Operating InstructionsDifferential pressure transmitter with metallic measuring diaphragmVEGADIF 65Foundation FieldbusDocument ID: 36130
103 Product descriptionVEGADIF 65 • Foundation Fieldbus36130-EN-130417Dierentialpressuremeasurement+21Fig. 5: Dierential pressure measurement wit
113 Product descriptionVEGADIF 65 • Foundation Fieldbus36130-EN-130417A metallic measuring cell is used as sensor element. The process pressuresaret
123 Product descriptionVEGADIF 65 • Foundation Fieldbus36130-EN-130417• viaaLinkingdevicewithHSE(HighspeedEthernet)andaddi-tionalpowersupp
133 Product descriptionVEGADIF 65 • Foundation Fieldbus36130-EN-130417Uptothetimeofinstallation,thepackagesmustbeleftclosedandstored acco
143 Product descriptionVEGADIF 65 • Foundation Fieldbus36130-EN-130417chambers.Thisallowsthezeropointofthepressuretransmittertobeadjusted.
154MountingVEGADIF 65 • Foundation Fieldbus36130-EN-1304174 Mounting4.1 General instructions to use the instrumentMakesurethatallpartsofthein
164MountingVEGADIF 65 • Foundation Fieldbus36130-EN-130417DetailedinstructionsformountingtheDPowelementarestatedinDINENISO5167aswell
174MountingVEGADIF 65 • Foundation Fieldbus36130-EN-130417+ –21Fig. 11: Marking for plus/minus side on the process component1 Plus side2 Minus side
184MountingVEGADIF 65 • Foundation Fieldbus36130-EN-130417during the setup. Thanks to the valve block it is possible to dismount theVEGADIF65witho
194MountingVEGADIF 65 • Foundation Fieldbus36130-EN-130417A:A1 23 452 213 45Fig. 14: Connection of a 3-fold valve block, anging on both sides1 Proc
2ContentsVEGADIF 65 • Foundation Fieldbus36130-EN-130417Contents1 About this document1.1 Function ...
204MountingVEGADIF 65 • Foundation Fieldbus36130-EN-130417A:A1 2435 7 89 62 23 194 67 85Fig. 15: Connection of a 5-fold valve block1 Process tting2
214MountingVEGADIF 65 • Foundation Fieldbus36130-EN-130417+–1243Fig. 16: Measurement setup with ow measurement of gases, connection via 3-fold valve
224MountingVEGADIF 65 • Foundation Fieldbus36130-EN-130417+–12335564Fig. 18: Measurement setup, ow measurement in vapours1 Condensate vessels2 Ori
234MountingVEGADIF 65 • Foundation Fieldbus36130-EN-130417+ – 1 2 2 35 5 6 4 4 Fig. 19: Measurement setup, ow measurement in liquids1 Orice or
244MountingVEGADIF 65 • Foundation Fieldbus36130-EN-1304171. MountVEGADIF65directlytothevessel2. Minussideisopentotheatmosphericpressu
254MountingVEGADIF 65 • Foundation Fieldbus36130-EN-1304171. MountVEGADIF65directlytothevessel2. Connectminussidealwaysabovethemax.lev
264MountingVEGADIF 65 • Foundation Fieldbus36130-EN-1304174. Formeasurementsinproductswithsolidcontentsuchase.g.dirtyliquids,theinstall
274MountingVEGADIF 65 • Foundation Fieldbus36130-EN-130417+ – min. max. 12345+ –Fig. 26: Measurement setup in closed vessel with superimposed steam1
284MountingVEGADIF 65 • Foundation Fieldbus36130-EN-130417Themax.adjustmentiscarriedoutforthedierentialpressuremeas-ured at density 1.2:Δp
294MountingVEGADIF 65 • Foundation Fieldbus36130-EN-1304171+–0,3 m0,81,0Fig. 28: Measurement setup with interface measurement4.7 Measurementsetupd
3ContentsVEGADIF 65 • Foundation Fieldbus36130-EN-1304177 Operating with PACTware and other adjustment programs7.1 Connect the PC via VEGACONNECT ..
