inoutLevel and PressureOperating InstructionsVEGACOM 557Profibus DPon557BAPC
10 VEGACOM 557 Profibus DP1.5 Technical dataPower supplySupply voltage Unom= 24 V AC (20 … 53 V), 50/60 Hz or= 24 V DC (20 … 72 V)Power consumption ap
VEGACOM 557 Profibus DP 11Product description1)Repeater = line amplifier2)Baud rate is automatically adjustedProfibus DP interface (RS 485)Standards c
12 VEGACOM 557 Profibus DPProduct descriptionCE conformityVEGACOM 557 meets the protective regulations of EMC (89/336/EWG) and NSR(73/23/EWG). The con
VEGACOM 557 Profibus DP 132 3 4ON1Basic boardDIL switchon additional boardAdditionalboardDIL switchon basic boardSide view of VEGACOM 557Special funct
14 VEGACOM 557 Profibus DPd b z1a c3c3c11a275791517192123252711132931VEGALOG cardInterface cardVEGACOM 5572 Mounting and electricalconnection2.1
VEGACOM 557 Profibus DP 152.2 Mounting in carrier and housingBGT 596 or BGT LOG 571For mounting, a slot module must be pro-vided at the location. A sl
16 VEGACOM 557 Profibus DPMounting and electrical connectionMultiple plug (rear of VEGACOM 557)Supply voltageGND ( )DISBUS (notused on VEGA-LOG)Profib
VEGACOM 557 Profibus DP 17Mounting and electrical connectionMounting instructions for VEGACOM557APThe two modules connected to the back-panel print co
18 VEGACOM 557 Profibus DPMounting and electrical connectionTerminalsfor supply voltageTerminalsfor DISBUSView of back-panel board (rear of the carrie
VEGACOM 557 Profibus DP 192 3 4ON1AdditionalboardDIL switchon basic boardDIL switchbelow additionalboardBasic boardSide view of VEGACOM 5573 Switch se
2 VEGACOM 557 Profibus DPContentsContentsSafety i nformation ... 2Note E x a rea
20 VEGACOM 557 Profibus DPDIL-switch block(Additional board)ON3.2 Adjustment of the Profibus DPinterfaceA 8-pole DIL switch block as well as two hooks
VEGACOM 557 Profibus DP 21Switch adjustments on VEGACOM 557Hook switches additional boardThe hook switches are used to switch on thebus terminator res
22 VEGACOM 557 Profibus DP4 Measurement loop in VEGAMET/VEGALOGGenerally a measurement loop in VEGAMET/VEGALOG processing systems is structured asfoll
VEGACOM 557 Profibus DP 234.1 PC/DCS outputMax. 255 PC/DCS outputs are available,depending on the processing system. Theconfiguration or parameter set
24 VEGACOM 557 Profibus DPLimitation of measured valuesParameter setting of the scalingParameter setting PC/DCS outputsMeasurement loop in VEGAMET/VEG
VEGACOM 557 Profibus DP 255 Transfer of measured valueAs DP norm slave, the VEGACOM 557 DPgateway is either configured with 50 Byteconsistent input da
26 VEGACOM 557 Profibus DP6 Operating mode VEGACOM 557Operating mode VEGACOM 557Two different operating modes ar e availablefor VEGACOM 557.Depending
VEGACOM 557 Profibus DP 27Selection of the operating mode in HW-Config of the Simatic-Manager for S7 systemsSelection of the operating mode in COM PRO
28 VEGACOM 557 Profibus DPData image in VEGACOM 5577 Data image in VEGACOM 557all measured valuesof VEGAMET #2Grouping of measured values acc. to VEGA
VEGACOM 557 Profibus DP 29Data image in VEGACOM 557Enquiry of measured value from the DP Master with control command 0xCC to DISBUSIn the 2 Byte outpu
VEGACOM 557 Profibus DP 3Contents4 Measurement loop in VEGAMET/VEGALOG4.1 PC/DCS output ...
