Operating InstructionsPressure transmitter with ceramic measuring cellVEGABAR 824 … 20 mA/HARTDocument ID: 45028
103 Product descriptionVEGABAR 82 • 4 … 20 mA/HART45028-EN-13101012453Fig. 3: Recessed installation of the CERTEC® measuring cell1 Measuring cell2 S
113 Product descriptionVEGABAR 82 • 4 … 20 mA/HART45028-EN-13101012345Fig. 6: Hygienic installation of the CERTEC® measuring cell1 Measuring cell2 F
123 Product descriptionVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310103.4 Accessories and replacement partsThe display and adjustment module PLICSCOM is u
133 Product descriptionVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010Youcanndfurtherinformationinthesupplementaryinstructions"PLICSMOBILE G
144 MountingVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310104 Mounting4.1 General instructions to use the instrumentMake sure that all parts of the instrum
154 MountingVEGABAR 82 • 4 … 20 mA/HART45028-EN-13101012Fig. 7: Temperature ranges1 Process temperature2 Ambient temperature4.2 Ventilation and pre
164 MountingVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310101 2 3666 6654Fig. 8: Position of the lter element - non-Ex, Ex-ia and Ex-d-ia version1 Single
174 MountingVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010213434Fig. 9: Position of the lter element - Ex-d version1 Single chamber housing, aluminium,
184 MountingVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310101Fig. 11: Position of the lter element - IP 69K version1 Filter elementInstruments with absolu
194 MountingVEGABAR 82 • 4 … 20 mA/HART45028-EN-13101014321234Fig. 13: Measurement setup with process pressure measurement of gases in pipelines1 VEG
2ContentsVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010Contents1 About this document1.1 Function ...
204 MountingVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010312Fig. 14: Measurement setup for process pressure measurement of liquids in pipelines1 VEGABAR
214 MountingVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310104.5 External housing12345Fig. 16: Setup process assembly, external housing1 Process assembly2
225 Connecting to power supplyVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310105 Connecting to power supply5.1 Preparing the connectionAlways keep in mind
235 Connecting to power supplyVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010In electroplating and CCP systems (cathodic corrosion protection) it mustbet
245 Connecting to power supplyVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010Fig. 19: Connection steps 5 and 6 - Double chamber housing6. Insert the wire
255 Connecting to power supplyVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010512+( )(-)6784...20mA2341Fig. 20: Electronics and connection compartment, sin
265 Connecting to power supplyVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310104...20mA2312+( )(-)1Fig. 22: Connection compartment, double chamber housing1
275 Connecting to power supplyVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310105.5 Double chamber housing Ex d56784...20mA212+( )(-)11Fig. 25: Electronics
285 Connecting to power supplyVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310105.6 Double chamber housing Ex d ia567812+( )(-)3124...20mAFig. 27: Electroni
295 Connecting to power supplyVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310105.7 Double chamber housing with DIS-ADAPT312Fig. 29: View to the electronics
3ContentsVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310108 Set up with other systems8.1 DD adjustment programs ...
305 Connecting to power supplyVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310105.9 External housing with version IP 68 (25 bar)123Fig. 32: VEGABAR 82 in IP
315 Connecting to power supplyVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310101234634125Fig. 34: Connection of the sensor in the housing base1 Brown2 Blue
325 Connecting to power supplyVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010Then the actual measured value is outputted to the signal cable. The value tak
336 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310106 Set up with the display and adjustment module6.1 Insert
346 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310101 2Fig. 37: Insertion of the display and adjustment module
356 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010 – Save value• [->] key: – Presentation, change measured
366 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310104. Position correctionInthismenuitemyoucompensatethe
376 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010Setup: Settings, e.g., for measurement loop name, applicati
386 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010If you have connected noslavesensor,youconrmthiswith
396 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010If with the automatic position correction, the actual measu
41 About this documentVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310101 About this document1.1 FunctionThis operating instructions manual provides all the
406 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010If these values are not known, an adjustment with levels of
416 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310102. Edit the mbar value with [OK] and set the cursor to the
426 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310102. Edit the percentage value with [OK] and set the cursor
436 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010On instrumdents with integrated 2. current output, the prop
446 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010• French• Spanish• Russian• Italian• Dutch• Portuguese• Pol
456 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010In another window you can carry out a reset of the two peak
466 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010The following reset functions are available:Delivery status
476 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010Menu item Parameter Default valueLock adjustment ReleasedRe
486 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010The copied data are permanently saved in the display and ad
496 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010ThesensoroerstheHARTmodes"Analogue current outp
52 For your safetyVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310102 For your safety2.1 Authorised personnelAll operations described in this operating inst
506 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310106.5 Saving the parameter adjustment dataWe recommended not
