Operating InstructionsSuspension pressure transmitter with metal measuring cellVEGABAR 874 … 20 mADocument ID: 45507
103 Product descriptionVEGABAR 87 • 4 … 20 mA45507-EN-1310103.3 Packaging, transport and storageYour instrument was protected by packaging during tra
113 Product descriptionVEGABAR 87 • 4 … 20 mA45507-EN-131010Youcanndfurtherinformationintheoperatinginstructions"VE-GADIS 62" (Doc
124 MountingVEGABAR 87 • 4 … 20 mA45507-EN-1310104 Mounting4.1 General instructions to use the instrumentMake sure that all parts of the instrument e
134 MountingVEGABAR 87 • 4 … 20 mA45507-EN-13101021Fig. 4: Temperature ranges1 Process temperature2 Ambient temperature4.2 Ventilation and pressure
144 MountingVEGABAR 87 • 4 … 20 mA45507-EN-1310101 2 34 4 4Fig. 5: Position of the lter element - non-Ex, Ex-ia version1 Plastic, stainless steel pr
154 MountingVEGABAR 87 • 4 … 20 mA45507-EN-131010• Donotmounttheinstrumentclosetothellingstreamoremptyingarea• Mount the instrument so th
164 MountingVEGABAR 87 • 4 … 20 mA45507-EN-13101090 mm(3.54")R 3,5 mm(0.14")3mm(0.12")70 mm(2.76")8 mm(0.32")93 mm(3.66"
175 Connecting to power supplyVEGABAR 87 • 4 … 20 mA45507-EN-1310105 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the f
185 Connecting to power supplyVEGABAR 87 • 4 … 20 mA45507-EN-131010This can lead to unacceptably high shield currents if the cable shield is grounded
195 Connecting to power supplyVEGABAR 87 • 4 … 20 mA45507-EN-131010Information:Solidcoresaswellasexiblecoreswithwireendsleevesareinsert-e
2ContentsVEGABAR 87 • 4 … 20 mA45507-EN-131010Contents1 About this document1.1 Function ...
205 Connecting to power supplyVEGABAR 87 • 4 … 20 mA45507-EN-1310105.5 External housing with version IP 68 (25 bar)Fig. 13: VEGABAR 87 in IP 68 versi
215 Connecting to power supplyVEGABAR 87 • 4 … 20 mA45507-EN-1310101234634125Fig. 15: Connection of the sensor in the housing base1 Brown2 Blue3 Ye
225 Connecting to power supplyVEGABAR 87 • 4 … 20 mA45507-EN-131010Then the actual measured value is outputted to the signal cable. The value takes al
236 Set up with the display and adjustment moduleVEGABAR 87 • 4 … 20 mA45507-EN-1310106 Set up with the display and adjustment module6.1 Insert disp
246 Set up with the display and adjustment moduleVEGABAR 87 • 4 … 20 mA45507-EN-1310101 2Fig. 18: Insertion of the display and adjustment module into
256 Set up with the display and adjustment moduleVEGABAR 87 • 4 … 20 mA45507-EN-131010 – Save value• [->] key: – Presentation, change measured valu
266 Set up with the display and adjustment moduleVEGABAR 87 • 4 … 20 mA45507-EN-1310104. Position correctionInthismenuitemyoucompensatetheinue
276 Set up with the display and adjustment moduleVEGABAR 87 • 4 … 20 mA45507-EN-131010Setup: Settings, e.g., for measurement loop name, application, u
286 Set up with the display and adjustment moduleVEGABAR 87 • 4 … 20 mA45507-EN-131010If you have connected noslavesensor,youconrmthiswith&quo
296 Set up with the display and adjustment moduleVEGABAR 87 • 4 … 20 mA45507-EN-131010If with the automatic position correction, the actual measured v
3ContentsVEGABAR 87 • 4 … 20 mA45507-EN-1310109.2 Diagnosis memory ...
