164 MountingVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910In vessels with conical bottom it can be advantageous to mount the sensor in the center of

Page 9 - 3 Product description

174 MountingVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910The reference plane for the measuring range of the sensors is the sealing surface of the t

Page 10 - 3.2 Principle of operation

184 MountingVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Corrective value in the process control systemIn the technical data under "Inuence o

Page 11 - 3 Product description

195 Connecting to power supplyVEGAFLEX 86 • Foundation Fieldbus44230-EN-1309105 Connecting to power supply5.1 Preparing the connectionAlways keep in

Page 12

2Quick startVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Quick startThe quick start procedure enables a quick setup of the instrument with many app

Page 13

205 Connecting to power supplyVEGAFLEX 86 • Foundation Fieldbus44230-EN-1309101. Unscrew the housing cover2. If a display and adjustment module is i

Page 14

215 Connecting to power supplyVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910the terminal opening is freed. When the screwdriver is released, the ter

Page 15 - 4 Mounting

225 Connecting to power supplyVEGAFLEX 86 • Foundation Fieldbus44230-EN-13091050101+678Bus2312( )(-)11Fig. 13: Electronics compartment, double chambe

Page 16

235 Connecting to power supplyVEGAFLEX 86 • Foundation Fieldbus44230-EN-1309105.5 Wiring plan, Ex-d-ia double chamber housing50101+678Bus2312( )(-)4

Page 17 - 1 Temperature insulation

245 Connecting to power supplyVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910312Fig. 18: View to the electronics compartment1 DIS-ADAPT2 Internal pl

Page 18

255 Connecting to power supplyVEGAFLEX 86 • Foundation Fieldbus44230-EN-1309105.7 Supplementary electronicsThe radio module PLICSMOBILE is an externa

Page 19 - 5 Connecting to power supply

266 Set up with the display and adjustment moduleVEGAFLEX 86 • Foundation Fieldbus44230-EN-1309106 Set up with the display and adjustment module6.1

Page 20 - 5 Connecting to power supply

276 Set up with the display and adjustment moduleVEGAFLEX 86 • Foundation Fieldbus44230-EN-1309101 2Fig. 23: Insertion of the display and adjustment m

Page 21

286 Set up with the display and adjustment moduleVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910 – Conrm selected menu – Edit parameter – Save value

Page 22

296 Set up with the display and adjustment moduleVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910You can nd "Extended adjustment" in the ne

Page 23

3Quick startVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910horizontal cylindrical or spherical tank. Activate the appropriate curve.5. A "False

Page 24

306 Set up with the display and adjustment moduleVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910centage value. The distance refers tot he sensor refe

Page 25

316 Set up with the display and adjustment moduleVEGAFLEX 86 • Foundation Fieldbus44230-EN-1309106.4 Parameter adjustment - Extended adjustmentFor te

Page 26

326 Set up with the display and adjustment moduleVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910In this menu item you can enter the probe length or h

Page 27

336 Set up with the display and adjustment moduleVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Dielectric con-stantType of medium Examples< 3 Hyd

Page 28

346 Set up with the display and adjustment moduleVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910In this menu item you can enter the min. adjustment f

Page 29

356 Set up with the display and adjustment moduleVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910If you have selected "No", you can enter th

Page 30

366 Set up with the display and adjustment moduleVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910The instrument carries out an automatic false signal

Page 31

376 Set up with the display and adjustment moduleVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910+ hD- hFig. 25: Vessel height und socket correction v

Page 32

386 Set up with the display and adjustment moduleVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Caution:With active PIN, adjustment via PACTware/DTM

Page 33 - Type of medium Examples

396 Set up with the display and adjustment moduleVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910The lighting is switched o in the delivery status.In

Page 34

4ContentsVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Contents1 About this document1.1 Function ...