304MountingVEGADIF 65 • Foundation Fieldbus36130-EN-1304171233564 4Fig. 30: Measurement setup with dierential pressure measurement between a vapour
314MountingVEGADIF 65 • Foundation Fieldbus36130-EN-1304171. Mountchemicalsealwithcapillariesontoporlaterallyonthepipeline2. Invacuuma
324MountingVEGADIF 65 • Foundation Fieldbus36130-EN-130417Mountthewallmountingplatesothatthecableentryofthesockethousingpointsdownward
335ConnectingtopowersupplyVEGADIF 65 • Foundation Fieldbus36130-EN-1304175 Connecting to power supply5.1 Preparing the connectionAlwayskeepin
345ConnectingtopowersupplyVEGADIF 65 • Foundation Fieldbus36130-EN-130417lowfrequencypotentialequalisationcurrentsarethussuppressed,butth
355ConnectingtopowersupplyVEGADIF 65 • Foundation Fieldbus36130-EN-130417Fig. 34: Connection steps 6 and 7Proceedasfollows:1. Loosenthefours
365ConnectingtopowersupplyVEGADIF 65 • Foundation Fieldbus36130-EN-130417Information:The cable gland can be mounted in three positions each displa
375ConnectingtopowersupplyVEGADIF 65 • Foundation Fieldbus36130-EN-130417I2CDisplay112 5 678Fig. 37: Wiring plan, single chamber housing1 Voltage
385ConnectingtopowersupplyVEGADIF 65 • Foundation Fieldbus36130-EN-1304175.5 Double chamber housing Ex d1212Fig. 40: Connection compartment, Ex-d
395ConnectingtopowersupplyVEGADIF 65 • Foundation Fieldbus36130-EN-1304175.7 External housing with version IP 68I²CDisplayTyp:12 5678BusSim.45612
41 About this documentVEGADIF 65 • Foundation Fieldbus36130-EN-1304171 About this document1.1 FunctionThis operating instructions manual provides all
405ConnectingtopowersupplyVEGADIF 65 • Foundation Fieldbus36130-EN-130417I2CDisplay112 5 678Fig. 45: Wiring plan external electronics1 Voltage su
416AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • Foundation Fieldbus36130-EN-1304176 Adjustment with the display and adjust
426AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • Foundation Fieldbus36130-EN-130417Fig. 46: Insert display and adjustment mo
436AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • Foundation Fieldbus36130-EN-130417 – Save value• [->] key to select: – M
446AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • Foundation Fieldbus36130-EN-130417▶Basic adjustmentDisplayDiagnosticsServic
456AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • Foundation Fieldbus36130-EN-1304172. Conrmthemenu"Basic adjustmen
466AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • Foundation Fieldbus36130-EN-130417OsetDP=-0.0035 bar0.0000 bar4. Moveto
476AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • Foundation Fieldbus36130-EN-1304171. Editthe%valueinthemenuitem&qu
486AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • Foundation Fieldbus36130-EN-130417Foranadjustmentwithlling,simplyent
496AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • Foundation Fieldbus36130-EN-130417value.Thelimitvalueis50%.Thisfunc
52 For your safetyVEGADIF 65 • Foundation Fieldbus36130-EN-1304172 For your safety2.1 Authorised personnelAll operations described in this operating
506AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • Foundation Fieldbus36130-EN-130417Thefollowingdataarereadoutorwritte
516AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • Foundation Fieldbus36130-EN-130417Peak valueThe min. and max. temperature o
526AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • Foundation Fieldbus36130-EN-130417Basicadjustmentow▶Basic adjustment 1Di
536AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • Foundation Fieldbus36130-EN-130417DiagnosticsBasic adjustment 3Display▶Diag
546AdjustmentwiththedisplayandadjustmentmodulePLICSCOMVEGADIF 65 • Foundation Fieldbus36130-EN-1304176.12 Saving the parameter adjustment dat
557OperatingwithPACTwareandotheradjustmentprogramsVEGADIF 65 • Foundation Fieldbus36130-EN-1304177 Operating with PACTware and other adjustmen
567OperatingwithPACTwareandotheradjustmentprogramsVEGADIF 65 • Foundation Fieldbus36130-EN-1304177.2 Parameter adjustment with PACTwareFurther
578 SetupVEGADIF 65 • Foundation Fieldbus36130-EN-1304178 Setup8.1 Select the modeThefollowingoperatingmodescanbesetonVEGADIF65:• Flowmeasu
588 SetupVEGADIF 65 • Foundation Fieldbus36130-EN-130417+–III+67324Fig. 51: Prefered measurement setup for gases, connection via 3-fold valve block,
598 SetupVEGADIF 65 • Foundation Fieldbus36130-EN-130417Forthispurpose,openvalvesA,B(ifavailable)aswellas2,4:MediumowsinIfnecessary,
62 For your safetyVEGADIF 65 • Foundation Fieldbus36130-EN-1304172.6 CE conformityThedevicefulllsthelegalrequirementsoftheapplicableECguid
608 SetupVEGADIF 65 • Foundation Fieldbus36130-EN-130417Fig. 53: Preferred measurement setup for open vesselsI VEGADIF 65II Separator1 Drain valve6.