306 Set up with the display and adjustment moduleVEGABAR 87 • 4 … 20 mA45507-EN-13101021100%0%2 m(78.74")Fig. 20: Parameter adjustment example mi
316 Set up with the display and adjustment moduleVEGABAR 87 • 4 … 20 mA45507-EN-131010If the adjustment ranges are exceeded, then the entered value wi
326 Set up with the display and adjustment moduleVEGABAR 87 • 4 … 20 mA45507-EN-131010Ifalinearizationcurveisselected,themeasuringsignalisno
336 Set up with the display and adjustment moduleVEGABAR 87 • 4 … 20 mA45507-EN-131010The following languages are available:• German• English• French•
346 Set up with the display and adjustment moduleVEGABAR 87 • 4 … 20 mA45507-EN-131010The respective min. and max. measured values of the measuring ce
356 Set up with the display and adjustment moduleVEGABAR 87 • 4 … 20 mA45507-EN-131010With a reset, certain parameter adjustments carried out by the u
366 Set up with the display and adjustment moduleVEGABAR 87 • 4 … 20 mA45507-EN-131010Menu item Parameter Default valueCurrent output Current output -
376 Set up with the display and adjustment moduleVEGABAR 87 • 4 … 20 mA45507-EN-131010• The menu items "Reset, Date/Time" in the menu "
386 Set up with the display and adjustment moduleVEGABAR 87 • 4 … 20 mA45507-EN-131010In menu item "Current output, adjustment" you can assi
396 Set up with the display and adjustment moduleVEGABAR 87 • 4 … 20 mA45507-EN-131010• All data of the menu "Setup" and "Display"
41 About this documentVEGABAR 87 • 4 … 20 mA45507-EN-1310101 About this document1.1 FunctionThis operating instructions manual provides all the infor
407 Setup with PACTwareVEGABAR 87 • 4 … 20 mA45507-EN-1310107 Setup with PACTware7.1 Connect the PC312Fig. 21: Connection of the PC directly to the
417 Setup with PACTwareVEGABAR 87 • 4 … 20 mA45507-EN-131010Fig. 22: Example of a DTM viewAll device DTMs are available as a free-of-charge standard v
428 Set up with other systemsVEGABAR 87 • 4 … 20 mA45507-EN-1310108 Set up with other systems8.1 DD adjustment programsDevice descriptions as Enhanc
439 Diagnosis, asset management and serviceVEGABAR 87 • 4 … 20 mA45507-EN-1310109 Diagnosis, asset management and service9.1 MaintenanceIf the instru
449 Diagnosis, asset management and serviceVEGABAR 87 • 4 … 20 mA45507-EN-131010the following tables there are more detailed error messages available
459 Diagnosis, asset management and serviceVEGABAR 87 • 4 … 20 mA45507-EN-131010CodeText mes-sageCause RecticationF013no measured value avail-able –
469 Diagnosis, asset management and serviceVEGABAR 87 • 4 … 20 mA45507-EN-131010CodeText mes-sageCause RecticationF265Measurement function dis-turbed
479 Diagnosis, asset management and serviceVEGABAR 87 • 4 … 20 mA45507-EN-131010CodeText mes-sageCause RecticationM501Error in the non-active lineari
489 Diagnosis, asset management and serviceVEGABAR 87 • 4 … 20 mA45507-EN-131010Error Cause Rectication4 … 20 mA signal missing – Electrical con-nect
499 Diagnosis, asset management and serviceVEGABAR 87 • 4 … 20 mA45507-EN-131010• FT:Thermalchangeofzerosignalandoutputspan• FKl: Deviation• F
52 For your safetyVEGABAR 87 • 4 … 20 mA45507-EN-1310102 For your safety2.1 Authorised personnelAll operations described in this operating instructi
509 Diagnosis, asset management and serviceVEGABAR 87 • 4 … 20 mA45507-EN-13101012534Fig. 24: VEGABAR 87 in IP 68 version, 25 bar and lateral cable ou
519 Diagnosis, asset management and serviceVEGABAR 87 • 4 … 20 mA45507-EN-131010Ordering and exchange are possible with or without sensor serial numbe