517 Setup with PACTwareVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310107 Setup with PACTware7.1 Connect the PC312Fig. 40: Connection of the PC directly to
527 Setup with PACTwareVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310107.2 Parameter adjustmentFor parameter adjustment of the sensor via a Windows PC, the
537 Setup with PACTwareVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010The standard version is available as a download under www.vega.com/downloads and &qu
548 Set up with other systemsVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310108 Set up with other systems8.1 DD adjustment programsDevice descriptions as E
559 Diagnosis, asset management and serviceVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310109 Diagnosis, asset management and service9.1 MaintenanceIf the i
569 Diagnosis, asset management and serviceVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010the following tables there are more detailed error messages avail
579 Diagnosis, asset management and serviceVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010CodeText mes-sageCause RecticationF013no measured value avail-ab
589 Diagnosis, asset management and serviceVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010CodeText mes-sageCause RecticationF265Measurement function dis-t
599 Diagnosis, asset management and serviceVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010CodeText mes-sageCause RecticationM501Error in the non-active li
62 For your safetyVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010radiated emissions must be taken into account, as is usual with a class A instrument accor
609 Diagnosis, asset management and serviceVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010Error Cause Rectication4 … 20 mA signal missing – Electrical con
619 Diagnosis, asset management and serviceVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010• FT:Thermalchangeofzerosignalandoutputspan• FKl: Deviati
629 Diagnosis, asset management and serviceVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010Caution:The exchange may only be carried out in the complete abse
639 Diagnosis, asset management and serviceVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010In Ex applications, only instruments and electronics modules with
6410 DismountingVEGABAR 82 • 4 … 20 mA/HART45028-EN-13101010 Dismounting10.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous proce
6511 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-13101011 Supplement11.1 Technical dataMaterials and weightsMaterials, wetted partsProcesstting 3
6611 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010Input variableAdjustmentAdjustment range of the min./max. adjustment relating to the nominal
6711 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010Nominal range Overload capacity, max. pressureOverload capacity, min. pres-sure0 … 0.1 bar/0
6811 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010Nominal range Overload capacity, max. pressureOverload capacity, min. pres-sure0 … 5 psi 435
6911 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010Dynamic behaviour outputRun-up time approx. 10 sDynamic characteristics, depending on medium,
73 Product descriptionVEGABAR 82 • 4 … 20 mA/HART45028-EN-1310103 Product description3.1 CongurationThenameplatecontainsthemostimportantdata
7011 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010Deviation (according to IEC 60770)Applies to the digitalsignaloutput(HART,ProbusPA,Fou
7111 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010Nominal measuring range in bar/kPaNominal measuring range in psigIn the compensated temperatu
7211 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010Long-term drift of the zero signalTime pe-riodMeasuring cell ø 28 mm Measuring cell ø 28 mmMe
7311 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010Measuring cell seal Product temperature - standard versionProduct temperature - version with
7411 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010Wire cross-section (spring-loaded terminals) Ʋ Massive wire, cord 0.2 … 2.5 mm² (AWG 24 … 14)
7511 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010 Ʋ Sizeofdigits W x H = 7 x 13 mmAdjustment elements 4 keysProtection rating Ʋ unassembled
7611 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010 Ʋ for UN 12 V DC (9.6 V< UB < 14 V) ≤0.7Ve(16…400Hz) Ʋ for UN 24 V DC (18 V<
7711 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010Plastic housing~ 69 mm(2.72")ø 79 mm(3.11")112 mm(4.41")M20x1,5/½ NPT~ 84 mm(3
7811 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010Aluminium housing in protection rating IP 66/IP 68 (1 bar)120 mm(4.72")~ 105 mm(4.13&quo
7911 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010Stainless steel housing in protection rating IP 66/IP 68 (1 bar)117 mm(4.61")~ 103 mm(4.
83 Product descriptionVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010This operating instructions manual applies to the following instrument versions:• Hard
8011 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010External housing with IP 68 version1234582 mm(3.23")80 mm(3.15")108 mm(4.25")4
8111 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010VEGABAR82,threadedttingnotfront-ushDD DLDUC2DQDIG½ G¼ G½ G¼ SW 27 mm(1.06")G½23 m
8211 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010VEGABAR82,threadedttingfront-ushC1C322 mm(0.87")44 mm(1.73")ø 24 mm (0.95&quo
8311 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010VEGABAR82,hygienicttingARAAESFR EZ/E1 E350 mm(1.97")51 mm(2.01")51 mm(2.01"
8411 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010VEGABAR82,angeconnection3.46"4.02"5.43" 0.12" 0.12" 0.12"
8511 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010VEGABAR82,extensionttingF1 F2AF/AGF9ø 32...60 mm(1.26...2.36")ø 48...90 mm(1.89...3.
8611 SupplementVEGABAR 82 • 4 … 20 mA/HART45028-EN-13101011.3 Industrial property rightsVEGA product lines are global protected by industrial propert
87INDEXVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010INDEXAAdjust Date/Time 45Adjustment – Level 41 – Menu 36 – Process pressure 40 – System 35 – Uni
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany45028-EN-131010All statements concerning scope of delivery, application, practi
93 Product descriptionVEGABAR 82 • 4 … 20 mA/HART45028-EN-131010• Absolute pressure• VacuumMeasured products are gases, vapours and liquids.Depending