618 SetupVEGADIF 65 • Foundation Fieldbus36130-EN-130417+AB6732415+–IIIIIIIIIFig. 54: Preferred measurement setup for closed vesselsI VEGADIF 65II 3
628 SetupVEGADIF 65 • Foundation Fieldbus36130-EN-130417+AB6732415+–IIIIIIIIIIVFig. 55: Preferred measurement setup for closed vessels with steam over
638 SetupVEGADIF 65 • Foundation Fieldbus36130-EN-130417Then carry out adjustment, see chapter "Set parameters".8.4 Density and interface m
648 SetupVEGADIF 65 • Foundation Fieldbus36130-EN-130417AB+1567+–243IIIIIIIIIFig. 57: Preferred measurement setup for liquidsI VEGADIF 65II 3-fold v
658 SetupVEGADIF 65 • Foundation Fieldbus36130-EN-130417Valves 2 and 4 are openValves A and B open (if present)Then carry out adjustment, see chapter
669MaintenanceandfaultrecticationVEGADIF 65 • Foundation Fieldbus36130-EN-1304179 Maintenanceandfaultrectication9.1 MaintenanceIftheinstru
679MaintenanceandfaultrecticationVEGADIF 65 • Foundation Fieldbus36130-EN-130417Error Cause RecticationInstrument does not appear during connect
689MaintenanceandfaultrecticationVEGADIF 65 • Foundation Fieldbus36130-EN-1304179.5 Software updateThesoftwareversionofVEGADIF65canbedet
699MaintenanceandfaultrecticationVEGADIF 65 • Foundation Fieldbus36130-EN-130417Bydoingthisyouhelpuscarryouttherepairquicklyandwithou
73 Product descriptionVEGADIF 65 • Foundation Fieldbus36130-EN-1304173 Product description3.1 CongurationThe scope of delivery encompasses:• VEGADI
7010 DismountingVEGADIF 65 • Foundation Fieldbus36130-EN-13041710 Dismounting10.1 Dismounting stepsWarning:Beforedismounting,beawareofdangerous
7111 SupplementVEGADIF 65 • Foundation Fieldbus36130-EN-13041711 Supplement11.1 Technical dataGeneral dataPressure typeDierentialpressureMeasuring
7211 SupplementVEGADIF 65 • Foundation Fieldbus36130-EN-130417Max.torquescrewsmountingstrap 30 NmMax.torquescrewssocketexternalhousing5 Nm (3
7311 SupplementVEGADIF 65 • Foundation Fieldbus36130-EN-130417 Ʋ acyclically approx. 50 msDamping(63%oftheinputvariable) 0…999s,adjustableAd
7411 SupplementVEGADIF 65 • Foundation Fieldbus36130-EN-130417 Ʋ Temperature +18…+30°C(+64…+86°F) Ʋ Relativehumidity 45…75% Ʋ Air pressure
7511 SupplementVEGADIF 65 • Foundation Fieldbus36130-EN-130417Measuringcells≥500mbar Ʋ Turndown1:1to15:1 ±0.075%ofthesetspan+inuen
7611 SupplementVEGADIF 65 • Foundation Fieldbus36130-EN-130417Measuring cell 10 mbar 30 mbar 100 mbar 500 mbarInuenceofthesys-tem pressure to the
7711 SupplementVEGADIF 65 • Foundation Fieldbus36130-EN-130417Diaphragm material Measuring range Total ErrorTantalum<500mbar 0.48%ofthemeasur
7811 SupplementVEGADIF 65 • Foundation Fieldbus36130-EN-130417Seal material Temperature limitsFKM,cleaned -10…+85°C(+14…+185°F)FKM,foroxygen