30 VEGACOM 557 Profibus DPeeeeBlock no.(dec)2333333313131VEGAMETwith DISBUSaddress 15Case 2:Only instruments of VEGAMET 513, 514, 515or series 600 are
VEGACOM 557 Profibus DP 31Control command 0xCB (DISBUS)In case of an enquiry with this control command, the measured values are grouped acc. toDCS ind
32 VEGACOM 557 Profibus DPMeas. valueAdd. infoImage of measured value when connecting to DISBUS with grouping acc. to PC/DCSindices (control command 0
VEGACOM 557 Profibus DP 33Image of the contact inputs/outputs on the DISBUS in mode 50E2ABeside the previously described measured values, it is possib
34 VEGACOM 557 Profibus DPData image in VEGACOM 557Note:A complete overview of the process image of the switching status of VEGACOM 557 is givenin sup
VEGACOM 557 Profibus DP 35Data image in VEGACOM 557Measured value image DISBUS in mode 6E6AIn this operating mode, it is possible to read out the PC/D
36 VEGACOM 557 Profibus DPImage of the contact inputs/outputs on DISBUS in mode 6E6ABeside the previously described individual PC/DCS measured values,
VEGACOM 557 Profibus DP 37The meaning of the individual bits is defined as follows:Status of the inputs (EK):0 = all inputs OK1 = input status not ava
38 VEGACOM 557 Profibus DP7.2 Measured value image whenconnecting to LOGBUSVEGALOG 571 can manage up to 255 meas-urement loops. For the transmission o
VEGACOM 557 Profibus DP 39Grouping of measured values acc. to PC/DCS outputnumber on LOGBUSBlock no. PC/DCS outputs-no.1 1...82 9...163 17...244
4 VEGACOM 557 Profibus DPProduct description1 Product description1.1 ApplicationThe VEGACOM 557 is an efficient and easy-to-use interface converter (G
40 VEGACOM 557 Profibus DPData image in VEGACOM 557Image of the contact outputs on LOGBUSBeside the previously described measured values, also the swi
VEGACOM 557 Profibus DP 41Note:A complete overview of the process image ofthe VEGACOM 557 measured values is givenin supplement B at the end of this m
42 VEGACOM 557 Profibus DPMeasured value image LOGBUS in mode 6E6AIn this operating mode, the PC/DCS values can be read out individually in VEGACOM 55
VEGACOM 557 Profibus DP 43Data image in VEGACOM 557Image of the contact outputs on LOGBUS in mode 6E6ABeside the previously described individual PC/DC
44 VEGACOM 557 Profibus DPFormat of the answering telegram for contact outputs on LOGBUS6 ByteByte1 Byte2 Byte3 Byte4 Byte5 Byte6The meaning of the in
VEGACOM 557 Profibus DP 457.3 Overview of the operating modes and control commandsIn the table below, you will find all operating modes and contr ol c
46 VEGACOM 557 Profibus DPSetup8 Setup8.1 Setup check listFor the setup of VEGACOM 557 on PROFI-BUS DP proceed as follows:I. Check hardware requiremen
VEGACOM 557 Profibus DP 47Integration of the GSD fileThe GSD file of VEGACOM 557 must beintegrated so that the VEGACOM 557 ap-pears in the instrument
48 VEGACOM 557 Profibus DPProviding of input and output addresses for VEGACOM 557SetupLengthOperating mode input section (Byte) Output section (Byte)
VEGACOM 557 Profibus DP 49Setup8.3 Setup SIEMENS S5 with IM308CIn this case, the DP-Master is the communi-cation processor IM308C from SIEMENS,which c
VEGACOM 557 Profibus DP 5VVOonPCVEGALOG571!PCVEGACOM557!BAonVVOonVEGAMET513!ESC OK-+100%CONNECTPCVEGACOM557!BAonProduct descriptionVEGACOM 557 as DISB
50 VEGACOM 557 Profibus DP9 Parameter adjustment via Profibus DPVEGACOM 557 also provides the option of enquiring and modifying different parameters o
VEGACOM 557 Profibus DP 5110 Utility diskette for VEGACOM 557 Profibus DPOn the supplied utility diskette you will find two files, a self-unpacking „
52 VEGACOM 557 Profibus DPComplete overview of the data image of measured values in VEGACOM557:Supplem. ASupplement A3...8 0x01 DCS 1 - - - - - -9...1
VEGACOM 557 Profibus DP 53Supplement A3...8 0x29 DCS 41 - - - 0x83 MET8, CH3 MET8, DCS39...14 0x2A DCS 42 - - - 0x93 MET9, CH3 MET9, DCS315...20 0x2B
54 VEGACOM 557 Profibus DPSupplement A3...8 0x51 DCS 81 0x51 - MET5, DCS1 - - -9...14 0x52 DCS 82 0x52 - MET5, DCS2 0x16 - MET1, DCS615...20 0x53 DCS
VEGACOM 557 Profibus DP 55Supplement A3...8 0x79 DCS 121 - - - - - -9...14 0x7A DCS 122 - - - - - -15...20 0x7B DCS 123 - - - - - -21...26 0x7C DCS 12
56 VEGACOM 557 Profibus DPSupplement A3...8 0xA1 DCS 161 0xA1 - MET10, DCS1-- -9...14 0xA2 DCS 162 0xA2 - MET10, DCS2-- -15...20 0xA3 DCS 163 0xA3 - M
VEGACOM 557 Profibus DP 57Supplement A3...8 0xF1 DCS 241 0xF1 -MET15, DCS1 - - -9...14 0xF2 DCS 242 0xF2 -MET15, DCS2-- -15...20 0xF3 DCS 243 0xF3 -ME