5210 DismountingVEGABAR 87 • 4 … 20 mA45507-EN-13101010 Dismounting10.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process co
5311 SupplementVEGABAR 87 • 4 … 20 mA45507-EN-13101011 Supplement11.1 Technical dataMaterials and weightsMaterials, wetted partsProcesstting 316LTr
5411 SupplementVEGABAR 87 • 4 … 20 mA45507-EN-131010Straining clamp 0.2 kg (0.441 lbs)Threadedtting 0.4 kg (0.882 lbs)Input variableAdjustmentAdjust
5511 SupplementVEGABAR 87 • 4 … 20 mA45507-EN-131010Nominal range Overload capacity, max. pressureOverload capacity, min. pres-sure0 … +5 psig +435 ps
5611 SupplementVEGABAR 87 • 4 … 20 mA45507-EN-131010Damping (63 % of the input variable), adjustable0 … 999 sDynamic behaviour outputRun-up time appro
5711 SupplementVEGABAR 87 • 4 … 20 mA45507-EN-131010Accuracy class Non-linearity, hysteresis and re-peatability with TD 1 : 1 up to 5 : 1Non-linearity
5811 SupplementVEGABAR 87 • 4 … 20 mA45507-EN-1310100,15 %-0,15 %-40°C -20°C20°C40°C 60°C 80°CFig. 26: Thermal change, current outputLong-term stabili
5911 SupplementVEGABAR 87 • 4 … 20 mA45507-EN-131010Process conditionsProduct temperature Ʋ Suspension cable -12 … +100 °C (+10 … +212 °F) Ʋ Connectio
62 For your safetyVEGABAR 87 • 4 … 20 mA45507-EN-131010radiated emissions must be taken into account, as is usual with a class A instrument according
6011 SupplementVEGABAR 87 • 4 … 20 mA45507-EN-131010Electromechanical data - version IP 68 (25 bar)Connection cable between IP 68 instrument and exter
6111 SupplementVEGABAR 87 • 4 … 20 mA45507-EN-131010Integrated clockDate format Day.Month.YearTime format 12 h/24 hTimezoneExfactory CETRate deviat
6211 SupplementVEGABAR 87 • 4 … 20 mA45507-EN-131010Housing material Version IP-protection class NEMA protectionStainless steel, investment castingSin
6311 SupplementVEGABAR 87 • 4 … 20 mA45507-EN-131010Housing~ 69 mm(2.72")ø 79 mm(3.11")112 mm(4.41")M20x1,5/½ NPT~ 116 mm(4.57")11
6411 SupplementVEGABAR 87 • 4 … 20 mA45507-EN-131010External housing with IP 68 version1234582 mm(3.23")80 mm(3.15")108 mm(4.25")41,6 m
6511 SupplementVEGABAR 87 • 4 … 20 mA45507-EN-131010VEGABAR 871 2 3 4175 mm(6.89")52 mm(2.05")197 mm(7.76")ø 8 mm(0.32") ø 29 mm(
6611 SupplementVEGABAR 87 • 4 … 20 mA45507-EN-131010VEGABAR87,angeconnectionDN PN Dkb. .2540 115 18 85A8 40 40 150 18 110B2 50 40 16520 125d24xø14
6711 SupplementVEGABAR 87 • 4 … 20 mA45507-EN-131010VEGABAR87,hygienicttingø 78 mm (3.07")ø 92 mm (3.62")51 mm(2.01")L51 mm(2.01&qu
6811 SupplementVEGABAR 87 • 4 … 20 mA45507-EN-13101011.3 Industrial property rightsVEGA product lines are global protected by industrial property rig
69INDEXVEGABAR 87 • 4 … 20 mA45507-EN-131010INDEXAAdjust Date/Time 34Adjustment – Level 30, 31 – Menu 26 – Overview 29 – System 25 – Unit 28Adju
73 Product descriptionVEGABAR 87 • 4 … 20 mA45507-EN-1310103 Product description3.1 CongurationThenameplatecontainsthemostimportantdatafori
70NotesVEGABAR 87 • 4 … 20 mA45507-EN-131010
71NotesVEGABAR 87 • 4 … 20 mA45507-EN-131010
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany45507-EN-131010All statements concerning scope of delivery, application, practi
83 Product descriptionVEGABAR 87 • 4 … 20 mA45507-EN-131010This operating instructions manual applies to the following instrument versions:• Hardware
93 Product descriptionVEGABAR 87 • 4 … 20 mA45507-EN-131010The VEGABAR 87 is a pressure transmitter for pressure and level measurements of liquids wit