7911 SupplementVEGADIF 65 • Foundation Fieldbus36130-EN-130417 Ʋ Single chamber housing – 1xcableglandM20x1.5(cable:ø5…9mm),1xblindpl
83 Product descriptionVEGADIF 65 • Foundation Fieldbus36130-EN-130417211211536478910Fig. 2: Layout of the type label (example)1 Instrument version2
8011 SupplementVEGADIF 65 • Foundation Fieldbus36130-EN-130417Electromechanical data - version IP 66/IP 68 with external electronicsConnectioncableb
8111 SupplementVEGADIF 65 • Foundation Fieldbus36130-EN-130417Electrical protective measuresProtection rating Ʋ Housing,standard IP 66/IP 67 Ʋ Alumin
8211 SupplementVEGADIF 65 • Foundation Fieldbus36130-EN-130417Secondary_value_2scale_in_0 scale_in_100Sensor_value0 %100 %bar0,500-0,5000 %100 %scale_
8311 SupplementVEGADIF 65 • Foundation Fieldbus36130-EN-130417 – XandYvaluesfortheuserdenedlinearizationcurve• curve_points_11_20 – XandY
8411 SupplementVEGADIF 65 • Foundation Fieldbus36130-EN-130417• max_peak_temperature_value – Holdsthemaximumprocesstemperature.Writeaccessreset
8511 SupplementVEGADIF 65 • Foundation Fieldbus36130-EN-130417Stainless steel housing~ 69 mm(2.72")ø 79 mm(3.11")117 mm (4.61")M20x1,5/
8611 SupplementVEGADIF 65 • Foundation Fieldbus36130-EN-130417External housing with version IP 6812+ –68,3 mm(2.69")103 mm(4.06")93 mm(3.66&
8711 SupplementVEGADIF 65 • Foundation Fieldbus36130-EN-130417+ –1268,3 mm(2.69")103 mm(4.06")93 mm(3.66")115 mm(4.53")ø 55 mm(2.1
8811 SupplementVEGADIF 65 • Foundation Fieldbus36130-EN-130417Ovalange,connection¼-18NPTorRC¼41,3 mm (1.63")85 mm(3.35")134,5 mm (5.
8911 SupplementVEGADIF 65 • Foundation Fieldbus36130-EN-130417Version Connection Fastening Material Scope of delivery21/4-18 NPT IEC 61518PN160:M10,
93 Product descriptionVEGADIF 65 • Foundation Fieldbus36130-EN-130417Flow measurementQQp1p1p2p2Q~∆pQ~∆p++––1 2Fig. 3: Flow measurement with VEGADIF 65
9011 SupplementVEGADIF 65 • Foundation Fieldbus36130-EN-130417Ovalange,preparedforchemicalsealconnection2372 mm(2.84")128 mm (5.04")9
9111 SupplementVEGADIF 65 • Foundation Fieldbus36130-EN-13041711.4 Industrial property rightsVEGA product lines are global protected by industrial pr
92INDEXVEGADIF 65 • Foundation Fieldbus36130-EN-130417INDEXAAccessories – Display and adjustment module 13 – External display and adjustment unit 13
93INDEXVEGADIF 65 • Foundation Fieldbus36130-EN-130417 – 3-foldvalveblock,angingonbothsides18 – Introduction 17WWEEE directive 70Wiring pla
94NotesVEGADIF 65 • Foundation Fieldbus36130-EN-130417
95NotesVEGADIF 65 • Foundation Fieldbus36130-EN-130417
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany36130-EN-130417All statements concerning scope of delivery, application, practi