58 VEGACOM 557 Profibus DPComplete overview of the process image of switching conditions inVEGACOM 557:Supplement BSupplement B7 Status output contac
VEGACOM 557 Profibus DP 59Supplement B7 Status output contacts Status input contacts6- -5- -4- -3- -2- -1 Output contact 10 Input contact 20 Output co
6 VEGACOM 557 Profibus DPonPCVEGALOG571!PCVEGACOM557!BAonononVEGAMET513!ESC OK-+100%CONNECTonVEGAMET513!ESC OK-+100%CONNECTonVEGAMET513!ESC OK-+100%CO
60 VEGACOM 557 Profibus DPSupplement B7 Status output contacts Status input contacts6- -5- -4- -3- -2- -1 Output contact 10 Input contact 20 Output co
VEGACOM 557 Profibus DP 61Supplement B7 Status output contacts Status input contacts6- -5- -4- -3- -2- -1 Output contact 10 Input contact 20 Output co
62 VEGACOM 557 Profibus DPSupplement B7 Status output contacts Status input contacts6- -5- -4- -3- -2- -1 Output contact 10 Input contact 20 Output co
VEGACOM 557 Profibus DP 63Supplement B7 Status output contacts Status input contacts6- -5- -4- -3- -2- -1 Output contact 10 Input contact 20 Output co
64 VEGACOM 557 Profibus DPSupplement B7 Status output contacts Status input contacts6- -5- -4- -3- -2- -1 Output contact 10 Input contact 20 Output co
VEGACOM 557 Profibus DP 65Supplement B7 Status output contacts Status input contacts6- -5- -4- -3- -2- -1 Output contact 10 Input contact 20 Output co
66 VEGACOM 557 Profibus DPSupplement B7 Status output contacts -6- -5- -4- -3- -2- -1 Output contact 10 -0 Output contact 9 -7 Output contact 8 -6 Out
VEGACOM 557 Profibus DP 67Supplement B7 Status output contacts -6- -5- -4- -3- -2- -1 Output contact 10 -0 Output contact 9 -7 Output contact 8 -6 Out
68 VEGACOM 557 Profibus DPSupplement B7 Status output contacts -6- -5- -4- -3- -2- -1 Output contact 10 -0 Output contact 9 -7 Output contact 8 -6 Out
VEGACOM 557 Profibus DP 69Supplement B7 Status output contacts -6- -5- -4- -3- -2- -1 Output contact 10 -0 Output contact 9 -7 Output contact 8 -6 Out
VEGACOM 557 Profibus DP 7Function VEGACOM 557Product descriptionDISBUSLOGBUSProfibusDPBuffermemoryProc-essimageEmis-sionmemoryTestconver-sionVEGACOM 5
70 VEGACOM 557 Profibus DPSupplement B7 Status output contacts -6- -5- -4- -3- -2- -1 Output contact 10 -0 Output contact 9 -7 Output contact 8 -6 Out
VEGACOM 557 Profibus DP 71Supplement B7 Status output contacts -6- -5- -4- -3- -2- -1 Output contact 10 -0 Output contact 9 -7 Output contact 8 -6 Out
72 VEGACOM 557 Profibus DPSupplement B7 Status output contacts -6- -5- -4- -3- -2- -1 Output contact 10 -0 Output contact 9 -7 Output contact 8 -6 Out
VEGACOM 557 Profibus DP 73Supplement B7 Status output contacts -6- -5- -4- -3- -2- -1 Output contact 10 -0 Output contact 9 -7 Output contact 8 -6 Out
74 VEGACOM 557 Profibus DPSupplement CSupplement C1 General information on PROFIBUSNote:This chapter is an excerpt of the PNO documentation PROFIBUS,
VEGACOM 557 Profibus DP 75Supplement CBasic properties of Profibus FMS andProfibus DPPROFIBUS determines the technical andfunctional properties of a s
76 VEGACOM 557 Profibus DPSupplement CTherefore, the Profibus bus access proce-dure includes the T oken-Passing procedurefor communication among compl
VEGACOM 557 Profibus DP 77Supplement C2 Special information onProfibus DPProfibus DP is designed for quick data ex-change on the sensor/actuator level
78 VEGACOM 557 Profibus DPEach Pr ofibus DP system consists of dif fer-ent instrument types. Depending on theirindividual tasks, the instruments can b
VEGACOM 557 Profibus DP 79Profibus DP multimaster systemDP Master (DPM2)PLCProfibus DPActor Sensordecentralised inputs and outputsDP SlavesSeveral Mas
8 VEGACOM 557 Profibus DPonVEGAMET513!ESC OK-+100%CONNECTonVEGAMET513!ESC OK-+100%CONNECTonVEGAMET513!ESC OK-+100%CONNECTonVEGAMET513!ESC OK-+100%CONN
80 VEGACOM 557 Profibus DPSync and Freeze modeIn addition to the participant-related usefuldata traffic, handled automatically by theDPM1, it is possi
VEGACOM 557 Profibus DP 81Supplement C10 km1,2 km1 km100 m30 m15 m100 1 k 10 k 20 k 100 k1 M Bit/s 10 MRS 422-ARS 485 RS 232-CDistanceTransmission rat
82 VEGACOM 557 Profibus DPNotes
VEGACOM 557 Profibus DP 83Notes
ISO 9001The statements on types, application, use and operating conditions ofthe sensors and processing systems correspond to the latest informa-tion
VEGACOM 557 Profibus DP 91.4 Type plate and order codeType plateBefore mounting and electrical connection,please check if you are using the correctver