Page 1 - Operating Instructions

Operating InstructionsVEGAFLEX 65Foundation FieldbusDocument ID:31848Guided Microwave

Page 2 - Contents

4 Mounting4.1 General instructionsMake sure that all parts of the instrument exposed to the process, inparticular the sensor element, process seal and

Page 3

Fig. 2: Measures against moisture penetrationThe reference plane for the measuring range of the sensors is the sealsurface of the thread.Keep in mind

Page 4 - 1 About this document

In vessels with conical bottom it can b e advantageous to mount thesensor in the center of the vessel, as measurement is then possibledown to the lowe

Page 5 - 2 For your safety

more than 1 m (3.281 in) length, you must secure the probe byfastening a suitable isolated brace or guy directly above the end of therod.VEGAFLEX 65 •

Page 6 - 2.6 CE conformity

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Page 7 - 3 Product description

In systems without potential equalisation, connect the cable screendirectly to ground potential at the power supply unit and at the sensor.In the conn

Page 8 - 3.3 Operation

7 Insert the wire ends into the open terminals according to the wiringplanFig. 5: Connection steps 6 and 78 Press down the opening levers of the termi

Page 9

I²C34512DisplayTyp:1 2 5 6 7 8 BusSim.Fig. 6: Electronics and connection compartment, single chamber housing1 Plug connector for VEGACONNECT (I²C inte

Page 10 - 4 Mounting

I²C231DisplayTyp:1 2 5 6 7 8BusSim.Fig. 8: Electronics compartment, double chamber housing1 Simulation switch ("on" = mode for simulation re

Page 11 - 31848-EN-120329

I2C11 2Fig. 10: Wiring plan, double chamber housing1 Voltage supply, signal output5.5 Wiring plan - version IP 66/IP 68, 1 bar12Fig. 11: Wire assignme

Page 12

Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .

Page 13

6 Set up with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,

Page 14 - 5 Connecting to power supply

Fig. 12: Insert indicating and adjustment moduleNote:If you intend to retrofit the instrument with an indicating and adjustmentmodule for continuous me

Page 15 - 5.2 Connection procedure

6.3 Adjustment system2311.1Fig. 13: Indicating and adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mo

Page 16

6.4 Setup stepsAfter VEGAFLEX 65 is connected to voltage supply or after voltagerecurrence, the instrument carries out a self-check for approx. 30seco

Page 17

1 Move from the measured value display to the main menu bypushing [OK].▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Select the menu item "Basi

Page 18

ApplicationLiquidStandard(DK ≥ 2)Measured products have different reflective properties depending ontheir respective permittivity (dielectric constant).

Page 19

This function enables reading out parameter adjustment data as wellas writing parameter adjustment data into the sensor via the indicatingand adjustme

Page 20 - 6.1 Short description

Function Reset valueLanguage No resetFactory settingLike basic adjustment, but in addition, special parameters are reset todefault values.3)Peak value

Page 21

6.5 Menu schematicBasic adjustment1▶Basic adjustmentDisplayDiagnosticsServiceInfo1.1Min. adjustment000.0 %=10.000 m(d)1.245 m(d)1.2Max. adjustment100.

Page 22 - 6.3 Adjustment system

Service4Basic adjustmentDisplayDiagnostics▶ServiceInfo4.2ApplicationLiquidStandard(DK ≥ 2)4.3False signal suppressionChange now?4.4SimulationStart sim

Page 23 - 6.4 Setup steps

8 Maintenance and fault rectification8.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .338.2 Remove interferences. . . . . . .

Page 24

6.6 Saving the parameter adjustment dataWe recommended noting the adjusted data, e.g. in this operatinginstructions manual, and archiving them afterwa

Page 25

7 Set up with PACTware and other adjustmentprograms7.1 Connect the PC312Fig. 14: Connection of the PC via VEGACONNECT directly to the sensor1 USB cabl

Page 26 - Copy sensor data?

