Technical Data
KLD2-GT-DP.1PA
096765_ENG.xml 2003-02-27
Supply
Connection Power Rail or terminals +, -, FE
Rated voltage 20 ... 35 V DC
Ripple ≤ 10 %
Rated current 138 mA ... 84 mA (without load)
Power loss 3 W
Fieldbus connection
Profibus DP 1 RS485 interface
Connection 9-pin sub-D socket
Baudrate 45,45 kBit/s ... 12 MBit/s
Protocol PROFIBUS DP V1
Connection to power link
Connection Power Rail or terminals CH1+ at 28+, CH1- at 29- of KLD2-PL1.PA
Power Rail or terminals CH1+ at 40+, CH1- at 41- of KLD2-PL-Ex1.PA
Baudrate 31,25 kBit/s
Electrical isolation
CH/PROFIBUS DP function insulation, rated insulation voltage 50 V
eff
PROFIBUS DP/Supply function insulation, rated insulation voltage 50 V
eff
All circuits/FE function insulation, rated insulation voltage 50 V
eff
Standard conformity
Electrical isolation EN 50178
Electromagnetic compatibility NAMUR NE 21
Protection degree IEC/EN 60529
Fieldbus standard EN 50170/2
Climatic conditions DIN IEC 721
Directive conformity
Electromagnetic compatibility standards
Directive 89/336/EG EN 61326, EN 50081-2
Ambient conditions
Classification 3K3
Ambient temperature -20 ... 60 °C (253 ... 333 K)
Relative humidity < 75 %
Degree of soiling max. 2, according to IEC 664
Mechanical specifications
Connection type terminals
Core cross-section
up to 2.5 mm
2
Housing 60 mm x 115 mm x 107 mm
Protection degree IP20
Mass 600 g
Mounting DIN rail mounting
Data for application in conjunction with
hazardous areas
Statement of conformity TÜV 02 ATEX 1819 X
Group, category, type of protection,
Temperature classification
¬ II 3 G EEx nA II T4
Connection to power link Connection to the data interface CH of KLD2-PL-Ex1.PA (Konf. TÜV 00 ATEX 1531X)
Connection to the data interface CH of KLD2-PL-1.PA (Konf. TÜV 00 ATEX 1788X)
Directive conformity standards
Directive 94/9 EU EN 50021
Operating principle
Together with at least one power link, the gateway forms a segment coupler for connecting a PROFIBUS PA segment to the PROFIBUS DP.
The PROFIBUS is standardised to EN 50 170/2. The gateway supports all transfer rates thus defined up to 12 MBit/s.
The gateway can make one, two or four channels available. The channels work completely independently of each other in terms of time. This
makes it possible to reduce response times considerably. Up to 5 power links can be connected to each channel, of which each forms its own
PROFIBUS PA segment.
Communication between the gateway and the power links takes place over the power rail for Channel 1 and over the terminals for the other
channels.
The communication process is transparent. Each PA station is addressed directly and planning for them is like a PROFIBUS DP station. The
planning does not include the gateway and power links.
The gateway can be mounted in Zone 2. Power Links are also permitted for this type of installation.
Version KLD2-GT-DPR.xPA allows for operation with a redundant transmission line on the PROFIBUS DP side.
The channels work directly at 31.25 kBaud (Manchester coded). This saves additional delay times in the power links.
For additional information, please consult the segment coupler manual/operating instructions (Part. No. 105085).