Page 35

406 Set up with the display and adjustment moduleVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910The respective min. and max. measured values are save

Page 36

416 Set up with the display and adjustment moduleVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Caution:During simulation, the simulated value is out

Page 37 - D Vessel height

426 Set up with the display and adjustment moduleVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910In delivery status, the PIN is "0000".In th

Page 38

436 Set up with the display and adjustment moduleVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Menu item Default value ModiedvalueMax. adjustment

Page 39

446 Set up with the display and adjustment moduleVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Menu item Default value ModiedvalueDevice memory -

Page 40

456 Set up with the display and adjustment moduleVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910In this menu item you gain access to the protected ar

Page 41

466 Set up with the display and adjustment moduleVEGAFLEX 86 • Foundation Fieldbus44230-EN-1309106.5 Saving the parameter adjustment dataWe recommend

Page 42

477 Setup with PACTwareVEGAFLEX 86 • Foundation Fieldbus44230-EN-1309107 Setup with PACTware7.1 Connect the PC312Fig. 26: Connection of the PC direc

Page 43 - Diagnostics

487 Setup with PACTwareVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Fig. 27: Example of a DTM viewAll device DTMs are available as a free-of-charge

Page 44

497 Setup with PACTwareVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Fig. 28: Select quick setup1 Quick setup2 Extended adjustment3 MaintenanceQui

Page 45

5ContentsVEGAFLEX 86 • Foundation Fieldbus44230-EN-1309109.2 Diagnosis memory ...

Page 46

507 Setup with PACTwareVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Serial numberHere, you can nd the serial number of your instrument. You cannot

Page 47 - 7 Setup with PACTware

517 Setup with PACTwareVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Demonstration mode: This mode is only suitable for test and demon-stration purp

Page 48 - 7 Setup with PACTware

527 Setup with PACTwareVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910You must enter the following vessel dimensions with non-linear condi-tions:• He

Page 49 - 3 Maintenance

537 Setup with PACTwareVEGAFLEX 86 • Foundation Fieldbus44230-EN-1309107.4 Saving the parameter adjustment dataWe recommend documenting or saving the

Page 50

548 Set up with other systemsVEGAFLEX 86 • Foundation Fieldbus44230-EN-1309108 Set up with other systems8.1 DD adjustment programsDevice description

Page 51

559 Diagnostics and serviceVEGAFLEX 86 • Foundation Fieldbus44230-EN-1309109 Diagnostics and service9.1 MaintenanceIf the device is used correctly, n

Page 52

569 Diagnostics and serviceVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910• Display and adjustment moduleFurther echo curves: Up to 10 echo curves ca

Page 53

579 Diagnostics and serviceVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910still valid. Plan in maintenance for the instrument because a failure is e

Page 54 - 8 Set up with other systems

589 Diagnostics and serviceVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910CodeText mes-sageCause Rectication PA DevS-pecDiagnosisF125Unper-missible

Page 55 - 9 Diagnostics and service

599 Diagnostics and serviceVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910CodeText mes-sageCause RecticationS600Unpermissi-ble electronics temperatu

Page 56 - 9 Diagnostics and service

61 About this documentVEGAFLEX 86 • Foundation Fieldbus44230-EN-1309101 About this document1.1 FunctionThis operating instructions manual provides al

Page 57

609 Diagnostics and serviceVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910CodeText mes-sageCause RecticationM505No echo avail-able – Level echo can

Page 58

619 Diagnostics and serviceVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Note:• Wherever the sensor displays a constant value, the reason could also

Page 59

629 Diagnostics and serviceVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Measurement error during emptyingFault description Error pattern Cause Rect

Page 60

639 Diagnostics and serviceVEGAFLEX 86 • Foundation Fieldbus44230-EN-1309109.6 Software updateThe following components are required to update the sen

Page 61

6410 DismountingVEGAFLEX 86 • Foundation Fieldbus44230-EN-13091010 Dismounting10.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous

Page 62

6511 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-13091011 Supplement11.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4

Page 63 - 9.6 Software update

6611 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910 Ʋ Tube: ø 42.2 mm (1.661 in) 300 Nm (221 lbf ft)Torque for NPT cable glands and Condui

Page 64 - 10 Dismounting

6711 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-13091024351

Page 65 - 11 Supplement

6811 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Fig. 39: Measuring ranges - VEGAFLEX 861 Reference plane2 Probe length L3 Measuring