Necessary components:l VEGAFLEX 65l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system7.2 Parameter adjustmen

Page 27

8 Maintenance and fault rectification8.1 MaintenanceIf the instrument is used properly, no special maintenance is requiredin normal operation.8.2 Remov

Page 28 - 6.5 Menu schematic

Error Cause RectificationInstrument doesnot appear duringconnection setupProfibus DP cab-le pole-reversedCheck cable and correct, if necessaryIncorrect

Page 29

8.3 Exchanging the electronics moduleIf the electronics module is defective, it can be replaced by the user.In Ex applications only one instrument and

Page 30

At "www.vega.com/downloads" go to "Software". Select under "plicssensors and instruments", "Firmware updates"

Page 31 - 7.1 Connect the PC

9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper

Page 32

10 Supplement10.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting 316L and TFM PCTFE +2

Page 33 - 8.2 Remove interferences

Input variableMeasured variable Level of liquidsMin. dielectric figure of the medium εr> 1.42453124531Fig. 16: Measuring ranges of VEGAFLEX 651 Refe

Page 34

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Page 35 - 8.4 Software update

Transmission rate 31.25 Kbit/sCurrent value 10 mA, ±0.5 mAResolution, digital > 1 mm (0.039 in)Accuracy (according to DIN EN 60770-1)Process refere

Page 36 - 8.5 Instrument repair

L0-2 mm (-0.079")2 mm (0.079")10 mm (0.394")5 mm (0.197")-5 mm (-0.197")0,15 m (5.906")0,1 m (3.937")0,15 m(5.906&q

Page 37 - 9 Dismounting

0°C(32°F)40°C(104°F)20°C(58°F)60°C(140°F)80°C(176°F)50°C(122°F)-40°C(-40°F)100°C(212°F)150°C(302°F)12Fig. 19: Ambient temperature -

Page 38 - 10 Supplement

Spring-loaded terminals for wire cross-sec-tion< 2.5 mm² (AWG 14)Electromechanical data - version IP 66/IP 68 (1 bar)Cable entry- Single chamber ho

Page 39

Power supply by/max. number of sensors- H1 power supply max. 32 (max. 10 with Ex)Electrical protective measuresProtection, depending on housing versio

Page 40

10.2 Foundation FieldbusBlock diagram, measured value processingThe following illustration shows the Transducer Block (TB) and Function block (FB) in

Page 41

Diagram, adjustmentThe following illustration shows the function of the adjustment.Secondary_value_1CalibrationLowest PointCalibrationHighest PointSen

Page 42

l secondary_value_2- This is the distance value (sensor_value) with the status of the transducer block- It is the input for the AIFB when CHANNEL = 3

Page 43

- Min./Max. adjustment: this is the value of level at "Calibration Lowest Point". The unit isdefined in "level_unit"- When writing

Page 44

10.3 DimensionsThe following dimensional drawings represent only an extract of thepossible versions. Detailed dimensional drawings can be downloadedon

Page 45 - 10.2 Foundation Fieldbus

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist

Page 46

Aluminium housing in protection rating IP 66/IP 68, 1 bar120 mm (4.72")~ 105 mm (4.13")116 mm (4.57")~ 150 mm (5.91")ø 84 mm (3.31

Page 47

VEGAFLEX 65, threaded versionL 36 (G¾, ¾ NPT) 41 (G1, 1 NPT) 46 (G1½, 1½ NPT) G¾, ¾ NPT, G1, 1 NPT, G1½, 1½ NPT 46 mm(1 13/16")27mm (1 1/16"

Page 48

VEGAFLEX 65, flange versionLbLbDd dDkk68mm(2.68")46mm(1.81")D b kdDN 25 PN 40 115 18 85 4x ø 14DN 40 PN 40 150 18 110 4x ø 181" 150 lb

Page 49 - 10.3 Dimensions

10.4 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only

Page 50 - Stainless steel housing

54 VEGAFLEX 65 • Foundation Fieldbus10 Supplement31848-EN-120329

Page 51 - , threaded version

VEGAFLEX 65 • Foundation Fieldbus 5510 Supplement31848-EN-120329

Page 52 - , flange version

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9

Page 53 - 10.5 Trademark

2.5 Safety label on the instrumentThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device fulfills the

Page 54

3 Product description3.1 StructureThe scope of delivery encompasses:l Level sensor VEGAFLEX 65l Documentation- this operating instructions manual- Ope

Page 55

l Article numbers, documentationWith the serial number, you can access the delivery data of theinstrument viawww.vega.com, "VEGA Tools" and

Page 56 - ISO 9001

3.4 Packaging, transport and storageYour instrument was protected by packaging during transport. Itscapacity to handle normal loads during transport i