Page 66

6911 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Max. deviation - Version with reference distance± 10 mm (0.39 in)Deviating upper dead b

Page 67

72 For your safetyVEGAFLEX 86 • Foundation Fieldbus44230-EN-1309102 For your safety2.1 Authorised personnelAll operations described in this operatin

Page 68

7011 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910The following table shows the resulting deviation for some typical gases and vapours. T

Page 69

7111 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910120°C(32°F)-40°C(-104°F)65°C(149°F)80°C(176°F)280°C(536°F)250°C(482°F)190°C(374°F)34-19

Page 70

7211 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-13091021-100°C(-148°F)-200°C(-328°F)100 bar(1450 psig)200 bar(2900 psig)300 bar(4350 psig)400

Page 71

7311 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Electromechanical data - version IP 66/IP 68 (1 bar)Options of the cable entry Ʋ Cable

Page 72 - 2 Process pressure

7411 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910 Ʋ Non-Ex instrument 9 … 32 V DC Ʋ EEx-ia instrument - Power supply FISCO model9 … 17.5

Page 73

7511 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Electricial Characteristics Physicial Layer Type Low-power signaling, bus-pow-ered, FIS

Page 74

7611 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910m(d)% Lin%PrimaryValueSecondaryValue 2SecondaryValue 1TBSensor_Valuemin/maxadjustmentLi

Page 75 - Function blocks

7711 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Function block PID ControlThe function block "PID Control " is a key componen

Page 76

7811 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Fig. 49: Schematic presentation function block Output SplitterFunction block Signal Cha

Page 77

7911 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Fig. 50: Schematic presentation function block Signal CharacterizerFunction block Integ

Page 78

82 For your safetyVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Electromagnetic compatibilityInstruments with plastic housing as well as in four-wir

Page 79

8011 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Fig. 51: Schematic presentation function block IntegratorFunction block Input SelectorT

Page 80

8111 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Fig. 52: Schematic presentation function block Input SelectorFunction block ArithmeticT

Page 81

8211 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Fig. 53: Schematic presentation function block ArithmeticParameter listThe following ta

Page 82 - Parameter list

8311 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910FF desciptor Description UnitDIAG_MASK_2DIAG_OUT_2DEVICE_IDENTIFICATION Manufacturer ID

Page 83

8411 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910FF desciptor Description UnitGU_ID_ENDECHO_CURVE_READ Echo curve dataECHO_EVALUATOR Ech

Page 84

8511 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910FF desciptor Description UnitNOISE_DETECTION_INFO Increase of the system noiseNOISE_DET

Page 85 - Aluminium housing

8611 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Aluminium housing in protection rating IP 66/IP 68 (1 bar)120 mm(4.72")~ 105 mm(4.

Page 86 - Stainless steel housing

8711 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Stainless steel housing in protection rating IP 66/IP 68, 1 bar117 mm(4.61")~ 103

Page 87 - (4.41")

8811 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910VEGAFLEX 86, coax versionG1½ /1½ NPTø 42,2 mm(1.66")L 312 mm (12.28")57 mm(2.

Page 88 - VEGAFLEX 86, coax version

8911 SupplementVEGAFLEX 86 • Foundation Fieldbus44230-EN-13091011.4 Industrial property rightsVEGA product lines are global protected by industrial p

Page 89 - 11.5 Trademark

93 Product descriptionVEGAFLEX 86 • Foundation Fieldbus44230-EN-1309103 Product description3.1 CongurationThe nameplate contains the most important

Page 90

90INDEXVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910INDEXAAdjustment – Max. adjustment 33, 34 – Min. adjustment 34Adjustment system 28Applicatio

Page 91

91INDEXVEGAFLEX 86 • Foundation Fieldbus44230-EN-130910Sensor status 39Service – Hotline 62Setup – Quick start 2Simulation 40Special parameters 4

Page 92 - Printing date:

Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany44230-EN-130910All statements concerning scope of delivery, application, practi